32
Multi V W
all-Mounted Indoor Unit
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Installation Guide
Level
Insta
llation
Guid
e
Step 1
Step 2
Step 3
Insta
llation
Guid
e
Step 4
Mounting — Gallery Indoor Units
Note:
Select the location carefully. Unit must be anchored to a strong wall to
prevent unnecessary vibration.
WARNING
•
When choosing a location for the indoor unit, be sure to take into
consideration routing of wiring for power outlets within the wall.
Contacting wiring can cause serious bodily injury or death.
• Use caution when drilling holes through the walls for the purposes
of piping connections. Power wiring can cause serious bodily injury
or death.
1.
Align and level the factory-supplied installation guide onto the
wall. Lightly attach the guide to the wall with tape (Steps 1 and
2).
2. At the cross marks on the installation guide, drill four (4) 1/4 inch
holes that are approximately 1-1/8 to 1-7/16 inches deep (Step 3).
Figure 17: Mounting the Gallery Indoor Unit
Figure 18: Gallery Install, continued
Plastic
Anchors
7/16 inches
Plastic Anchors
Hanging Hole
(On Back of
the IDU)
Step 5
Installatio
n Guide
Insta
llatio
n Gu
ide
Step 6
Step 7
Step 8
Step 9
3. Choose rear left or right routing for the refrigerant / drain con
-
nection piping, and, using the installation guide, drill a two (2) inch
diameter hole at the appropriate location (Step 4).
4. Drive the four (4) plastic anchors into each of the drilled holes
(Step 5).
5. Insert screws into the top left and right of the installation guide,
leaving about 7/16 inches of the screw out of the wall to hang the
Gallery indoor unit (Step 6).
6. Hang the Gallery indoor unit on the top left and right screws, us
-
ing the hanger holes on the back of the unit. Remove the installation
guide (Step 7).
7. After the top of the Gallery unit is secure, attach the bottom with
the remaining two (2) screws (Step 8). Tighten all screws.
8. After the unit is anchored, test the installation by gently applying
downward pressure with both hands and jiggling to be sure it is at-
tached securely (Step 9).
9. If the Gallery indoor unit is loose, repeat the steps above and
adjust the screws as necessary. If the Gallery unit is secure, then
procedure with connecting the piping and wiring.
GENERAL INSTALLATION GUIDELINES
Gallery Indoor Units
SF Frame