Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Note:
• Indoor units (IDUs) must not be placed in an environment where the IDUs may be exposed to harmful volatile organic compounds
(VOCs) or in environments where there is improper air make up or supply or inadequate ventilation. If there are concerns about VOCs in
the environment where the IDUs are installed, proper air make up or supply and/or adequate ventilation must be provided. Additionally, in
buildings where IDUs will be exposed to VOCs, consider a third party factory-applied epoxy coating to the fan coils for each IDU, where the
entire coil is dipped, not sprayed.
•
If the unit is installed near a body of water, the installation parts are at risk of corroding. Appropriate anti-corrosion methods must be taken
for the unit and all installation parts.
The unit must not be installed where sulfuric acid and flammable or cor
-
rosive gases are generated, vented into, or stored. There is risk of fire,
explosion, and physical injury or death.
The unit may be damaged, may malfunction, and / or will
not operate as designed if installed in any of the conditions
listed.
Figure 11: Installing Near a Heat or Steam Source.
Install a ventilation fan
with sufficient capacity
Heat or steam source
Include enough
distance
Indoor Unit
Required Clearances for Gallery Indoor
Unit
See the figure on the right for required clearance distances around a
typical installed Gallery indoor unit.
Figure 12: Required Clearances Around Installed Gallery Unit
More than 8 inches
More than
20 inches
Recommended height
More than 5 feet from
the floor
More than
20 inches
Figure 13:
Required Clearances Around Installed Wall-Mounted Unit
GENERAL INSTALLATION GUIDELINES
Required Clearances
More than 8 inches
More than 4 inches
More than
4 inches
More than 7.5 feet from the floor
Required Clearances for Wall
Mounted Indoor Unit
See the figure on the right for required clearance distances around
a typical installed wall-mounted indoor unit.
Dos
•
There must be a minimum clearance of 8 inches from the top
of the indoor unit to the ceiling.
•
Clearance gap between any wall or enclosure and the left or
right side of the unit must be greater than 4 inches. Ensure
there is sufficient maintenance space.
•
Unit must be at least 7.5 feet from the floor for adequate clear
-
ance.