30 Floor Standing Type Air Conditioner
Installation
Set the both 3-way(liquid side) and 3-way(gas side) valves to open position with the Hexagonal
wrench for the unit operation.
Checking a gas leakage for the left piping
• Connect the manifold gauge to the service port of 3-way(gas side) valve.
Measure the pressure.
• Keep it for 5 - 10 minutes.
Ensure if the pressure indicated on the gauge is as same as that of measured at first time.
CLOSE
CLOSE
Closed
Closed
Indoor unit
Outdoor unit
Liquid side
Gas side