3. ACP operation by using the LG ACCS

Installation/Owner's Manual

3-9

ENGLISH

Current  & desired temperature

Item

Icon

Description

The current air conditioner is at the peak operation
ratio control status.

The current air conditioner performs the artificial
intellitent operation. The artificial intelligent operation is
the automatic operation for the air conditioner by itself
to set and operate the operation mode and the air flow
of the air conditioner according to the room
temperature.

Error status

The current air conditioner has the error occurred.

The error caused by the network is occurred.

The temperature of the space where the air conditioiner is installed is displayed at the current
temperature. However, if the error lamp is turned ON, the number of the current temperature does not
display the temperature, but the error code.

The desired temperature set at the air conditioner is displayed at the desired temperature. The desired
temperature is not displayed if the air conditioner performs the ventilation or the dehumidification
operatioin or at the error condition.

Normal operation

Summary of Contents for PQCPA11A0E

Page 1: ...ww lg com AIR CONDITIONER Please read this manual carefully before operating your set and retain it for future reference TYPE Advanced Control Platform MODEL PQCPA11A0E PQCPB11A0E INSTALLATION OWNER S MANUAL ENGLISH êìëëäàâ üáõä ...

Page 2: ... controller 2 9 Setting the address by the wireless remote controller 2 10 Setting the PI485 and Connecting the cable 2 12 Setting the PI485 DIP switch 2 12 Connecting the 2PIN connector 2 14 Connceting RS485 cable to PI485 2 16 Installing the ACP and Connecting the cable 2 19 Fixing the ACP at the installation site 2 19 Connecting RS485 cable to ACP 2 20 Connecting Ethernet cable to ACP 2 23 Conn...

Page 3: ...2 49 If the ACP is connected to the AC Manager 2 49 If the ACP is not connected to the AC Manager 2 50 Making sure and checking the ACP installation 2 67 Accessing the ACCS 3 1 Reviewing the initial ACCS screen 3 4 Controlling the air conditioner 3 7 Controlling the ventilator 3 14 Setting the schedule 3 21 Reviewing the schedule setup screen 3 21 Example for setting the schedule 3 32 Controlling ...

Page 4: ...lation occurred by the installation work without the installation certification for which our company does not offer the free of charge service Using the product ignoring the note for safety may cause the misoperation of the product which may cause the body s injury or the damage of the product The note for safety is classified into two following items The symbols used at this manual have the foll...

Page 5: ...NK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DO 1 2 3 4 Consult the service center or the professional installation agency about reinstalling the installed product The non professional may cause electric shock explosion or injury The flammable gas or the combustible substance such as gasoline benzene and thinner should not ...

Page 6: ...ET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DO 1 2 3 4 Do not let water flow into the product It may cause electric shock and failure Do not put heavy weight on the power cord It may cause fire or electric shock Do not put heavy weight on the product It may cause the failure of the product LG NET...

Page 7: ...RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DO 1 2 3 4 LG NET 1 MENU SELECT TX RX LG NET 2 TX RX LG NET 3 TX RX LG NET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DO 1 2 3 4 Do not use strong detergent suc...

Page 8: ...t each room of the building from the place such as the control room of a building the administrative room of a school Main functions of the ACP are as follows Using the external button of the ACP to set the environment The following functions can be set by using the external buttons of the ACP Set the network environment IP address net mask gateway Set one of Peak Demand function to use Set the la...

Page 9: ...ACP Especially when using the schedule feature of the AC Manager because the ACP has its own engine even though the user turns off the PC where the AC Manager is installed the ACP can perform the schedule featre by itself LG NET 1 MENU SELECT TX RX LG NET 2 TX RX LG NET 3 TX RX LG NET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 ...

Page 10: ...the building are used together the airconditioner can be controlled more easily Simple central controller Central control address Central control address ON L1 2 3 4 KSDO4H PI485 ON L1 2 3 4 KSDO4H Multi V Multi V PI485 00 0 0 0 1 0 F 0 0 0 1 0 F LG NET 1 MENU SELECT TX RX LG NET 2 TX RX LG NET 3 TX RX LG NET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX...

Page 11: ...work environment setting and other information RS485 communication port for PI485 connection RS485 communication port connecting to the PI485 to connect the airconditioner and the ventilator 4EA in total RS485 communication port for external extension RS485 communication port spar for exter extension 2EA in total Ethernet port for connecting the Internet and the AC Manager The Ethernet port for co...

Page 12: ...QCPA11A0E model a separate IO Kit Model PQCPE11A0E can be purchased and installed to use for connecting the external signal 1 ACP Functions Specification Reset switch Switch for resetting the ACP by the software Power switch Switch for turning on off the ACP Adaptor connection port Port for DC 12V to connect the adaptor supplying the power External input signal terminal Port for connecting the ext...

Page 13: ...1 2 3 4 180mm 250mm 57mm 273mm 237mm ACP Advanced Control Platform Adaptor for Power supply Input 100 240V AC 50 60Hz 1 5A Output DC 12V 3 33A 40W MAX Power Cord International Standard IEC320 C14 Type ACP Installation Owner s Manual Notice In Australia purchase the power code In Australia the power code from local area The power code is not included in the package Caution Using the standardized pa...

Page 14: ...hernet port for Internet connectioin 1EA 10Base T Spare 1EA For the PQCPB11A0E model the following ports are supplied as default External input port 20EA Pulse contable DC 12V External output port 4EA Relay output 5V For the PQCPA11A0E model the IO Kit PQCPE11A0E should be separately purchased for connecting the above port LED 20EA for displaying RS communication status Ethernet communication stat...

Page 15: ...the ACP not overlapped with the connecting indoor unit and connect the PI485 STEP 3 Install the ACP and set the environment and the function Install the ACP and set the network environment and the function STEP 4 ACCS access and Information input Set the access environment at the LG ACCS the ACP operation program and enter the air conditioner information STEP 5 Make sure and check the ACP installa...

Page 16: ...m number of units for the ACP to connect But in order to improve the communication performce of the RS485 we recommend to distribute them to four ports By considering three following cases using the ACP perform the installation after carefully considering how to use Install the single ACP to use as web server Connect the single ACP to the AC Manager to use Connect more than one ACP to the AC Manag...

Page 17: ...3 4 KSDO4H ON L1 2 3 4 KSDO4H 00 01 02 10 30 31 32 33 11 12 Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 PI485 Multi 20 21 22 LG NET 1 MENU SELECT TX RX LG NET 2 TX RX LG NET 3 TX RX LG NET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DO 1 2 3 4 ACP Simple central c...

