background image

ENGINEERING AND 

SPECIFICATIONS GUIDE 2009

DUCTLESS AIR CONDITIONING SYSTEMS • ART COOL • INVERTER 

• FLEX MULTI-SPLIT  • FLOOR STANDING • CEILING CASSETTE • PTAC

INNOVATIVE    COMFORT    SOLUTIONS

Summary of Contents for LMU365HV

Page 1: ...ENGINEERING AND SPECIFICATIONS GUIDE 2009 DUCTLESS AIR CONDITIONING SYSTEMS ART COOL INVERTER FLEX MULTI SPLIT FLOOR STANDING CEILING CASSETTE PTAC INNOVATIVE COMFORT SOLUTIONS ...

Page 2: ......

Page 3: ...fications 18 B Electrical and Refrigeration Quick Reference 19 Flex Multi Split Standard Air Conditioners Dual and Tri Zone 20 A Product Specifications 22 B Electrical and Refrigeration Quick Reference 23 Flex Multi Split Dual Tri Quad Zone Air Conditioning Systems 26 Outdoor Units H P Inverter Specifications 27 Flex Multi Indoor Unit Specifications 32 Flex Multi Inverter Performance 47 Packaged T...

Page 4: ...Dual Zone Mix and match for 18 000 to 24 000 BTUs Tri Zone Mix and match for 27 000 to 36 000 BTUs Quad Zone Mix and match for 36 000 to 45 000 BTUs Heat Pump Inverter Disclaimer Items represented in this catalogue may change without notice LG is not responsible for information contained in this catalogue that may have changed Please contact your LG Sales Representative for updated information See...

Page 5: ...ant R 410A and our Neo Plasma Air Purifying System providing powerful sterilization for health conscious customers Also the Art Cool series has received the International Forum Design Award and Red Dot Design Award for its outstanding design An innovative air flow system makes it the quietest in the industry for a more pleasant and convenient indoor environment 2 ART COOL DISPLAY RACK WIRELESS WAL...

Page 6: ...that temperature It is quieter to operate and uses less energy than conventional ACs which cycle on and off R 410A Refrigerant Environmentally friendly refrigerant used in the majority of LG systems NOTE R 410A service port access will require a special adapter to attach standard 1 4 hoses Ask your equipment supplier for more details Patented Neo Plasma Air Purifying System The 4 stage system feat...

Page 7: ...4 THE LG HVAC ADVANTAGE ...

Page 8: ...ses less energy and maintains a constant comfort level This can save you up to 44 in utility costs FPO FPO Neo Plasma Air Purification System PLASMA FILTER PRE FILTER TRIPLE FILTER NANO CARBON FILTER Nano Carbon Balls ensure the destruction of bacteria and allergens by causing the nuclei of cells to decompose and die Conventional filters only inactivate the cell allowing it to reactivate later The...

Page 9: ...nditioning Systems from LG maximize the efficiency and economics of ductless technology Now you can bring more attractive cost effective solutions to your commercial and residential customers providing single zone systems in both air conditioning and heat pump models Indoor Unit with Remote Outdoor Unit Available styles and finishes Outstanding air purification The wall unit features LG s Neo Plas...

Page 10: ... Refrigerant Neo Plasma Air Purifying System Self cleaning indoor coil Dehumidifying mode Chaos Swing Three way cooling Jet Cool Cooling mode Heating mode H P model only Fan mode Auto operation Manual power switch Defrost control H P model only Auto sleep mode Auto restart Built in low ambient standard down to 0 F cooling mode 24 Hour on off timer Evaporator frost control Interior Unit Includes Wa...

Page 11: ...t is secured Take out the existing picture from under the panel 4 Slide the new picture under the panel and press the front panel shut 5 Secure the tabs on the bottom of the front panel 6 Your new picture should now be displayed in your LG Art Cool HIGH WALL DUCTLESS ART COOLTM MINI SPLIT SINGLE ZONE Warranty 1 year parts and labour 7 years compressor See electrical specifications refrigerant line...

