Type
Ceiling Concealed Duct -Middle Static
Model
Unit
ARNU283M2A4 ARNU363M2A4 ARNU423M2A4
Cooling Capacity
kW
kcal/h
Btu/h
Heating Capacity
kW
kcal/h
Btu/h
Power Input
Nominal W
Rated W
Casing
Dimensions
(WxHxD)
Body
mm
inch
Coil
Rows x Columns x FPI
Face Area
m
2
(ft
2
)
Fan
Type
Motor Output x Number
W
Running Current
A
Air Flow Rate(H / M / L)
(High Mode-Factory Set)
External static pressure
CMM
CFM
mmAq(Pa)
Air Flow Rate(H / M / L)
(Standard mode)
External static Pressure
CMM
CFM
mmAq(Pa)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Pipe Connections
Liquid Side
mm(inch)
Gas Side
mm(inch)
Drain Pipe(Internal Dia.)
mm(inch)
Net Weight
Body
kg(lbs)
Sound Pressure Levels (H / M / L)
dB(A)
Sound Power Levels (H / M / L)
dB(A)
Power Supply
Ø, V, Hz
Refrigerant Control
Transmission Cable (AWG# -C)
- 4 -
Copyright © 2018 LG Electronics Inc.
All rights reserved. Only training and service purposes.
8.2
7 100
28 000
9.2
8 000
31 500
123
430
Galvanized Steel Plate
1 250 × 270 × 700
49-7/32 x 10-5/8 x 27-9/16
3 x 13 x 18
0.27(2.91)
Sirocco Fan
350 x 1
2.3
28.0 / 24.0 / 21.0
989 /848 / 742
6(59)
28.0 / 24.0 / 21.0
989 /848 / 742
5(49)
Direct
BLDC
Microprocessor, Thermostat
for cooling and heating
Foamed polystrene
-
Fuse
Ø9.52(3/8)
Ø15.88(5/8)
25(1)
39.1(86)
40 / 39 / 37
64 / 61 / 57
1, 208-230, 60
EEV
AWG 18 x 2C
10.6
9 100
36 200
11.9
10 200
40 600
184
430
Galvanized Steel Plate
1 250 × 270 × 700
49-7/32 x 10-5/8 x 27-9/16
3 x 13 x 18
0.27(2.91)
Sirocco Fan
350 x 1
2.3
28.0 / 24.0 / 21.0
989 / 848 / 742
6(59)
28.0 / 24.0 / 21.0
989 / 848 / 742
5(49)
Direct
BLDC
Microprocessor, Thermostat
for cooling and heating
Foamed polystrene
-
Fuse
Ø9.52(3/8)
Ø15.88(5/8)
25(1)
39.1(86)
42 / 40 / 38
65 / 62 / 60
1, 208-230, 60
EEV
AWG 18 x 2C
12.3
10 600
42 000
13.8
11 800
47 000
231
430
Galvanized Steel Plate
1 250 × 270 × 700
49-7/32 x 10-5/8 x 27-9/16
3 x 13 x 18
0.27(2.91)
Sirocco Fan
350 x 1
2.3
38.0 / 33.0 / 28.0
1 342 / 1 165 / 989
6(59)
38.0 / 33.0 / 28.0
1 342 / 1 165 / 989
5(49)
Direct
BLDC
Microprocessor, Thermostat
for cooling and heating
Foamed polystrene
-
Fuse
Ø9.52(3/8)
Ø15.88(5/8)
25(1)
39.1(86)
44 / 43 / 40
66 / 65 / 63
1, 208-230, 60
EEV
AWG 18 x 2C
Notes:-
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m(24.6ft)
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m(24.6ft)
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Noise Level is Standard Mode
(for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dBA)
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
CFM = m
3
/min x 35.3
l/s = CMM x 1 000/60