Page 18: ...T TX RX LG NET 2 TX RX LG NET 3 TX RX LG NET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DO 1 2 3 4 ACP Simple central controller possible to connect when necessary 2 Installing ACP Not using the hub If it is connected without the hub the network can be configured as shown at the following example ...

Page 19: ... 2 3 4 KSDO4H ON L1 2 3 4 KSDO4H 00 01 02 10 30 31 32 33 11 12 Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 PI485 Multi 20 21 22 LG NET 1 MENU SELECT TX RX LG NET 2 TX RX LG NET 3 TX RX LG NET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DO 1 2 3 4 ACP AC Manager Si...

Page 20: ...Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 PI485 Multi 20 21 22 LG NET 1 MENU SELECT TX RX LG NET 2 TX RX LG NET 3 TX RX LG NET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DO 1 2 3 4 ACP AC Manager Simple central controller possible to connect when necessary LAN ...

Page 21: ...e following examples Simple central controller possible to connect when necessary Simple central controller possible to connect when necessary ON L1 2 3 4 KSDO4H Multi V 00 01 02 10 11 12 20 21 22 30 31 32 Multi V PI485 PI485 PI485 Multi V ON L1 2 3 4 KSDO4H ON L1 2 3 4 KSDO4H ACP ACP AC Manager Hub LAN Direct cable ON L1 2 3 4 KSDO4H PI485 Multi Connecting more than on ACPs to the AC Manager ...

Page 22: ...ecimal can be set to the indoor unit address The next section describes how to set the address to each indoor unit by using the wired or wireless remote controller according to the given number The following example sets the address to the indoor unit When the ACP is interconnected with the AC Manager the ventilator can be together installed and controlled The above figure shows the example that s...

Page 23: ... 07 09 11 13 15 17 19 21 23 Plasma Program Set Ctl 1 Press Week Program Set Clr keys at the same time 2 Set the indoor unit address using the temperature controller Allowed Range 00 FF 3 Complete the address setting to press the week Program Set Clr keys at the same time for 3 seconds Some remote controllers may not be suported by above functions a coording to the production date of wired wireless...

Page 24: ...ss the Operate Stop button once toward the indoor unit 4 When the set address is displayed on the indoor unit the address setting is complete 5 When you reset the remote controller it switches from the address setting mode to general operation mode Setting address with wireless remote controller Reference Address display time and method The address display time and method may differ by the type of...

Page 25: ...roceed as follows 1 With the Wind Up Down button pressed press the RESET button The Wind Up Down button must be pressed for more than 3 seconds 2 Press the Operate Stop button once toward the indoor unit The set address will be shown on the display part of the indoor unit The address display time and method can differ by the type of indoor unit 3 Reset the remote controller again to use it in gene...

Page 26: ...O N K S D O 4 H Dip switch Setting Product type 1 4 ON Multi V product CRUN LRA product excluded 2 3 OFF MPS product with the common PCB applied MPS inverter product 2 4 ON MPS product with the common PCB not applied 1 3 OFF 1 2 3 4 ON Multi V CRUN LRA product 3 4 ON Single indoor unit connected to the PI485 for the indoor unit Ventilator connected to the PI485 for ventilating O N K S D O 4 H O N ...

Page 27: ... more than the LED03G If the LED is abnormally different from the above description check again the indoor unit address setting and the DIP switch setting ON L1 2 3 4 KSDO4H O N K S D O 4 H LED03G LED02G LED01G Note PCB part number The MPS product with the common PCB applied has the following PCB part number PCB P NO 6871A20910A Z PCB P NO 6871A20917A Z PCB P NO 6871A20918A Z Caution Setting the P...

Page 28: ...nnector If you want to use the individual lock function for setting mode wind flow and temperature lock by the central control the 2PIN connector should be connected to the CN_DRY terminal of the PI485 according to the product type ON L1 2 3 4 KSDO4H ...

Page 29: ...ion 20 C setting high fan level temperature lock through the central control the applicable command is transmitted through the remote controller HL Hard Lock message showing the central control status is displayed on the remote controller If the user sets the temperature to 25 C the command is blocked at the remote controller 3 Heating 25C Strong wind 4 Heating 20C Strong wind ON L1 2 3 4 KSDO4H M...

Page 30: ... ACP two RS485 cables should be connected to the BUS_A and the BUS_B of the PI485 Connect the RS485 cables by referring to the following figure When connecting more than one PI485 to one ACP connect the BUS_A BUS_B of the PI485 to the BUS_A BUS_B of the other PI485 respectively ON L1 2 3 4 KSDO4H ...

Page 31: ...10V GND BUS_A BUS_B ON L1 2 3 4 KSDO4H ON L1 2 3 4 KSDO4H ON L1 2 3 4 KSDO4H 10V GND BUS_A BUS_B 10V GND BUS_A BUS_B LG NET 1 MENU SELECT TX RX LG NET 2 TX RX LG NET 3 TX RX LG NET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DO 1 2 3 4 ACP TX RX ...

Page 32: ...t the DIP switch No 1 of the simple central controller to OFF slave and No 2 to ON LGAP mode CN POWER GND CN COM A S4 S3 S12 S16 TX1 LED4 LED8 LED12 LED11 LED16 LED15 PWB 6870A10001A ASM 6711A20005E LED7 LED3 L S15 S18 S19 S15 S11 S2 LED2 S5 S9 S1 IC1P LED5 LED9 LED13 LED17 LED10 LED14 S14 S6 S10 CN POWER CN COM B ON L1 2 3 4 KSDO4H ON L1 2 3 4 KSDO4H C D GND RS485 RS485 RS485 S19 LED13 LED17 LED1...

Page 33: ...lowing description Here the installation method of the ACP is described with the example installing the ACP at the wall 1 Decide the space to install the ACP Before installing the ACP check whether the place is suitable for connecting the ACP and the RS485 cable 2 Use the screw driver to fix them at the wall It can be fixed as shown at the following figure according to the installation place Fixin...

Page 34: ... be connected to the ACP to the TX Next connect the end of the RS485 cable connecting to the BUS_B of the PI485 to the RX 2 The RS485 cable connecting to the PI485 to the LG NET port RS485 port of the ACP Connect the connector connecting the RS485 cable to one of the ports LG NET1 LG NET4 The number of LG NET ports is 1 4 and it is possible to connect to any of them to use Connecting RS485 cable t...