Page 12: ...5 16 x W x H x D inches 25 13 16 x 12 5 8 Weight lbs 149 9 Thermostat Range Cooling Heating F 64 86 LG verified sound ratings HIGH WALL DUCTLESS ART COOLTM MINI SPLIT SINGLE ZONE Features R 410A Refrigerant Neo Plasma Air Purifying System Self cleaning indoor coil Dehumidifying mode Chaos Swing Jet Cool Three way cooling Cooling mode Fan mode Auto operation Manual power switch Auto sleep mode Auto...

Page 13: ...r than 25 ft see chart above refrigerant lines must be oil trapped at least every 16 4 ft of elevation Each system should have a 6 8 inch inverted trap at the condensing unit if mounted above indoor unit Figure A Oil trap required at 8 16 4 ft elevation condenser over evaporator ART COOLTM MINI SPLIT SINGLE ZONE ELECTRICAL AND REFRIGERATION QUICK REFERENCE NOTE Recommend shielded cable for low vol...

Page 14: ...T COOLTM MINI SPLIT SINGLE ZONE INVERTER Features Inverter Compressor R 410A Refrigerant Neo Plasma Air Purifying System Chaos Swing Self cleaning indoor coil Auto changeover Jet Cool Cooling Heating Fan Mode Auto sleep mode Ultra quiet operation Dehumidifying mode Auto restart 24 Hour on off timer Built in low ambient standard down to 14 F cooling mode Manual power switch Defrost control Temperat...

Page 15: ...PV Outdoor Model LSU182HPV LSU242HPV Performance Capacity BTUs 18 000 17 500 24 000 23 600 20 700 20 200 27 600 27 200 SEER HSPF 16 2 16 2 8 2 16 2 16 2 8 2 Air Circulation CFM H M L 460 380 320 530 445 378 Fan Speeds 5 Auto Chaos 5 Auto Chaos Dehumidification pts hr 5 3 6 6 Indoor dB A 42 39 36 47 42 39 Outdoor dB A 55 56 Electrical Rated Voltage Outdoor 230 208 60 1 230 208 60 1 Rated Voltage In...

Page 16: ... ft 50 25 H P LS242HPV 24 000 3 8 5 8 0 33 oz ft 100 50 Type System Model BTUs Rated Amps MCA MOP Each outdoor unit is pre charged with enough refrigerant to charge the indoor unit and up to 25 ft of line set You must adjust the charge if this length varies NOTE Systems having the outdoor unit mounted above the indoor unit e g basement installations have the following additional requirement For sy...

Page 17: ...ofile design Models are available in a variety of sizes from 9 000 through 27 000 BTUs LG s Mini Split Standard air conditioners are easy to install efficient and cost effective Outdoor Unit Indoor Unit Mini Split Standard Indoor Unit White Heat Pump Inverter 27 000 BTUs Available styles Mini Split Standard Indoor Unit White Cooling 9 000 24 000 BTUs 14 ...

Page 18: ...120CP Performance Capacity BTUs 9 000 12 000 SEER 13 13 Air Circulation CFM H M L 250 210 170 330 280 230 Fan Speeds 4 Auto Chaos 4 Auto Chaos Dehumidification pts hr 2 6 3 0 Indoor dB A 36 31 28 41 36 34 Outdoor dB A 48 48 Electrical Rated Voltage Outdoor 1 15 60 1 1 15 1 60 Rated Voltage Indoor 36V DC 36V DC Indoor Dimensions 33 1 16 x 35 3 16 x W x H x D inches 10 5 8 x 1 1 5 8 x 6 1 32 6 1 2 W...

Page 19: ...Indoor Model LSI180CP LSI240CP Outdoor Model LSO180CP LSO240CP Performance Capacity BTUs 18 000 17 800 22 500 22 100 SEER 13 13 Air Circulation CFM H M L 460 380 320 530 450 370 Fan Speeds 4 Auto Chaos 4 Auto Chaos Dehumidification pts hr 5 3 6 6 Indoor dB A 41 38 36 46 41 38 Outdoor dB A 55 57 Electrical Rated Voltage Outdoor 230 208 60 1 230 208 60 1 Rated Voltage Indoor 36V DC 36V DC Indoor Dim...

