76
ELECTRICAL WIRING
ENGLISH
Self-Diagnosis Function
Error Indicator
- This function indicates types of failure in self-diagnosis and occurrence of failure for air condi-
tion.
- Error mark is displayed on display window of indoor units and wired remote controller, and 7-
segment LED of outdoor unit control board as shown in the table.
- If more than two troubles occur simultaneously, lower number of error code is first displayed.
- After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit number.
Ex)
Error No. of Compressor
Error No.
Error No. of Unit
Repeat
* If error code displayed is apart from above list, refer related indoor unit’s manual.
Display
Title
Cause of Error
Indoor unit related error
0
1
-
Air temperature sensor of indoor unit
Air temperature sensor of indoor unit is open or short
0
2
-
Inlet pipe temperature sensor of indoor
unit
Inlet pipe temperature sensor of indoor unit is open or
short
0
3
-
Communication error : wired remote con-
troller
↔
indoor unit
Failing to receive wired remote controller signal in in-
door unit PCB
0
4
-
Drain pump
Malfunction of drain pump
0
5
-
Communication error : outdoor unit
↔
in-
door unit
Failing to receive outdoor unit signal in indoor unit
PCB
0
6
-
Outlet pipe temperature sensor of indoor
unit
Outlet pipe temperature sensor of indoor unit is open
or short
0
9
-
Indoor EEPROM Error
In case when the serial number marked on EEPROM
of Indoor unit is 0 or FFFFFF
1
0
-
Poor fan motor operation
Disconnecting the fan motor connector / Failure of in-
door fan motor lock
Outdoor unit related error
2
1
*
Master Outdoor Unit Inverter Compressor
IPM Fault
Master Outdoor Unit Inverter Compressor Drive IPM
Fault
2
2
*
Inverter Board Input Over Current(RMS)
of Master Outdoor Unit
Master Outdoor Unit Inverter Board Input Current ex-
cess (RMS)
2
3
*
Master Outdoor Unit Inverter Compressor
DC link Low Voltage
DC charging is not performed at Master Outdoor Unit
after starting relay turn on.
2
4
*
Master Outdoor Unit High Pressure
Switch
System is turned off by Master Outdoor Unit high
pressure switch.
2
5
*
Master Outdoor Unit Input Voltage High/
Low Voltage
Master Outdoor Unit input voltage is over 506V or
below 414V
2
6
*
Master Outdoor Unit Inverter Compressor
Start Failure
The First Start Failure by Master Outdoor Unit Inverter
Compressor Abnormality
2
9
*
Master Outdoor Unit Inverter Compressor
Over Current
Master Outdoor Unit Inverter Compressor Fault OR
Drive Fault