Page 35: ... the malfunction The following figure shows the example for separately connecting the LG NET1 and the LG NET2 with the BUS form Simple central controller Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 ON L1 2 3 4 KSDO4H LG NET 1 MENU SELECT TX RX LG NET 2 TX RX LG NET...

Page 36: ...PI485 ON L1 2 3 4 KSDO4H Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 ON L1 2 3 4 KSDO4H Multi V PI485 ON L1 2 3 4 KSDO4H LG NET 1 MENU SELECT TX RX LG NET 2 TX RX LG NET 3 TX RX LG NET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DO 1 2 3 4 ACP TX RX ...

Page 37: ... cable Use the Ethernet cable cross cable to connect to the Ethernet 1 port of the ACP LG NET 1 MENU SELECT TX RX LG NET 2 TX RX LG NET 3 TX RX LG NET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DO 1 2 3 4 1 ACT LNK 2 ACT LNK e n er TX RX TX RX Connecting to the hub Direct cable Connecting to the AC...

Page 38: ...18 19 20 DO 1 2 3 4 K Console Run Power TX RX Connecting Power adaptor to ACP After connecting the Ethernet cable the power adaptor should be connected for supplying the power to the ACP 1 Connect the power adaptor supplied with the ACP product to the power adaptor connection port of the ACT as shown at the below figure 2 After connecting the power adaptor connect the power cord connected to the p...

Page 39: ... ACP information and the menu are displayed at the LCD and the menu can be changed and selected by pressing MENU SELECT button and Up Down Left Right buttons Beforing configuring the ACP environment LG NET 1 MENU SELECT TX RX LG NET 2 TX RX LG NET 3 TX RX LG NET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18...

Page 40: ...etwork environment of the ACP When the power switch is turned on the ACP booting screen is displayed on the LCD as shown at the below figure and when booting is completed the initial ACP screen is displayed LG Electronics Wait for booting ACP SW ver 2 77 2 ACP booting screen Initial ACP screen After booting Note Software version The software version of the current ACP is displayed at the initial A...

Page 41: ...n below MENU SELECT MENU fi Set IP Address MENU fi Set IP Address Ƣ MENU fi Set GW Address MENU fi Set Update Svr MENU fi Set Netmask MENU fi Set PeakDemand MENU fi Set Language MENU fi Set PDI MENU fi Set SCH MENU fi Set Log MENU Information Error record display setting Menu to display the set network Info Set the consumed power display function Set Schedule function Select Peak or Demand Select ...

Page 42: ... down button MENU SELECT Set IP Address 192 168 000 000 Set IP Address 192 167 000 000 MENU SELECT Set IP Address 192 168 000 000 Set IP Address 192 168 000 000 Set IP Address 192 168 000 000 Set IP Address 192 148 000 000 Cannot be set Possible to set after setting the next digit to less than or equal to 4 When pressing the right button Also in order the sum of three numbers not to exceed 255 the...

Page 43: ...LECT Click MENU SELECT button Example to set IP address Set IP Address 192 168 002 101 MENU SELECT ACP SW ver 2 77 2 MENU SELECT MENU fi Set IP Address Set IP Address 192 168 000 000 MENU SELECT Click MENU SELECT button Example to set IP address Set IP Address 192 168 002 101 MENU SELECT ACP SW ver 2 77 2 2 Use Up Down Left Right button to enter the desired IP address 3 After entering the IP addre...

Page 44: ...ECT MENU Set GW Address Set GW Address 192 168 000 000 MENU SELECT Click MENU SELECT button Example to set Gateway address Set GW Address 165 186 002 001 MENU SELECT ACP SW ver 2 77 2 2 Use Up Down Left Right button to enter the desired gateway address 3 After entering the gateway address press the MENU SELECT button to set the entered gateway address But there is no MENU SELECT button pressed for...

Page 45: ... is displayed MENU SELECT MENU Set Netmask Set Netmask 192 168 000 000 MENU SELECT Click MENU SELECT button Example to set Netmask address Set Netmask 255 255 255 000 MENU SELECT ACP SW ver 2 77 2 2 Use Up Down Left Right button to enter the desired net mask address 3 After entering the netmask address press the MENU SELECT button to set the entered netmask address But there is no MENU SELECT butt...

Page 46: ...t button to display the following Information screen Press the MENU SELECT button again The currently set network information can be checked Each different information is displayed on the LCD screen about every 3 seconds It is displayed as follows MENU SELECT MENU Information MAC Address 001B 1987 7B14 1023 Click MENU SELECT button MAC Address 001B 1987 7B14 1023 IP Address 165 168 002 101 Netmask...

Page 47: ...nction of the ACP should be set and used as follows Before setting the functions of the ACP ACP only ACP interconnected with AC Manager ACP interconnected with Demand controller Set to Peak function Set to Demand function Set to Demand function Set the schedule Set the schedule Set the schedule function to use function not to use function to use Set to use if interconnected woth the wattmeter or s...

Page 48: ...the total target wattage One of these methods can be selected and used at the ACP And if it is set by the menu of the ACP the UI screen is differently displayed when accessing the web screen to set the function The ACP should be set to the Demand function for the following cases Interconnecting with the Demand Controller of the professional Demand control company Interconnecting with the AC Manage...

Page 49: ...ethod 3 When the MENU SELECT button is pressed the set wattage control method is applied to the system But there is no MENU SELECT button pressed for a specific period about 5 seconds it returns to the initial screen with the set control method not applied to the system and the existing set method is used MENU SELECT Example for setting Demand to use Set PeakDemand PK 0 DMD 1 1 MENU SELECT ACP SW ...

Page 50: ...e LG ACCS is offered with the Korean version and the English version which can be changed by the user s setting Change the language setting of the LG ACCS as follows 1 Press the MENU SELECT button of the ACP and then press Left Right button to display the following language setup screen Press the MENU SELECT button again The screen to set the display language is displayed MENU SELECT MENU Set Lang...

Page 51: ...he MENU SELECT button is pressed the set display language is applied to the system But there is no MENU SELECT button pressed for a specific period about 5 seconds it returns to the initial screen with the set display language not applied to the system and the existing set method is used MENU SELECT Example for setting the LG ACCS to display in English MENU SELECT ACP SW ver 2 77 2 Set Language KR...

Page 52: ...the ACP to automatically operate at the specified time Whether to use the schedule function at the ACP or not should be set Set whether to use the schedule function as follows 1 Press the MENU SELECT button of the ACP and then press Left Right button to display the following schedule function setup screen Press the MENU SELECT button again The screen to set whether to use the schedule function or ...