Page 20: ...ndoor coil and a 25 line set System Model LS302HPV Indoor Model LSN302HPV Outdoor Model LSU302HPV Performance Capacity BTUs 27 000 27 000 29 000 29 000 SEER HSPF 16 7 8 Air Circulation CFM H M L 710 640 530 Fan Speeds 4 Auto Chaos Dehumidification pts hr 7 2 Indoor dB A 47 42 39 Outdoor dB A 58 Electrical Rated Voltage Outdoor 230 208 60 1 Rated Voltage Indoor 230 208 60 1 Indoor Dimensions 47 3 5...

Page 21: ...Maximum Overcurrent Protection NOTE Please see local electrical codes for proper wire specifications MINI SPLIT STANDARD SINGLE ZONE ELECTRICAL AND REFRIGERATION QUICK REFERENCE Each outdoor unit is pre charged with enough refrigerant to charge the indoor unit and up to 25 ft of line set You must adjust the charge if this length varies NOTE Systems having the outdoor unit mounted above the indoor ...

Page 22: ...s can be combined to achieve between 18 000 and 24 000 BTUs on a Dual Zone System and from 27 000 to 36 000 BTUs on a Tri Zone System The interior units are available in a variety of styles including Art Cool and standard models Both Dual Zone and Tri Zone Systems are available in Cooling Only or Heat Pump systems Flex Multi Split Standard Indoor Unit Flex Multi Split Art Cool Indoor Unit Metal Fi...

Page 23: ...261 194 Fan Speeds 4 Auto Chaos 4 Auto Chaos 4 Auto Chaos 4 Auto Chaos 4 Auto Chaos Dehumidification pts hr 2 3 2 3 2 5 3 0 2 5 Indoor dB A 31 29 22 37 31 27 39 25 21 43 39 31 39 25 21 Outdoor dB A 50 50 50 50 50 Electrical Rated Voltage Outdoor 230 208 60 1 230 208 60 1 230 208 60 1 230 208 60 1 230 208 60 1 Rated Voltage Indoor 36V DC 36V DC 36V DC 36V DC 36V DC Indoor Dimensions 33 1 16 x 22 13...

Page 24: ...os 4 Auto Chaos 4 Auto Chaos Dehumidification pts hr 2 3 2 3 2 5 3 0 2 5 Indoor dB A 31 29 22 37 31 27 39 25 21 43 39 31 39 25 21 Outdoor dB A 50 50 50 50 50 Electrical Rated Voltage Outdoor 230 208 60 1 230 208 60 1 230 208 60 1 230 208 60 1 230 208 60 1 Rated Voltage Indoor 36V DC 36V DC 36V DC 36V DC 36V DC Indoor Dimensions 33 1 16 x 22 13 32 x 35 3 16 x 22 13 32 x 36 x W x H x D inches 10 5 8...

Page 25: ... LMO240C 24 000 230 208 1 1 1 20 30 Units A C LMO360C 36 000 230 208 16 6 30 40 H P LMO240H 24 000 230 208 1 1 1 20 30 H P LMO360H 36 000 230 208 16 6 30 40 All equipment single phase NOTE Please consult local electrical codes for proper wire requirements Minimum Circuit Ampacity Maximum Overcurrent Protection HIGH WALL DUCTLESS FLEX MULTI SPLIT DUAL AND TRI ZONE ELECTRICAL AND REFRIGERATION QUICK...

Page 26: ... units are available in a variety of styles including Art Cool and Standard models Dual Tri and Quad Zone are inverter driven Heat Pump systems Flex Multi Split Standard Indoor Unit Flex Multi Split Ceiling Cassette Ceiling Concealed Duct Dual Zone Flex Multi Split System Mix and match for 18 000 24 000 BTUs Heat Pump Inverter Available styles and finishes Flex Multi Split Art Cool Indoor Unit Mir...

Page 27: ...24 FLEX MULTI SPLIT ...

