- 13 -
Error Indicator
• This function indicates types of failure in self-diagnosis and occurrence of failure for air condition.
• Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of
outdoor unit control board as shown in the table.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurrence, if error is released, error LED is also released simultaneously.
Error Display
- 1st,2nd,3rd LED of 7-segment indicates error number, 4th LED indicates unit number. Indicates unit number.
(* = 1:Master, 2 : Slave 1, 3 : Slave 2)
Ex) 211 : No.21 error of master unit
213 : No.21 error of slave2
1051 : No.105 error of master unit
h
Refer to the DX-Venitilation manual for DX-Venitilation error code
(repetition)
Error Compressor
Error number
Unit(1:Master, 2:Slave 1, 3:Slave 2)
7. Self-diagnosis function
Display
Title
Cause of Error
Indoor unit related error
0
1
-
Air temperature sensor of indoor unit
Air temperature sensor of indoor unit is open or short
0
2
-
Inlet pipe temperature sensor of indoor unit
Inlet pipe temperature sensor of indoor unit is open or short
0
3
-
Communication error : wired remote controller
↔
indoor unit
Failing to receive wired remote controller signal in indoor unit PCB
0
4
-
Drain pump
Malfunction of drain pump
0
5
-
Communication error : Indoor communication
PCB
↔
indoor unit
Indoor Unit PCB did not receive signal from Indoor
communication PCB for over 3 minutes continuously
0
6
-
Outlet pipe temperature sensor of indoor unit
Outlet pipe temperature sensor of indoor unit is open or short
0
9
-
Indoor EEPROM Error
In case when the serial number marked on EEPROM of
Indoor unit is 0 or FFFFFF
1
0
-
Poor fan motor operation
Disconnecting the fan motor connector / Failure of indoor
fan motor lock
2
3
0
Refrigerant leakage sensing error
Refrigerant leakage sensing error and sensor defect error
2
3
7
Communication defect in indoor communication
PCB
↔
outdoor communication PCB
Indoor communication PCB did not receive signal from outdoor
communication PCB for over 3 minutes continuously
2
3
8
Communication error in outdoor communication
PCB
↔
outdoor unit
Outdoor communication PCB did not receive communication sig-
nal from outdoor unit for over 3 minutes continuously
Copyright © 2018 LG Electronics Inc.
All rights reserved. Only training and service purposes.