Mount the MultiSITE Communications Manager controller in a location that allows clearance for wiring, servicing, and module removal.
Environmental Requirements
Following are the ambient conditions for mounting the MultiSITE Communications Manager controller.
• Operating temperature range: -4°F to 140°F (-20°C to 60°C).
• Storage Temperature: -40°F to 185°F (-40°C to 85°C ).
• Relative humidity range: 5% to 95% non-condensing.
• Pollution Degree: 3.
• Supply (mains) voltage requirements: Allowable voltage fluct/- 10%.
• For a unit mounted inside an enclosure, ensure that the enclosure is designed to keep the unit within its required operating temperature
range (considering a 24-watt dissipation by the controller). This is important if the controller is mounted inside an enclosure with other heat-
producing equipment.
Do not mount the unit in the following areas:
• Any area with excessive moisture, corrosive fumes, or explosive vapors.
• Any area where vibration or shock is likely to occur.
• A location subject to electrical noise, such as in the proximity of large electrical contactors, electrical machinery, welding equipment,
and so on.
Note:
This product is for indoor use only, in an altitude of up to 2,000m (6,562 ft).