Page 28: ...gy Wide Choice of Indoor Units Standard Art Cool Concealed Ducted Cassette Types Design Flexibility Outdoor units connect to any indoor unit style DUAL ZONE LMU185HV Outdoor Units Heat Pump Inverter TRI ZONE LMU245HV QUAD ZONE LMU365HV NOTE LG Wireless Wall Thermostat ...

Page 29: ...3x31 8x12 6 Net Weight lbs 115 143 3 143 3 Max of Connectable Indoor Units 2 3 4 Refrigerant Charge at 24 6 ft oz 59 97 89 95 89 95 Type R410A R410A R410A Control EEV EEV EEV Sound Level H L Sound Pressure dB A 3 51 45 52 52 Piping Connections Liquid inch 1 4 x 2EA 1 4 x 3EA 1 4 x 4EA Gas inch 3 8 x 2EA 3 8 x 3EA 3 8 x 4EA Piping length spec Max total piping ft 164 0 246 1 246 1 Max OD ID piping f...

Page 30: ...20 9 20 9 28 7 Net Weight Decorative Panel lbs STANDARD FLEX MULTI SPLIT LMN095HV H P Model LMN125HV H P Model LMN185HV H P Model Inverter Compressor Chaos Swing Jet Cool Plasma air purifying system Self cleaning indoor coil Auto operation Artificial Intelligence Auto restart operation 24 Hour on off timer Interior Unit Includes Wall unit Installation plate hardware Wireless LCD remote control bat...

Page 31: ...ative Panel lbs ART COOL FLEX MULTI SPLIT LMAN095HV H P Model LMAN125HV H P Model LMAN185HV H P Model Changeable front color panel option Inverter Compressor Chaos Swing Jet Cool Plasma air purifying system Self cleaning indoor coil Auto operation Artificial Intelligence Auto restart operation 24 Hour on off timer Interior Unit Includes Wall unit Installation plate hardware Wireless LCD remote con...

Page 32: ...orative Panel inches Net Weight Body lbs 45 2 45 2 58 4 Net Weight Decorative Panel lbs CEILING CONCEALED DUCT FLEX MULTI SPLIT LMDN095HV H P Model LMDN125HV H P Model LMDN185HV H P Model Inverter Compressor Drain pump Control lock function Auto operation Artificial Intelligence Auto restart operation 2 thermistor control Interior Unit Includes Ceiling unit Owner s manual Installation manual FEATU...

Page 33: ...MCN125HV H P Model LMCN185HV H P Model Inverter Compressor Drain pump Jet Cool Plasma air purifying system Control lock function Auto operation Artificial Intelligence Auto restart operation 24 Hour on off timer 2 thermistor control Interior Unit Includes Ceiling unit Wireless LCD remote control batteries Owner s manual Installation manual Ceiling Grill required Order Seperately PT_UMC 37 13 32 x ...

Page 34: ... 15 0 25 0 25 0 15 0 15 0 25 0 25 MCA 12 6 16 4 19 0 MOP 30 30 40 Flex Multi Split Type H P H P H P H P H P H P H P H P H P H P H P Model LMN095HV LMAN095HV LMDN095HV LMN125HV LMAN125HV LMDN125HV LMCN125HV LMN185HV LMAN185HV LMDN185HV LMCN185HV Pipe size Liquid Suction 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 1 2 1 4 1 2 1 4 1 2 1 4 1 2 Additional Refrigerant 0 22 oz ft 0 22 oz ...

Page 35: ...3 Ducted Indoor Unit 24 000 11 5 18 1 28 800 3 3 20 168 2 6 9 8 Mixed Ducted Non Ducted 24 000 12 0 18 6 28 800 3 3 20 664 2 5 10 1 LMU365HV Non Ducted Indoor Unit 34 000 9 6 18 5 37 000 2 9 26 100 2 3 9 8 Ducted Indoor Unit 34 000 9 1 17 6 37 000 3 1 27 405 2 4 9 3 Mixed Ducted Non Ducted 34 000 9 4 18 1 37 000 3 0 26 750 2 3 9 6 Accessory Wired Wall Thermostat for Flex Multi Split System Applied...

