13
Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MAX
MULTI
F
MULTI
F
Table 4:
Multi F Multi Zone Art Cool Mirror Wall-Mounted Indoor Unit Specifications
GENERAL DATA
Specifications
Model Name
LAN090HSV4
LAN120HSV4
LAN180HSV4
Nominal Cooling Capacity (Btu/h)
1
9,000
12,000
18,000
Nominal Heating Capacity (Btu/h)
1
10,400
13,800
20,800
Operating Range
Cooling (°F WB)
57-77
Heating (°F DB)
59-81
Fan
Type
Cross Flow
Motor Output (W) x Qty.
14.4 x 1
76.0 x 1
Motor/Drive
Brushless Digitally Controlled / Direct
Airflow Rate CFM (H/M/L)
247 / 230 / 212
335 / 318 / 300
572 / 501 / 434
Unit Data
Refrigerant Type
2
R410A
Refrigerant Control
Electronic Expansion Valve (EEV)
Power Supply V, Ø, Hz
3
208-230, 1, 60
Rated Amps (A)
0.2
0.3
Sound Pressure Level ±3 dB(A) (H/M/L)
4
33 / 30 / 27
39 / 36 / 31
37 / 33 / 28
Dimensions (W x H x D, in.)
34-13/16 x 11-1/4 x 8-1/16
34-13/16 x 11-1/4 x 8-1/16 40-9/16 x 12-13/16 x 9-11/16
Net Unit Weight (lbs.)
24
32
Shipping Weight (lbs.)
29
39
Power Wiring / Communications Cable (No. x AWG)
5
4 x 18
Heat Exchanger (Row x Column x Fin / inch) x No.
(2 x 16 x 23) x 1
(3 x 18 x 22) x 1
Pipe Size
Liquid (in.)
1/4
Vapor (in.)
3/8
1/2
Connection Size
Liquid (in.)
1/4
3/8
Vapor (in.)
3/8
5/8
Drain O.D. / I.D. (in.)
27/32, 5/8
1
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping
length in accordance with standard length of each outdoor unit and a 0 ft. level difference
between outdoor and indoor units. All capacities are net with a combination ratio between
95 – 105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb
(DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and
75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb
(DB) and 60ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and
43ºF wet bulb (WB).
2
This unit comes with a dry helium charge.
3
Acceptable operating voltage: 187V-253V.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and
are the same in both cooling and heating mode. These values can increase due to ambient
conditions during operation.
5
All power wiring / communications cable to be minimum 18 AWG, 4-conductor, stranded,
shielded, and must comply with applicable local and national codes.