52
Single Zone Mega, Standard Efficiency
, and Mega 1
15V W
all Mounted Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
ELECTRICAL SYSTEM INSTALLATION
Figure 82: Schematic of a Single Zone System When the Wiring is GREATER THAN 130 Feet.
Two-Conductor
Power Cable
GN/YL
GN/YL = (Ground, Yellow)
Two-Conductor
Communication /
Ground Cable
Separate At Least
Two (2) Inches
13/16
"
7/16
" ± 1/8
"
1(L1)
2(L2)
13/16
"
7/16
" ± 1/8
"
3
Figure 84: LS090HEV2, LS120HEV2, LS090HFV3, LS120HFV3 Power
/ Communication System Diagram For Wiring Lengths GREATER THAN
130 Feet.
Power
Supply
1(L1) (Power, L)
2(L2) (Neutral, N)
G (Ground)
Power Flow: L
→
N
Diagram is an example of communication and power
cables when the wiring is GREATER THAN 130 feet.
Terminals may be labeled differently depending on the model.
Outdoor and Indoor Unit appearances may vary depending on the model.
Communication Flow: Comm
→
N
3 (Communications)
GREATER THAN 130 feet: Must Separate Communications and Ground (G) Cable from the Power
(1[L1]) and Neutral (2[L2]) Cable at Least Two (2) Inches.
At Least Two (2) Inches
Figure 85: LS180HEV2, LS240HEV2, LS180HFV3, LS240HFV3 Power
/ Communication System Diagram For Wiring Lengths GREATER THAN
130 Feet.
Connections and Specifications
Figure 83: Single Zone Outdoor Unit to Indoor Unit Wiring and Com-
munications Cable Diagram For Wiring Lengths GREATER THAN 130
Feet.
LS090, 120HEV2
208/230 VAC
LS180HEV2, LS240HEV2
Figure 86: LS090-120HXV2 Power / Communication System Diagram
For Wiring Lengths GREATER THAN 130 Feet.
LSU090HXV2, LSU120HXV2
115 VAC
2(L2)
2(L2)
2(L2)