Page 53: ...ssed whether to use the schedule function or not is applied to the system But there is no MENU SELECT button pressed for a specific period about 5 seconds it returns to the initial screen with the setting not applied to the system and the existing set method is used MENU SELECT ACP SW ver 2 77 2 ...

Page 54: ...ether to use the wattage display interconnection function as follows Set whether to use the wattage display interconnection function as follows 1 Press the MENU SELECT button of the ACP and then press Left Right button to display the wattage display setup screen Press the MENU SELECT button again The screen to set whether to use the wattage display or not is displayed MENU SELECT MENU Set PDI MENU...

Page 55: ... whether to use the wattage display function or not is applied to the system But there is no MENU SELECT button pressed for a specific period about 5 seconds it returns to the initial screen with the setting not applied to the system and the existing set method is used MENU SELECT ACP SW ver 2 77 2 ...

Page 56: ...utton The screen to set whether to use the error history function will be displayed 2 Use the up and down button to set whether to use the error history function When you press the up button it will be set to use the error history function and down button not to use the error history function 3 When you press the MENU SELECT button setting of whether to use the error history function will be appli...

Page 57: ...user accesses the ACP by using the Internet Explorer with no separate program installed The MS JAVA Virtual Machine should be installed for accessing the LG ACCS program of the ACP Because it is not automatically installed since the Windows XP version the user using the Windows XP or higher version should manually install the MS JAVA Virtual Machine 1 Execute Start Program Internet Explorer at the...

Page 58: ...k only the Use Java JIT Compiler system rebooting required item at the Microsoft VM item and unselect all other items If JAVA Sun item exists at Microsoft VM item and it is checked it should be unselected Caution If Microsoft Java Virtual Machine is not installed If the Java Virtual Machine of the Microsoft is not installed msjavx86 exe file should be downloaded and installed by the search site Cl...

Page 59: ...et Explorer a web browser should be changed Change the security setting of the Microsoft Internet Explorer by the following procedure Here it is described by the example changing the setting at the Windows XP operating environment 1 Execute Start Program Internet Explorer at the Windows 2 When the Internet Explorer is executed execute Tools Internet Option at the menu The Internet Option window is...

Page 60: ...ion window press Custom Level at the bottom Security setup window is displayed 4 When the Security setup window is displayed find out Microsoft VM and check Custom When Java Custom Settings button is displayed later click it Then Internet window is displayed Click Click Click Click ...

Page 61: ... Edit Right tab at the Internet window set Run Unsigned Content item to Enable Press OK button to exit Internet window 6 Press OK button at the previous Security setup window Warning window for checking the security setting is displayed Press Yes button Click Click Click Click ...

Page 62: ...2 Installing ACP ACP 2 48 7 Finally press OK button at the Internet Options window Now the security setup to use the LG ACCS is completed Click ...

Page 63: ...nding on the condition as follows When the ACP is connected to the AC Manager register the information by using the AC Manager When the ACP is not connected to the AC Manager register the information by using the LG ACCS program of the ACP When the AC Manager is installed at the specific PC to connect to the ACP the information set at the AC Manager is automatically entered into the ACP So the ACP...

Page 64: ... of the ACP you should access the LG ACCS first of all Access the LG ACCS at the PC connected to the internal network to which the Internet or the ACP can be connected as follows 1 Execute the Internet Explorer at the PC connected to tye ACP via the Internet or the internal network And then enter the IP address set at the ACP into the address window and press Enter key Note ACP access IP If you do...

Page 65: ... entered the following LG ACCS Login screen is displayed Enter the ID and the password and then click Login button Set the ID to admin and the password to digital21 for the first access to the ACP 3 When the login is successfully done the following access procedure will be executed Click Input ...

Page 66: ... ACP 2 52 4 When the login is successfully done the initial screen of the LG ACCS is displayed as shown at the below Click System setup button the last mentu The system setup screen to set the system is displayed Click ...

Page 67: ...d 3 1 Click Air conditioner setup tab at System setup menu of the LG ACCS 2 In order to set the air conditioner first of all enter the outdoor unit information group number of the air conditioner Each outdoor unit information is used as the information of the physical group connecting the indoor unit Click Outdoor unit input at System setup screen of the LG ACCS to display the window for setting t...

Page 68: ...ups to set according to the air conditioner installation plan delete all remaining outdoor units by pressing button Here because we assume that four groups in total are set and the group number is set to 0 1 2 and 3 leave only four groups as shown at the below figure Click Default input button to enter the default values Delete all outdoor units escept the outdoor units as many as the number of gr...

Page 69: ...e outdoor unit UAC Unified air conditioner it means the outdoor unit for the unitified air conditioner Model Enter the model name of the outdoor unit Maximum consumed Set the maximum wattage for the outdoor unit to consume power W 5 Enter the setting value suitable for each item When you click the item to set the related item changes to yellow whose setting value can be modified See the following ...

Page 70: ... air conditioner included at the group is also created 7 Leave the indoor units as many as the number of the air conditioners to set for each group and delete the remaining indoor units by pressing button As five indoor units of the air conditioner are connected for each group all units are deleted except five indoor units information Click Default input button to create the group s and the air co...

Page 71: ...ption Group name Enter the air conditioner group name for the user to easily recognize Enter the indoor unit type Indoor types to set are as follows UAC Unified air conditioner SGL Single type air conditioner Type Air conditioner name Enter the air conditioner name for the user to easily recognize Caution Set to UAC type The indoor unit type should be set to UAC unified air conditioner type At pre...

Page 72: ...of 0 15 If the user directly enters the physical address it can be easily entered incorrectly So Default value button should be used to enter Model name Enter the model name of the indoor unit Maximum consumed power Enter the maximum consumed power for the indoor unit to use The maximum consumed power depends on the model 9 For the remaining three groups set the number of the indoor units and the ...

Page 73: ...ual 2 59 ENGLISH 11 The saving process is performed When the air conditioner setup is successfully done the group and the air conditioner information set at present can be checked Possible to check the set group and air conditioner information ...

Page 74: ...own at the above figure the logical group can be said the set of the air conditioners connected to the same outdoor unit However the logical group can be configured even when the air conditioners at the 1st grade classrooms are connected to the different outdoor units regardless to the physical connection 2 Installing ACP ACP 2 60 ON L1 2 3 4 KSDO4H Physical group Ex three floors Logical group Ex ...

Page 75: ...ab at System setup menu of the LG ACCS 2 To set up the ventilator you must first enter the group number of the ventilator The information of each outdoor unit is used as the physical group information connecting the ventilator When you click on Enter ventilator group button in the System setting screen of LG ACCS the window to set the group number is displayed Click ʻSystem setupʼ menu And then cl...

