- 16 -
6-2 PTC AND OLP
6
5
Shows continuity
Open
Separate PTC-Starter
from Compressor and
measure resistance
between No. 5 and 6
of PTC-Starter with a
Tester.
(Figure 1)
Observation value is
115V/60Hz : 6.8
?
±20%
The resistance value
is 0
?
(short) or
Check another
electric component.
Replace OLP.
Replace PTC-
Starter.
Figure 1
Figure 2
Normal operation of
compressor is impossible
or poor.
Separate OLP from
compressor and check
resistance value between
two terminals of OLP whit a
tester.
(Figure 2)
?
at room temperature 25 c
8.2
? at
25 c