Test Run
ENGLISH
Installation Manual
57
Night Silent Operation
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at
night which has low cooling load.
Caution
1. Request installer to set the function during installation.
2. In case the function is not used, set the DIP switch OFF and reset the power.
3. If ODU RPM changes, cooling capacity may go down.
Main PCB power reset
DIP switch No.12+14 ON
ODU
SW01S
ODU
SW01B
Setting complete
Max. RPM setting method
Setting the Fan Max. RPM
SW01V
SW02V
Note 1)
[Note]
1. Select appropriate RPM referencing noise table.
1 time
1 time
1 time
Red button
Black button
9
9
9
Operation
(hr)
8
8
8
420
370
320
1 time
2 times
3 times
1
2
3
Judgment
(hr)
Fan Max
RPM
Setting
Step