6. Heating mode operation
• Operating frequency of compressor depend on the difference of the temperature
(= compressor off temp. - intake air temp.)
• Compressor off temp. = setting temp.+3.0°C
on temp. = setting temp.
• If compressor operates at some operation frequency, the operating frequency of compressor cannot be
changed within 30 seconds.
• Condition of compressor turned off
- When intake air temperature r3°C above the setting temperature.
• Condition of indoor fan turned off
- While in compressor on:indoor pipe temp. < 26°C
off: indoor pipe temp. < 37°C
• While in defrost control, between the indoor and outdoor fans are turned off.
• Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
Temp. differences
over 3.0°C
2.5~3.0°C
2.0~2.49°C
1.5~1.99°C
1.0~1.49°C
0.5~0.99°C
0.0~0.49°C
Comp. Operating frequency
Step 19
Step 15
Step 13
Step 9
Step 5
Step 3
Step 1
[ The operating freq. step of comp]
[The targeting operating freq. of comp. each model]
Model
7K Btu Series
9K Btu Series
12K Btu Series
18K Btu Series
Comp. Operating frequency
42
47
56
67
80
86
90
42
56
68
82
95
103
110
41
49
57
64
72
76
83
41
47
53
58
67
71
76
Step 1
Step 3
Step 5
Step 9 Step 13(Fh) Step 15 Step 19