10. Soft Dry Operation.
ƒU
During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1
¡
, the compres-
sor OFF temperature is the setting temperature minus 0.5
¡
ƒU
When the room temperature rises over the compressor ON temperature, the operation mode is switched to the
cooling mode.
ƒU
When the room temperature falls between the compressor ON temperature and OFF temperature, the opera-
tion mode is switched to the Soft Dry Operation.
In this temperature range, 10min. Dry Operation, 5.5min operation OFF, 1.5min. only fan operation repeat. Dur-
ing 10min Dry operation, even if the room temperature falls below compressor OFF temperature, 10min(MAX)
Compressor ON from starting of Dry operation which includes 4 min. Compressor ON operation below the
comperssor OFF temperature.
ƒU
In micom dehumidify mode, control of fan speed is as following.
11. Forced operation
ƒU
If you lose wireless remote controller, you can operate the unit with forced operation switch.
ƒU
The standand conditions are as following.
ƒ¡
20
ƒ¡
ROOM TEMP.
SETTING TEMP.+1°C
(COMP. ON)
SETTING TEMP.
(COMP. OFF)
INDOOR FAN
OFF
LOW
LOW
OFF
LOW
LOW
COMPRESSOR
ON
OFF
ON
OFF
ON
Selecting
fan speed
2 minutes
5.5 minutes
maximum
4 minutes
1 minutes
1.5 minutes
10 minutes
maximum
10minutes
Operation
Cooling
Dry operation
Heat pump Model
Room Temp
¡ˆ
24°C
21°C
¡´
Room Temp
£…
24°C
Room Temp
£…
21°C
Operation Mode
Cooling
Cooling
Soft Dry
Heating
FAN Speed
High
High
Low
High
Setting Temp.
24°C
24°C
Room Temp.
22°C
Cooling Model
¢”
¢”