1-6. Refrigerant Charging
Charging Tube
Suction Pipe
Discharge Pipe
1-7. Leak Inspection and Cycle Check
Required equipment: Leakage checking machine (foam and leakage inspection machine)
Check for leakage by using form or a leakage inspection machine at the worked part if charging of refrigerant is
completed.
Check for leakage at the low pressure part with the compressor stopped, and check at the high pressure part with the
compressor being operating.
If leakage is detected, proceed to repair according to repair process again starting from “2-1. Returnof Refrigerator
Refrigerant”.
(Never perform welding work or work using fire appliances.)
Check that heat remains at a discharge pipe or condenser with the hands if leakage check is completed. If heat remains,
the cooling cycle is normal.
(Take care since a discharge pipe may be hot.)
Heavy Repair Method of Refrigerator by Application of Refrigerant
1-8. Failure Checking Procedures
Check of rotation
of COMP
Surface of
cooler is cold.
Surface of
cooler is cold.
Clogged capillary
tube
Leakage of
welding part
Check of
leakage part
Leakage of
radiator
Leakage of
refrigerant
Normal
Clogged cycle
Somewhat cold
Moisture clogged
Check of cooler
at F-Room, R-
Room
Required equipment: Bombe, R134 a refrigerant (Energy Star Al spiral condenser model
165g
DOE Fe wire condenser
model 175g
• Firstly remove fire appliances and heating source for performing work when charging scaled refrigerant. (Do not spray
refrigerant indoor.)
• Measure the accurate quantity (Energy Star
l piral ondenser
odel
165g
OE
e
ire ondenser
odel
175g) of
refrigerant to charge it into a Bombe.
• Make the Bomber as vacuum status to charge refrigerant.
(If there is air or moisture in a Bombe, it may give effect on performance of a cooling cycle.)
• Please manage refrigerant quantity as 165g
1 or 175g
1. Differently from R134a, R134a gives much effect on cooling
performance depending on change of refrigerant quantity.
Refrigerant quantity = Weight after charging Weight before charging (weight of vacuumed Bombe)
• Connect Bombe with a charging tube to charge refrigerant.
• Turn on power of refrigerator to operate a compressor.
• Measure Bombe weight after 5 through 10 minutes to check remained refrigerant quantity to complete charging of
refrigerant.
(After charging refrigerant, never perform welding work or work using fire appliances.)
-
,
:
/
,
:
)
,
:
/
,
:
A s
c
m
D
F w
c
m
Summary of Contents for LSXS26326
Page 9: ...Circuit Diagram ...
Page 25: ...Micom Circuit description ...
Page 31: ...Compressor ...
Page 33: ...Compressor ...
Page 34: ...Compressor ...
Page 35: ...Compressor ...
Page 50: ...Troubleshooting ...
Page 52: ...Troubleshooting ...
Page 54: ...Troubleshooting ...
Page 55: ...Troubleshooting 2 9 Communication Error CO E ...
Page 78: ...August 2014 MFL ...