Installation of Indoor, Outdoor Unit
Installation Manual 9
ENGLISH
3. Piping length and the elevation
24k Btu/h
15.88(5/8)
9.5(3/8)
7.5(25)
5(16)
35(0.38)
Gas
Liquid
Standard
Max.
Standard
Max.
Capacity
Pipe Size
Length A
Elevation B
*Additional
Unit : mm(inch)
Unit : m(ft)
Unit : m(ft)
refrigerant
Unit : g/m(oz/ft)
Oil trap
Gas piping
Liquid piping
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
*15m
* Install trap at each
difference in height
15m
A trap is not necessary when the
outdoor unit is installed in a higher
position than the indoor unit.
CAUTION:
• Rated performance for refrigerant line length of:7.5m(25ft)
• Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
50(164)
cassette type
30(98)
Floor standing type
30(98)
cassette type
20(66)
Floor standing type