14
INSTALLATION SPACE
ENGLISH
*Distance is more than 49 cm because of Auto Dust Removal mode.
Seasonal wind and cautions in winter
• Sufficient measures are required in a snow area or severe cold area in winter so that product
can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes
on the air suction hole, the system may malfunction. If it is installed at snowy area, attach the
hood to the system.
• Install the outdoor unit at the higher installation console by 50 cm than the average snowfall
(annual average snowfall) if it is installed at the area with much snowfall.
• Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm, always
remove snow for operation.
- The height of H frame must be more than 2 times the snowfall and its width shall not ex-
ceed the width of the product. (If width of the frame is wider than that of the product,
snow may accumulate)
- Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal
wind.
Category
Installation Space
Distance
Only 2
sides are
walls
Limita-
tions on
the height
of the wall
(Refer to 4
side walls)
A
E
B
D
A
C
B
D
E
C
A
E
B
F
C
D
A
E
B
F
C
D
A
E
B
A
B
E
A
E
B
D
A
C
B
D
E
C
A
E
B
F
C
D
A
E
B
F
C
D
A
E
B
A
B
E
A
E
B
D
A
C
B
D
E
C
A
E
B
F
C
D
A
E
B
F
C
D
A
E
B
A
B
E
h2
h1
1500
A
B
500
• The height of the wall on the front side must be 1500 mm or less.
• The height of the wall on the inlet side must be 500 mm or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the side are higher than the limit,
there must be additional space on the front and the side.
- Additional Space on the front side by 1/2 of h1.
- Additional Space on the inlet side by 1/2 of h2
- h1 = A(Actual height) - 1500
- h2 = B(Actual height) - 500
A
≥
50
B
≥
300
A
≥
200
B
≥
300
E
≥
400