Installation Manual 

3

ENGLISH

4 . Pipe length and difference between high and low

Install the branch pipe so that pipe length and difference between high and low will not exceed
below SPEC.

• When installing the branch pipe, direction and angle of installation is not limited.

• Take care so that burrs and foreign material may not enter into the cutting surface

when connecting.

• Connect a gas pipe of Ø19.05 by using the socket in the indoor unit and connect

remaining those by cutting or direct insertion to the diameter of pipe.

• Don’t use the liquid pipe 

by too bending or twisting.

5 .Thermal insulation work

• Securely wrap the refrigerant and the branch pipe by using thermal insulation

materials provided.
When using thermal insulation materials released, use withstand heat insulation
materials
(thickness of more than 15mm).

• Securely adhere thermal insulation materials 

wrapping the branch pipe so that

they do not widen.
After wrapping them with auxiliary materials 

, bound them with a band 

.

• Finish the work by wrapping with a vinyl tape after the insulation material work.

Pipe Length(m)

Total(Main+Branch)
Main Pipe(L1)
Branch Pipe----Total

Each

In out (h1)
In-In (h2)
L1+L2/L3/L4/L5
Indoor-Indoor_(b)

Spec.

110

50
60
15
30

1

65
10

Branch

Main (L1)

h1

b

L2

L3

L4

L5

h2

Vinyl Tape

Insulation 4

Band  7

Insulation 6

Insulation 5

Insulation  6

Band  7

Band  7

Vinyl Tape