Installation manual
17
Installation
ENGLISH
• To enable the filter check alarm function, you must set "test run" in the installer settings on the
remote control.
• After the test run is finished, the product will turn off.
• During the test run, the remote control will not turn off the power.
• Noise caused by operation mode change during test run may occur, but this is not a product error.
• Check filter contamination before test run operation.
• Except for rated voltage(220~240V), it can be detected incorrectly.
• It may be affected by the external environment, but this is not a product error.
How to connect remote controller(accessory)
How to use the filter check alarm function by filter clogging
(LZ-H150/200GBA5)
Please connect indoor unit and remote controller using connection cable.
Please use extension cable if the distance between wired remote controller and
indoor unit is more than 10m.
Please check if connector is normally connected.
Connecting cable
Indoor
Unit side
When installing the wired remote controller, do not bury it in the wall.
(It can cause damage in the temperature sensor.)
Do not install the cable to be 50m or above.
(It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the remote controller
side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
CAUTION
• If the test run function is not used, the filter check alarm function can not be used.
• After T.A.B and filter and PCB replacement, test run must be performed.
CAUTION
• Some categories of the menu may not be displayed according to the function of the
product, or the menu name may be different.
• For more details, refer to the remote controller manual.