7
ENGLISH
- Follow ordinance of your governmental organization for technical
standard related to electrical equipment, wiring regulations and
guidance of each electric power company.
- Install the Outdoor Unit communication cable away from the power
source wiring so that it is not affected by electric noise from the power
source. (Do not run it through the same conduit.)
- Be sure to provide designated grounding work to Outdoor Unit.
CAUTION
Be sure to correct the outdoor unit to earth. Do not connect
ground wire to any gas pipe, liquid pipe, lightening rod or
telephone earth line. If earth is incomplete, it may cause an
electric shock.
!
WARNING
Be sure to have authorized electrical engineers do the electric
work using special circuits in accordance with regulations and
installation manual.
If power supply circuit has a lack of capacity or electric work
deficiency, it may cause an electric shock or fire.
!
ELECTRICAL WIRING
- Give some allowance to wiring for electrical part box of Indoor and
Outdoor Units, because the box is sometimes removed at the time of
service work.
- Never connect the main power source to terminal block of
communication cable. If connected, electrical parts will be burnt out.
- Use 2-core shield cable for communication cable.( mark in the
figure below) If communication cable of different systems are wired
with the same multiplecore cable, the resultant poor transmitting and
receiving will cause erroneous operations. ( mark in the figure
below)
- Only the communication cable specified should be connected to the
terminal block for Outdoor Unit communication.
- Supply line of appliances shall not be lighter than polychloroprene
sheathed. (code designation 60245 IEC 57)
2-Core Shield Cable
Multi-Core Cable
Remote
control
Remote
control
Remote
control
Remote
control
Indoor
Unit
Indoor
Unit
Indoor
Unit
Indoor
Unit
Compressor Module
Heat Exchanger
Module
Compressor Module
Heat Exchanger
Module
Remote
control
Remote
control
Indoor
Unit
Indoor
Unit
Remote
control
Remote
control
Indoor
Unit
Indoor
Unit
Compressor Module
Heat Exchanger
Module
Compressor Module
Heat Exchanger
Module
CAUTION
• Use the 2-core shield cables for communication cables. Never
use them together with power cables.
• The conductive shielding layer of cable should be grounded to
the metal part of both units.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase
leading capacitor not only will deteriorate power factor
improvement effect, but also may cause capacitor abnormal
heating. Therefore, never install a phase leading capacitor.
• Make sure that the power unbalance ratio is not greater than
2%.
If it is greater the units lifespan will be reduced.
!
Electric Characteristics
- Recommended circuit breaker is ELCB
- MFA is used to select the circuit breaker and ground fault circuit
interrupter
- Refer to the PDB about detail electric characteristics
ELCB : Earth Leakage Circuit Breaker
MFA : Maximum Fuse Amperes(A)
PDB : Product Data Book
1,MFL69171214,영어 2018. 2. 23. 오후 4:43 페이지 7