Product data | 19
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG ” is a registered trademark of LG Corp.
inDoor UniT AcoUSTic DATA
Figure 3: Indoor Unit Sound Levels
2.62 ft
3.28 ft
Microphone
Model
Sound Pressure Levels (dB[A])
Cooling
Heating
H
M
L
H
M
L
LSn090HSV4
38
33
23
38
33
23
LSn120HSV4
39
33
23
39
33
23
LSn180HSV4
45
40
35
45
40
35
Table 6: Indoor Unit Acoustic Data
Figure 4: Sound Pressure Levels for LSn90-120-180HSV4 Indoor Units.
10
20
30
40
50
60
70
80
63
125
250
500
1000
2000
4000
8000
Octave Band Sound Pressure Level (0dB = 20μPa)
Octave Band Center Frequency (Hz)
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
10
20
30
40
50
60
70
80
63
125
250
500
1000
2000
4000
8000
Octave Band Sound Pressure Level (0dB = 20μPa)
Octave Band Center Frequency (Hz)
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
Octave Band Sound Pressure Level (0dB = 20μPa)
Octave Band Center Frequency (Hz)
10
20
30
40
50
60
70
80
63
125
250
500
1000 2000 4000 8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
LSN090HSV4
LSN120HSV4
LSN180HSV4
• Measurements are taken 3.28 ft away from the front of the unit.
• Sound pressure levels are measured in dB(A) with a tolerance of ±3.
• Sound pressure levels are tested in an anechoic chamber under ISo Standard 3745.
• Sound level will vary depending on a range of factors including the construction (acoustic absorp-
tion coefficient) of a particular room in which the unit was installed.