Page 36: ...12 13 200 2 INDOOR UNITS 9 9 18 8 800 8 800 9 12 21 8 143 10 857 12 12 24 9 500 9 500 Ducted Type Indoor Unit Cooling Combination of Each Capacity Indoor Unit kBTU h Class INDOOR UNIT UNIT A UNIT B UNIT C UNIT D Total UNIT A UNIT B UNIT C UNIT D BTU h BTU h BTU h BTU h 1 INDOOR UNIT 9 9 9 000 12 12 12 000 2 INDOOR UNITS 9 9 18 9 000 9 000 9 12 21 7 714 10 286 12 12 24 9 000 9 000 Heating Combinati...

Page 37: ...1 700 2 060 4 4 7 4 8 9 3 1 8 3 11 400 3 4 19 000 5 6 21 300 6 3 1 100 1 840 2 180 4 9 8 1 9 6 3 2 8 3 Total Capacity Input W Current A EER SEER Min Rated Max BTU h kW BTU h kW BTU h kW Min Rated Max Min Rated Max Rated Rated 6 300 1 9 9 000 2 6 9 900 2 9 550 890 1 030 2 3 4 0 4 7 9 9 7 200 2 1 12 000 3 5 13 200 3 9 670 1 120 1 390 2 8 4 9 6 0 10 1 10 800 3 2 18 000 5 3 19 000 5 6 790 1 320 1 810 ...

Page 38: ...9 9 900 12 12 13 200 18 18 19 800 2 INDOOR UNITS 9 9 18 10 350 10 350 9 12 21 10 350 13 800 12 12 24 14 400 14 400 9 18 27 9 600 19 200 12 18 30 11 520 17 280 3 INDOOR UNITS 9 9 9 27 9 600 9 600 9 600 9 9 12 30 8 640 8 640 11 520 9 12 12 33 7 855 10 473 10 473 Ducted Type Indoor Unit Cooling Combination of Each Capacity Indoor Unit kBTU h Class INDOOR UNIT UNIT A UNIT B UNIT C UNIT D Total UNIT A ...

Page 39: ... 6 7 1 554 2 590 3 090 6 9 11 4 14 1 2 3 8 5 14 490 4 3 24 150 7 1 26 560 7 8 1 608 2 680 3 100 7 2 12 0 13 9 2 6 8 5 17 280 5 1 28 800 8 5 32 000 9 4 1 716 2 860 3 300 7 5 12 4 14 6 3 0 8 5 17 280 5 1 28 800 8 5 33 000 9 7 1 716 2 860 3 300 7 5 12 4 14 6 3 0 8 7 17 280 5 1 28 800 8 5 33 000 9 7 1 932 3 220 3 500 8 4 14 0 15 5 2 6 8 7 17 280 5 1 28 800 8 5 33 000 9 7 1 596 2 660 3 300 7 1 11 8 14 ...

Page 40: ...IT C UNIT D BTU h BTU h BTU h BTU h 1 INDOOR UNIT 9 9 9 000 12 12 12 000 18 18 18 000 2 INDOOR UNITS 9 9 18 9 000 9 000 9 12 21 9 000 12 000 12 12 24 12 000 12 000 9 18 27 9 000 18 000 12 18 30 11 600 17 400 18 18 36 16 500 16 500 3 INDOOR UNITS 9 9 9 27 9 000 9 000 9 000 9 9 12 30 9 000 9 000 12 000 9 12 12 33 8 618 11 491 11 491 12 12 12 36 11 333 11 333 11 333 9 9 18 36 8 500 8 500 17 000 9 12 ...

Page 41: ... 6 9 10 8 11 6 15 1 12 600 3 7 21 000 6 2 23 100 6 8 1 025 1 708 2 632 4 4 7 4 11 7 12 3 15 3 14 400 4 2 24 000 7 1 26 400 7 8 1 116 1 860 2 830 4 7 7 8 12 5 12 9 15 7 16 200 4 8 27 000 7 9 29 700 8 7 1 320 2 200 3 270 5 6 9 3 14 4 12 3 16 4 17 400 5 1 29 000 8 5 32 000 9 4 1 578 2 630 3 710 6 5 10 8 16 3 11 0 16 4 19 800 5 8 33 000 9 7 35 000 10 3 2 124 3 540 3 920 8 5 14 2 17 3 9 3 16 4 16 200 4...

Page 42: ...OR UNITS 9 9 9 9 36 9 250 9 250 9 250 9 250 9 9 9 12 39 8 538 8 538 8 538 11 385 9 9 12 12 42 7 929 7 929 10 571 10 571 9 12 12 12 45 7 400 9 867 9 867 9 867 9 9 9 18 45 7 400 7 400 7 400 14 800 Ducted Type Indoor Unit Cooling Combination of Each Capacity Indoor Unit kBTU h Class INDOOR UNIT UNIT A UNIT B UNIT C UNIT D Total UNIT A UNIT B UNIT C UNIT D BTU h BTU h BTU h BTU h 1 INDOOR UNIT 9 9 9 0...

Page 43: ... 4 100 9 8 16 3 18 5 2 9 9 4 22 200 6 5 37 000 10 9 41 000 12 1 2 220 3 700 4 100 9 8 16 3 18 5 2 9 9 8 22 200 6 5 37 000 10 9 42 300 12 4 2 220 3 700 4 100 9 8 16 3 18 5 2 9 9 8 22 200 6 5 37 000 10 9 41 600 12 2 2 220 3 700 4 100 9 8 16 3 18 5 2 9 9 8 22 200 6 5 37 000 10 9 42 000 12 3 2 220 3 700 4 100 9 8 16 3 18 5 2 9 9 8 22 200 6 5 37 000 10 9 42 000 12 3 2 220 3 700 4 100 9 8 16 3 18 5 2 9 ...

Page 44: ...h BTU h BTU h 1 INDOOR UNIT 9 9 9 900 12 12 13 200 18 18 19 800 2 INDOOR UNITS 9 9 18 10 350 10 350 9 12 21 10 350 13 800 12 12 24 13 800 13 800 9 18 27 10 350 20 700 12 18 30 13 340 20 010 18 18 36 18 975 18 975 3 INDOOR UNITS 9 9 9 27 10 350 10 350 10 350 9 9 12 30 10 350 10 350 13 800 9 12 12 33 9 911 13 215 13 215 12 12 12 36 12 333 12 333 12 333 9 9 18 36 9 250 9 250 18 500 9 12 18 39 8 538 1...

Page 45: ...2 950 6 9 11 4 13 2 2 8 8 1 16 560 4 9 27 600 8 1 30 360 8 9 1 580 2 630 3 140 7 1 11 8 12 7 3 1 8 1 18 630 5 5 31 050 9 1 34 150 10 0 1 680 2 800 3 330 7 5 12 6 14 9 3 2 8 3 20 010 5 9 33 350 9 8 36 680 10 8 1 780 2 970 3 810 8 0 13 3 17 1 3 3 8 3 22 770 6 7 37 950 11 2 40 000 11 8 2 060 3 430 3 810 8 0 13 3 17 1 3 2 8 3 18 630 5 5 31 050 9 1 35 700 10 5 1 710 2 850 3 330 7 6 12 7 14 3 3 2 8 5 20...

Page 46: ...tte models are ideal for light commercial applications and work well in large open spaces The ceiling cassette is a useful alternative when floor space is limited The outdoor and indoor unit for all models operate on high voltage 230 208 power Ductless Split Floor Standing Indoor Units Brushed Metal Finish Ductless Split Ceiling Cassette Indoor Units White Finish 42 000 BTUs 24 000 BTUs 42 000 BTU...

Page 47: ...Heating F 60 86 60 86 LG verified sound ratings Warranty 2 years parts 5 years compressor See page 46 for electrical specifications refrigerant line requirements formulas 24 000 BTUs LF245HV H P Model 24 000 BTUs Cooling 24 000 BTUs Heating FEATURES Inverter Compressor R 410a Refrigerant Chaos Swing Three dimensional cooling Jet Cool Cooling mode Dehumidifying mode Evaporator frost control 7 Hour ...

Page 48: ...ears parts 5 years compressor See page 46 for electrical specifications refrigerant line requirements formulas 24 000 BTUs DUCTLESS CEILING CASSETTE SINGLE ZONE LC425HV H P Model 42 000 BTUs Cooling 44 000 BTUs Heating 42 000 BTUs FEATURES Inverter Compressor R 410A Refrigerant Internal condensate pump included Lifts 27 from bottom of machine Swirl Wind Four way cooling Jet Cool Cooling mode Dehum...

Page 49: ...se DUCTLESS FLOOR STANDING CEILING CASSETTE SINGLE ZONE ELECTRICAL REFRIGERATION QUICK REFERENCE Figure A Example 25 ft maximum eleva tion Floor Standing Ceiling Cassette Type H P H P H P H P System LF245HV LF425HV LC245HV LC425HV Indoor Outdoor 230 208 230 208 230 208 230 208 230 208 230 208 230 208 230 208 Voltage BTUs 24 000 42 000 24 000 42 000 Rated Amps 11 5 11 5 20 0 20 0 11 5 12 4 11 5 16 ...

Page 50: ...ficiency ratings up to 12 5 SEER these units are also your energy efficient choice Other features include standard connections for remote thermostat and front desk controls Gold Fin technology protects the unit from the corrosive effects of outside air and extends the operating life of PTAC models The industry standard size makes installation easy and economical 7 000 15 000 BTUs Digital Control P...

Page 51: ...86 54 86 54 86 54 86 54 86 54 86 54 86 LG verified sound rating Adjustable by temperature limiting with DIP switches on the unit Features Gold FinTM anti corrosion treatment Cooling mode Heating mode Fan mode Energy saver mode Auto restart Wall thermostat temperature control connection Front desk control connection DIP switch settings for max and min energy conservation Evaporator frost control Te...

Page 52: ... after a power failure ADA compliant Freeze Room Protection Electronic temperature controls constantly monitor and maintain indoor temperature to prevent freezing Ceramic Heater Even stable and safe heating platform PTAC FEATURES BENEFITS 1 year full system warranty parts and labour Warranty on unit for 2 5 years parts only exclusive of the refrigeration system Warranty on sealed refrigeration sys...

Page 53: ...sor Digital Touch Screen Controls Built In Occupancy Sensor Built In Energy Management Controls True Wireless RF Communication Installs in as little as 10 minutes Easy to program Wireless Energy Management Digital Thermostat Control Board included in Wireless Wall Thermostat kit Snaps directly on to PTAC control board no tools required Sensors 4 sensors provide highly efficient operation and maxim...

Page 54: ... PYRCUCC0A 1 10V Power Adapter PYRCUCC1A option for wireless wall thermostat Architecture Grille Aluminum AYAGALA01A 42 Wall Sleeve AYSVB01A 42 Stamped Aluminum Grille AYRGALA01 PACKAGED TERMINAL AIR CONDITIONERS PARTS AND ACCESSORIES PACKAGED TERMINAL AIR CONDITIONERS PARTS ACCESSORIES CFM Heating BTUs Hydronic Steam 270 300 335 355 390 420 14 500 15 500 16 500 17 000 17 500 18 500 18 500 19 500 ...

Page 55: ... white display INSTALLATION FEATURES System Configuration Menu allows selection of either Heat Pump or Air Conditioner compressor type for optimum system integration and performance Advanced Settings Menu allows pre programming of fan speeds for maximum comfort and energy efficiency Temperature Display lets you select Fahrenheit or Celsius readings COMPONENTS INCLUDED LG Wireless Wall Thermostat w...

Page 56: ...53 Stabs bacteria Breaks it Deodorizes ...

Page 57: ...54 NOTES ...

Page 58: ...55 NOTES ...

Page 59: ...NOTES 56 ...

Page 60: ...LG Electronics Canada Inc 1 888 LG Canada 542 2623 LG ca ...