Page 76: ...according to the installation plan of the ventilator and press button to delete all remaining outdoor units Here because two groups group number 0 and 1 are assumed to be set in total leave only two groups as shown at the below figure Click Default input button to enter the default value Leave the group s as many as the number of groups to set and delete the remaining groups ...

Page 77: ...ow and its setting value can be modified See the below table for the description on the item to set Item Description Group number Enter the number to classify the ventilator group When the number is entered through the Input default value button it is good to keep the number as it is Name Do not set up the name and keep the default value Modify the setting value for each item ...

Page 78: ...bout the ventilator included at the group is created 7 Leave the item s as many as the number of ventilators to set for each group and press button to delete all remaining ventilators Here because five ventilators are assumed to be connected to each group only five ventilator information is left and all remaining ones are deleted Press Default input button to create the groups and the ventilators ...

Page 79: ...on is pressed it is automatically created by inheriting the higher information Physical address is composed of 4 numbers The first and second number is the G W number and ventilator group number respectively This can be set only within the entered information from existing G W information and Ventilator group input menu The third number is the ventilator number which cannot be duplicated within th...

Page 80: ...ess Save button to display the window to confirm to save the setting information Press OK button to save the setting information 11 The saving process is performed When the ventilator setup is successfully done the group and the ventilator information set at present can be checked at the Ventilating menu Press Save button to the setting When the confirmation window is displayed press OK button ...

Page 81: ... the related PI485 Check the related PI485 DIP switch Check whether the indoor outdoor communication is normal or not Check the address setting of the indoor unit Are all indoor units not connected Is it not connected per outdoor unit PI485 LED02G and 03G are continuously blinking Check the PI485 model name PNF P14A1M should be used 16 or more indoor units are connected to one outdoor unit Recheck...

Page 82: ...e indoor units are deselected Insert the CN Dry into the related PI485 of the outdoor unit not the Super product Check the product number of the PI485 and replace it with the product with the function applied Chec the version of the outdoor unit and perform the program onboarding Version 33 or higher No No Is it not performed per outdoor unit No Yes Are all indoor units the Multi V super Yes Yes Y...

Page 83: ...he following procedure at the PC connecting the internal network where can be connected to the ACP 1 Execute the Internet Explorer at the PC connecting the ACP via the Internet or the internal network And enter the IP address set to the ACP into the address window and press Enter key Accessing the ACCS 3 ACP operation by using the LG ACCS Installation Owner s Manual 3 1 ENGLISH Note ACP access IP ...

Page 84: ...d the following LG ACCS Login screen is displayed Enter the ID and the password and then click Login button Set the ID to admin and the password to digital21 for the first access to the ACP 3 When the login is successfully done the following access procedure will be executed Input Click ...

Page 85: ...e LG ACCS Installation Owner s Manual 3 3 ENGLISH 4 The initial screen of the LG ACCS is displayed as shown at the below When you click the button of the function to control the screen is changed to use the related function Click ...

Page 86: ...m is the program which is automatically executed when accessing the ACP web server The user can control the indoor unit and the ventilator of the air conditioner connected to the ACP and monitor various status information by using the LG ACCS When accessing the AG ACCS the following LG ACCS program will be executed 1 2 3 4 5 ...

Page 87: ...oner for the operation ratio of the air conditioner not to exceed the setting value If this function is set to the ACP the demand power control function can not be used simultaneously Demand Set the demand power control function by monitoring the whole power of the indoor unit of the air conditioner at reat time not to exceed the target power If this function is set to the ACP the peak operation r...

Page 88: ... of the peak operation ratio control mode and the air status of the network as icon 5 Item Icon Description Displayed when the peak operation ratio control mode is being executed Peak operation ratio Displayed when the peak operation ratio control mode is being stopped No icon displayed when the peak operation ratio control is not installed Displayed when the error is occurred at the network conne...

Page 89: ...the lock the temperature control and the stop The air conditioner control function has the following advantages Manage all installed air conditioiners by using the computer screen with the central control method Easily operate and monitor Perform the integrated management by the group setup Click Air conditioner menu at the top of the LG ACCS to control the air conditioner Click Air conditioner me...

Page 90: ...r conditioners The color of the lamp displays the status of the air conditioner The color displays the air conditioner status as follows At the operation mode if the air conditioner is currently operating the operation mode is displayed as icon Operation mode Lamp color Status Description green On The current air conditioner normally operates red Blinking The current air conditioner has the error ...

Page 91: ...itioner according to the room temperature Error status The current air conditioner has the error occurred The error caused by the network is occurred The temperature of the space where the air conditioiner is installed is displayed at the current temperature However if the error lamp is turned ON the number of the current temperature does not display the temperature but the error code The desired ...

Page 92: ...onditioner group set at the ACP is displayed at Group Whe a specific air conditioner group is selected from the air conditioner group list the list of the air conditioners belonging to the related air conditioner group is displayed at Air conditioner located at the right side When the air conditioner group to select is clicked at the list the related group is selected and when it is again clicked ...

Page 93: ...ture can not be set It circulates the fresh air The ventiliation only may be used in Spring and Autumn When it is selected the desired temperature can not be set It evaluates the indoor condition and maintains the optimal condition automatically Note Setting the desired temperature Because too much cooling is harmful for health set the suitable desired temperature About 5 C is better for the diffe...

Page 94: ...onditioner When the lock function is set the air conditioner can not be controlled by the wirless or wired remote controller Use the lock function not for the user individually but to centrally control the air conditioner Icon Description It executes the air direction operation of the air conditioner It stops the air direction operation of the air conditioner Type Icon Description Control not to s...

Page 95: ...Icon Description Click Start or Stop button to start or stop the air conditioner Note When using each lock function at the Multi model When using each lock function at the indoor unit wall mounted ART COOL ART COOL Mirror model of the Multi model use the temperature lock the mode lock and the airflow lock at a time Note Changing the control setting After selecting more than one air conditioner wit...

Page 96: ...l function and the lock The ventilation control function has the following advantages It can centrally control all the installed ventilators by the computer screen It can easily operate and monitor It can perform the integrated control by the group setting Click Ventilating menu at the top of the LG ACCS for controlling the ventilator Click Ventilating menu to display the following screen for cont...

Page 97: ...yed at Ventilator located at the right side When you click the ventilating group to select from the list the related group is selected and when you click it again the related group is deselected Also more than one group can be selected together by Select Ventilating group Ventilator window The list for the ventilating group and the ventilator set at the system is displayed on this window Also the ...

