7

ENGLISH

- Follow ordinance of your governmental organization for technical

standard related to electrical equipment, wiring regulations and
guidance of each electric power company.

- Install the Outdoor Unit communication cable away from the power

source wiring so that it is not affected by electric noise from the power
source. (Do not run it through the same conduit.)

- Be sure to provide designated grounding work to Outdoor Unit.

CAUTION

Be sure to correct the outdoor unit to earth. Do not connect
ground wire to any gas pipe, liquid pipe, lightening rod or
telephone earth line. If earth is incomplete, it may cause an
electric shock.

!

WARNING

Be sure to have authorized electrical engineers do the electric
work using special circuits in accordance with regulations and
installation manual.
If power supply circuit has a lack of capacity or electric work
deficiency, it may cause an electric shock or fire.

!

ELECTRICAL WIRING

- Give some allowance to wiring for electrical part box of Indoor and

Outdoor Units, because the box is sometimes removed at the time of
service work.

- Never connect the main power source to terminal block of

communication cable. If connected, electrical parts will be burnt out. 

- Use 2-core shield cable for communication cable.(     mark in the

figure below) If communication cable of different systems are wired
with the same multiplecore cable, the resultant poor transmitting and
receiving will cause erroneous operations. (     mark in the figure
below)

- Only the communication cable specified should be connected to the

terminal block for Outdoor Unit communication.

- Supply line of appliances shall not be lighter than polychloroprene

sheathed. (code designation 60245 IEC 57)

2-Core Shield Cable

Multi-Core Cable

Remote

control

Remote

control

Remote

control

Remote

control

Indoor

Unit

Indoor

Unit

Indoor

Unit

Indoor

Unit

Compressor Module

Heat Exchanger

Module

Compressor Module

Heat Exchanger

Module

Remote

control

Remote

control

Indoor

Unit

Indoor

Unit

Remote

control

Remote

control

Indoor

Unit

Indoor

Unit

Compressor Module

Heat Exchanger

Module

Compressor Module

Heat Exchanger

Module

CAUTION

• Use the 2-core shield cables for communication cables. Never

use them together with power cables.

• The conductive shielding layer of cable should be grounded to

the metal part of both units.

• Never use multi-core cable

• As this unit is equipped with an inverter, to install a phase

leading capacitor not only will deteriorate power factor
improvement effect, but also may cause capacitor abnormal
heating. Therefore, never install a phase leading capacitor.

• Make sure that the power unbalance ratio is not greater than

2%. 
If it is greater the units lifespan will be reduced.  

!

Electric Characteristics

- Recommended circuit breaker is ELCB
- MFA is used to select the circuit breaker and ground fault circuit

interrupter        

- Refer to the PDB about detail electric characteristics

ELCB : Earth Leakage Circuit Breaker
MFA : Maximum Fuse Amperes(A)
PDB : Product Data Book

1,MFL69171214,영어  2018. 2. 23.  오후 4:43  페이지 7

Summary of Contents for Multi V ARU Series

Page 1: ...opean Shared Service Center B V Krijgsman 1 1186 DM Amstelveen The Netherlands Manufacturer LG Electronics Inc Changwon 2nd factory 84 Wanam ro Seongsan gu Changwon si Gyeongsangnam do KOREA This manual is the simplified version of original manual You can obtain the original manual for more information form www lg com VRF FOR INDOOR INSTALLAION ENGLISH PORTUGUÊS MALTI ITALIANO MAGYAR SLOVENČINA РУ...

Page 2: ...DW H FKDQJHU 0RGXOH XFWLQJ XFWLQJ Total amount of replenishedrefrigerant in refrigerant facility kg Capacity of smallest room whereindoor unit is installed m3 Refrigerant concentration kg m3 Limiting concentration 0 44kg m3 R410A Model Designation Product Name Air conditioner Model Name Product information Additional information Serial number is refer to the bar code on the product Model Name ARU ...

Page 3: ...jury Do not install remove or re install the unit by yourself customer There is risk of fire electric shock explosion or injury Do not store or use flammable gas or combustibles near the air conditioner There is risk of fire or failure of product Use the correctly rated breaker or fuse There is risk of fire or electric shock Prepare for strong wind or earthquake and install the unit at the specifi...

Page 4: ... if the unit is so equipped There is risk of physical injury electric shock or product failure CAUTION Installation Always check for gas refrigerant leakage after installation or repair of product Low refrigerant levels may cause failure of product Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods It may cause a problem for your neighbors Ke...

Page 5: ...g the operational season Do not touch any of the refrigerant piping during and after operation It can cause a burn or frostbite Do not operate the air conditioner with the panels or guards removed Rotating hot or high voltage parts can cause injuries Do not directly turn off the main power switch after stopping operation Wait at least 5 minutes before turning off the main power switch Otherwise it...

Page 6: ... be no drop in pressure Airtight test Electrical work connection circuits and drive circuits Make sure no gaps are left where the insulating materials are joined Heat insulation work Make sure airflow is sufficient Duct work Adjust to downward gradient Drain pipe work Special attention to dryness cleanness and tightness Refrigerant piping work Check model name to make sure the fitting is made corr...

Page 7: ...eiving will cause erroneous operations mark in the figure below Only the communication cable specified should be connected to the terminal block for Outdoor Unit communication Supply line of appliances shall not be lighter than polychloroprene sheathed code designation 60245 IEC 57 2 Core Shield Cable Multi Core Cable Remote control Remote control Remote control Remote control Indoor Unit Indoor U...

Page 8: ...8 ENGLISH 1 MFL69171214 영어 2018 2 23 오후 4 43 페이지 8 ...

Reviews: