20 Air Conditioner
Wiring Connection
Connection method of the connecting cable(Example)
(1) Remove two-caps on the conduit panel.
(for low voltage line)
(2) Pull out connection cable through conduit.
(3) After conduit to the panel, fix nut to the opposite
side of panel.
(4) Pass the connection cabel through the hole.
(5) Properly connect the cable on the terminal block.
(6) Fix the connection cable with cord clamp
provided on the unit not to have strain at the
terminal when the connection cable is pulled
outside up to a 35 pound weight
WARNING: Loose wiring may cause
the terminal to overheat or result in
unit malfunction. A fire hazard may
also exist. Therefore, be sure all
wiring is tightly connected.
When connecting each power wire to the
corresponding terminal, follow instructions "How
to connect wiring to the terminals" and fasten
the wire tightly with the fixing screw of the
terminal plate.
How to connect wiring to the
terminals
For strand wiring
(1) Cut the wire end with a wire cutter or wire-
cutting pliers, then strip the insulation to
expose the strand wiring about 10 mm(3/8").
(2) Using a screwdriver, remove the terminal
screw(s) on the terminal plate.
(3) Using a round terminal fastener or pliers,
securely clamp each stripped wire end with a
round terminal.
(4) Position the round terminal wire, and replace
and tighten the terminal screw using a
screwdriver.
G
Terminal
block
Lock nut
Power supply line
(1Ø, 208/230V)
Conduit panel
Cap(Reuse)
Cord clamp
Conduit Hole
Cap(Remove)
Taping
(for sealing)
Connecting cable
(1Ø, 208/230V)
Power supply cable
Connecting Cable
Str
ip 10 mm(3/8")
Round
terminal
Connecting cable
Loosening the
terminal block
screw
Fastening the
wire tightly
Strand wire
Lock nut
(field supply)
Conduit
(field supply)
Conduit panel
Power supply line or
Connecting cable