Page 98: ...the status of the other ventilators can be checked by pressing or The color of the lamp displays the status of the ventilator The color displays the ventilator status as follows At the operation mode if the ventilator is currently operating the operation mode is displayed as icon The following operation modes are displayed on the screen Lamp color Status Description green On The current ventilator...

Page 99: ...ns displayed on the screen are as follows Various additional functions can be set to the ventilator The icon displays whether the additional function is set or not The additional icons displayed on the screen are as follows Icon Description Weak air flow Strong air flow Air flow at maximu Automatic air flow according to the indoor environment Icon Description Poswer saving in operation Quick funct...

Page 100: ...ontrolling Monitoring the ventilator window This window displays the information such as operation mode of each ventilator air directioin lock feature and additional function 3 Mode Description Set both the air supply and the exhaust to be ventilated via the electric heat exchanger It is used in Summer and Winter with much difference of temperature and humidity between the indoor and the outdoor S...

Page 101: ...ions can be set to the ventilator The types of additional functions to set are as follows Icon Description It performs the power saving function It finds out the best efficiency of the ventilator and operates it to save the consumed power It performs the quick ventilation It prevents the polluted air or moisture of the indoor from being dispersered to other rooms It performs the heater function It...

Page 102: ...peration Click Start or Stop button to start or stop the selected ventilator Button Description Operate the ventilator according to the set value Stop the operating ventilator Note Changing the control setting After selecting more than one ventilator with different control conditioin when the control setting of the ventilator is changed it is applied to all of the currently operating ventilators w...

Page 103: ... because it is used only when necessary Click Schedule menu at the top of the LG ACCS for setting the schedule Click Schedule menu to display the schedule setup screen as follows Reviewing the schedule setup screen Note Saving after the system setup Be careful to change the system information at System setup menu and save it because it initializes all schedule information Reference Schedule mainte...

Page 104: ... no change after applying the schedule following schedule that has been set pattern will be applied repeatedly in the following week If you save the pattern and select the right schedule before operating the schedule you can operate and apply the schedule Maximum of 10 patterns can be saved and can be utilized as shown in the following examples Pattern 1 Save schedule pattern mainly used in spring...

Page 105: ...r checking the set schedule and applying it to the system can be performed It d better use this mode except setting the schedule When Setup mode button is displayed at the bottom of the Schedule menu the current schedule is set to the setup mode At the setup mode the functions such as setting and saving the schedule can be performed but the schedule can not be applied to the system Use this mode o...

Page 106: ...ever the air conditioner group and the air conditioner located at the top of the list are not deselected because they are selected as default More than one air conditioner group or air conditioner can be selected together by clicking them However at the view mode only one group or air conditioner can be selected The list of the air conditioner group and the air conditioner set at the ACP is displa...

Page 107: ...oisture It can effectively eliminate moisture during the rainy season or at the high humidity condition When it is selected the desired temperature can not be set It circulates the fresh air The ventiliation only may be used in Spring and Autumn When it is selected the desired temperature can not be set Note Setting the desired temperature Because too much cooling is harmful for health set the sui...

Page 108: ...e lock function is set the air conditioner can not be controlled by the wirless or wired remote controller Use the lock function not for the user individually button to centrally control the air conditioner Click Lock setup button to display the window to set the Lock function When you set the Lock function and click Done button the lock function is set Air flow Air direction Air flow Description ...

Page 109: ...handle the specific date as exceptional schedule 4 It displays the operation start time and the operation stop time of the period selected from the weekly operation schedule table At the view mode the current set schedule is displayed at the schedule display window However at the setup mode the period to set the schedule can be selected One column of the display window corresponds to 10 minutes an...

Page 110: ... All set information can be saved only by clicking Save the setting button Especially if you click View mode button without pressing this button to save after setting the schedule at the setup mode the schedule information set up to now may be cancelled so be carefull Click Apply the schedule button to apply the schedule saved as pattern to the system to be performed Because applying the schedule ...

Page 111: ...tion handling button In order to exit from the exception handling schedule screen to the previous screen press Exit the exception handling button 6 When you click Exception handling schedule button the exception handling schedule screen to set the exception handling schedule is displayed At this time Exception handling schedule button is changed to Exit the exception handling button When you click...

Page 112: ...ing schedule into Title input field and click Add button the exception handling date is displayed on the screen And then when you click Save button the related setting is applied to the system In order to delete the existing setting after specifying the related data at the calendar when the exceptional schedule title to delete is displayed at Title input field click Delete button And then when you...

Page 113: ... One column of the display window corresponds to 10 minutes and at the setup mode more than one period can be deleted by clicking the set period again You can delete the priod by clicking the period again The time with the exception handling schedule set is displayed in sky blue while the period selected by clicking is displayed in green When you select the period with the exception handling sched...

Page 114: ...to the system as schedule Target group 1st grade group Time 9 11 1 3 a m Operation Cooling Air flow Middle Temperature 23 C Lock function set Saving pattern Pattern5 1 When you click Schedule menu at the LG ACCS screen the following screen is displayed Click View mode button to switch to the schedule setup mode When you click View mode button it is switched to the setup mode and the View mode butt...

Page 115: ...lick Pattern5 item at the displayed Pattern setup window and click Set button If the pattern is not selected it is saved at Pattern1 as default 3 Now select the target to which the schedule is applied Here because it is applied to all 1st grade group all air conditioners are selected by pressing Select All button Click Pattern5 and the Set button Select the group and click Select All button to spe...

Page 116: ...re 5 Set the Lock function for the user not to individually set the air conditioner When you click Lock setup button the Lock setup window to set the lock function is displayed Click Set radio button and then Done button Specify the schedule operation Cooling Middle air flow Desired temperature 23 C After clicking Lock setup button select Set at the Lock setup window Click Done button ...

Page 117: ...lect 9 11 a m and 1 3 p m from Monday to Friday by clicking or dragging 7 Now press Save the setting button to save the set schedule When you click Save the setting button the window to confirm saving is displayed Click Done button to save the schedule Specify the schedule time by clicking or dragging After elicking Save the setting button click Done button when confirming to save ...

Page 118: ...When you click Apply the schedule button the set schedule operates Apply the schedule button is changed to Cancel the schedule button Pattern setup button is displayed with the currently applied pattern number You can check the schedule by clicking the air conditioner You can check the setting by clicking the schedule Screen switched to the view mode by clicking Setup mode button It shows that the...

Page 119: ... handling title Discretional holiday Time 9 12 a m Operation Cooling Weak as air flow 25 C as temperature Total stopped time 12 00 1 When you click Exception handling schedule button at Schedule menu screen the screen to set the exception handling is displayed At this time the Exception handling schedule button is changed to Exit the exception handling to exit from setting the exception handling s...

Page 120: ... the title Discretional holiday to 2007 7 6 3 The exception schedule title is added to the list but it is not saved at the system Click Save button to save the exception handling title at the system If you do not click Save button the related information is deleted when switching to the other screen Press Save button to save the exception schedul Select the date from the calendar Enter the excepti...

Page 121: ... schedule title is displayed at Title input field and make sure that the related date is displayed at Schedule field 5 Click View mode button to switch to the schedule setup mode When you click the View mode button it is switched to the setup mode and View mode button to Setup mode button After checking the exception handling schedule from the list click the related date from the calendar Check Ti...

Page 122: ...t grade group all air conditioners are selected by pressing Select All button 7 Now specify the operation for the schedule to perform Set Cooling operation as operation Weak as air flow and 25 C as desired temperature Select the group and click Select All button to specify all Specify the schedule operation Cooling Weak air flow Desired temperature 25 C ...

Page 123: ...y the schedule At the schedule setup window at the right side of the screen select 9 12 a m by clicking or dragging 9 Set to stop all air conditioners at 12 00 Set 12 00 at Stop All item and click Done button Specify the schedule time by clicking or dragging After setting Stop All time click Done button ...

Page 124: ...schedule 11 Now press Setup mode button to switch to the view mode When you click each air conditioner name of the 1st grade you can find that the same schedule is applied to each group Also you can find wich operation is set by clicking the schedule time After clicking Save the setting button click Done button when confirming to save Screen switched to the view mode by clicking Setup mode button ...

Page 125: ... ACCS 12 When setting the exception handling schedule is completed click Exit the exception handling button to close the exception handling setup window and return to the previous schedule view screen Click Exit the exception handling button to return to the previous screen ...

Page 126: ...nconvenience due to setting the peak operation period is minimized When the air conditioner forcefully operates by the peak operation ratio control function the air conditioiner cannot be individually managed because the automatic central control is used However when the current operation uses the power less than or equal to the target operation ratio setting the air conditioner can be individuall...

Page 127: ... menu it is set for the setting of the ACP to use the demand power control function In order to use the peak power control function change the setting of the ACP by referring to Chapter 2 Setting the ACP functions Selecting Peak or Demand Caution When the peak power function is used When the peak power function is used the function should be used or set after the current information about Current ...

Page 128: ...ys the current wattage in kW Operation status Description Displayed when the current wattage is higher than the setting value of the peak operation ratio control function In this case the air conditioner operates at the condition to start or stop with the peak operation period according to the peak operation ratio control function Displayed when the peak operation ratio control function is stopped...

Page 129: ...tes Setting the current operation status and the power control graph The graph for displaying the current operation status and setting the power control function is displayed at the left side of the peak operation ratio control screen The operator can use this graph to check the power when all current installed air conditioners operate 100 and to set the target power In order to change the peak op...

Page 130: ... be set within the range of 0 100 of the maximum wattage which can be controlled by 1 When the value is set by the desired power kW is changed according to the setting value Operation switching period It sets the peak operation period It can be set within the range of 5 15 minutes which can be controlled by 1 minute Setting the power control text The setup item to set the wattage in kW or is displ...

Page 131: ... from Peak excluded air conditioner and press Apply button The related air conditioner is displayed at All air conditioners at the left side of the screen Installation Owner s Manual 3 49 ENGLISH Note Changing the setting value of the desired wattage and operation ratio The setting values of the desired wattage and the desired operation ratio are changed according to the setting of the peak exclud...

Page 132: ...opping It starts the peak operatioin ratio control function When the peak operation ratio control is being operated the button is displayed in green It stops the peak operation ratio control function When the peak operation ratio control is stopped the button is displayed in green 6 Note Setting the peak Set the peak at the peak operation condition or perform the peak operation after setting the p...

Page 133: ... control function the air conditioiner cannot be individually managed because the automatic central control is used However when the current operation uses the power less than or equal to the target operation ratio setting the air conditioner can be individually managed Note Peak operation ratio control Demand control The ACCS offers the peak operation ratio control function and the demand control...

Page 134: ...llowing air conditioner control screen is displayed Note When there is no demand menu If the ACCS menu does not have Demand menu but Peak power menu it is set for the setting of the ACP to use the peak control function In order to use the demand power function change the setting of the ACP by referring to Chapter 2 Setting the ACP functions Selecting Peak or Demand 1 2 3 ...

Page 135: ...nt air conditioner reaches Also it displays the current wattage in kW Operation status Description Displayed when the current wattage is higher than the setting value of the demand control function In this case the air conditioner operates at the condition to start or stop according to the demand control function Displayed when the demand control function is stopped Displayed when the setting valu...

Page 136: ...Operation switching period It displays the period for stopping the peak operation For example if it is set to 5 minutes period the air conditioners with the peak operation are switched every 5 minutes which controls the time for all air conditioners to stop constantly The operation switching period can be controlled within the range of 5 15 minutes Caution Setting the demand control Because the de...

Page 137: ...er operation rule 3 Desired power It displays the desired power in kW per hour to operate the peak operation function Desired operation ratio It displays the desired power in to operate the peak operation function Operation switching period It displays the period to forcefully stop the operatioin Caution Setting the demand control Because the demand control is set by the externally connected deman...

Page 138: ...ioner click Monitoring menu at the top of the LG ACCS When you click Monitoring menu the following monitoring screen is displayed The following information is displayed at the monitoring screen Item Description Air conditioner name Name of air conditioner currently registred at the system Operation mode Operation mode of set air conditioner Air flow Air force of set air conditioner Air direction W...

Page 139: ... lock function or not Room temperature The indoor temperature of the place where the current air conditioner is installed Desired temperature The desired temperature to set the indoor temperature Start Stop The operation status of the air conditioner The error code is displayed if the error is occurred Remarks Network Error NE System Error SE ...

Page 140: ...red from all indoor units of the air conditioners connected to the ACP You can see this error history at Error history menu of the LG ACCS In order to view the error history of the air conditioner click the Error history menu at the top of the LG ACCS When you click Error history menu the following error history screen is displayed 1 2 3 ...

Page 141: ...ion about the error occurred within the period is displayed Confirm to delete button is used to safely delete the error displayed at the error history list within the system After pressing button to delete the error displayed at the error history list press Confirm to delete button to completely delete the related error within the ACP If Confirm to delete button is not pressed after pressing butto...

Page 142: ... the network Error occurred from the system outdoor indoor unit Date Date when the error was occurred Time Time when the error was occurred Index Address of the indoor unit of air conditioner the last digit of the physical address Air conditioner name Name of group and air conditioner with the error occurred Error code Code number for the occurred error Contents Description for the occurred error ...

Page 143: ... wattage without the separate inspection program it can easily check the wattage on which the billing can be done LG NET 1 MENU SELECT TX RX LG NET 2 TX RX LG NET 3 TX RX LG NET 4 TX RX Ethernet 1 ACT LNK Ethernet 2 ACT LNK Console Run Power TX RX FDD TX RX Ext TX RX DI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DO 1 2 3 4 AC Manager ACP Outdoor Unit Indoor Unit Power display Wattmeter Cau...

Page 144: ...hen you click Wattage menu the following wattage screen is displayed Wattage monitor The wattage monitor displays the total wattage of the air conditioner groups connected to the ACP and the wattage for each group 1 Wattage by group list The wattage can be queried by group The wattage within the specific period set by the user is classified and displayed by group 2 1 3 2 ...

Page 145: ...tage by group with the Excel format It displays the wattage by indoor unit list The information for each item is as follows It displays the list of the groups set at the system Details Click button to display the detailed history of each air conditioner Air Indoor unit name of air conditioner conditioner Current Wattage of current indoor unit wattage W Total wattage Accumulated wattage of indoor u...

Page 146: ...esides the accumulated wattage of each air conditioiner the daily wattage within the query period can be queried at the detailed history of each air conditioner Setting the wattage query period You can set the period to query the wattage at the right side of the Wattage screen 3 It displays the set query period Start calendar The start date of the query period can be set at Start calendar ...

Page 147: ...el button The end date of the query period can be set at End calendar When you click Apply button after setting the query period the wattage within the set query period is displayed at Wattage screen When you click Cancel button all settings up to now are cancelled and it returns to the previous screen ...

Page 148: ...conditioner can be registered or deleted at System setup menu of the LG ACCS Caution Setting the system System setup menu is used for installing the product Because the product should be installed by the professional engineer with knowledge about the air conditioner the user should not operate this menu at random Caution Interconnecting the ACP with the AC Manager When the ACP is interconnected wi...

Page 149: ...the system click System setup menu of the LG ACCS When you click System setup menu the following system setup screen is displayed Note Air conditioner setup and the ventilating setup The air conditioner setup is almost same to the ventilating setup Here the system setup function is described based on the air conditioner setup 7 1 2 3 4 5 6 ...

Page 150: ...me can be entered At this time the group number is automatically entered so be careful The existing group may be modified by the same method Click the group to modify and when the related column is changed to yellow modify the group name In order to delete the group click the group name to delete and when the related column is changed to yellow delete the group name Group Default input button When...

Page 151: ...window First in order to add a new indoor unit or ventilator click the related input column When it is changed to the yellow input window enter the information of each item Modifying the existing indoor unit or ventilator is same Click the information field of the indoor unit or ventilator to modify and when it is changed to the yellow input window modify the existing information In order to delet...

Page 152: ... outdoor unit information The third number is the indoor unit or ventilator number which can not be set overlapped within the same outdoor unit number and should be set within the range of 0 15 Model name Enter the model name of the indoor unit or ventilator Maximum Enter the maximum consumed power for the indoor unit or ventilator to consumed power use The maximum consumed power depends on the mo...

Page 153: ...lick Outdoor unit input button located at the right side of the screen the outdoor unit information input window is displayed First in order to add a new outdoor unit click the related input column When the input window is changed to yellow enter information of each item Modifying the existing indoor unit or ventilator is same Click the information column of the indoor unit or ventilator to modify...

Page 154: ...o consumed power use The maximum consumed power depends on the model Item Description Caution Deleting the outdoor unit When the outdoor unit information is deleted the information of the indoor unit connected the related outdoor unit is also deleted Note Physical and Logical group Each outdoor unit information is used as the information of physical group connecting the indoor unit However the air...

Page 155: ...ill be displayed First to add a new ventilator group you must click on the applicable input block When the input window switches to yellow color enter the information of each item Editing existing ventilators is applied in the same way Click on the information block of the ventilator to edit and when it changes to yellow color edit the existing information To delete the existing ventilator informa...

Page 156: ...ld and then click Save button to save the setting information of the ID and the password Click Cancel button to cancel without saving the setting value The A S button is not used at present It will be updated later Time synchronization button 6 Time synchronization button aligns synchronizes the time of the user s PC with the system time of ACP The schedule function of ACP must be executed at accu...

Page 157: ...e button not to change the information When you click Last save state button the window for confirming to execute the command is displayed and when you click Confirm button all information set up to now is cancelled and it returns to the previous save state Last save state button Caution Deleting the indoor unit information When you click Confirm button at the confirmation window the not saved inf...

Page 158: ...evious condition When you click Confirm button all information set up to now is saved and the saving process is informed to the user by the confirmation window Click Save button to change the information Save button Caution Initializing the information of other functions When saving is done at System setup menu all existing information such as schedule peak operation ratio control peak excluded ai...

Page 159: ...ndoor unit name for the user to easily know 3 Click Ventilating setup tab and then click Outdoor unit input button at the right side of the screen When you click Default input button at the Outdoor unit information input window the outdoor unit information group number is entered as default And then delete the number of the not installed outdoor unit group number and modify the outdoor unit name f...

Page 160: ...the ACP does not operrate If the GUI of the EE ACCS the application program of the ACP does not operate close the Explorer window and execute a new Explorer to connect again When network error status Code 242 is displayed on ventilator in LG ACCS of ACP When the network error status is continuously displayed on the ventilator as shown below through LG ACCS the web server program of ACP check the f...

Page 161: ...o the EE electronics via the following e mail you can receive the CD ROM containing it by paying the cost including media cost and transportation cost This proposal is valid for three years after receiving this product from the EE electronics The source of the GPL LGPL license can be downloaded at http www systemaircon com Some of softwares used at this product conform to the following copyright C...

Page 162: ... of which four lines No 1 and 2 for receiving Rx and No 3 and 6 for transmitting Tx are actually used for the data transmission at the general LAN environment It can be largely classified two types according to the method for connecting the line for receiving and transmitting Direct cable It is also called the 1 1 straight cable used for connecting the other equipment at the network Cross cable It...

Page 163: ......

Reviews: