![LG LMU365HV Specifications Download Page 32](http://html.mh-extra.com/html/lg/lmu365hv/lmu365hv_specifications_1891763032.webp)
29
9,000-18,000 BTUs
Indoor Model H/P Inverter #
LMDN095HV
LMDN125HV
LMDN185HV
Performance
Capacity*
9,000 BTU/h Class
12,000 BTU/h Class
18,000 BTU/h Class
Fan Air Flow Rate (CMM)
8.5/7.5/6.5
9.5/8.5/7.5
15/13.5/11.5
Fan H/M/L (CFM)
300/265/230
336/300/265
530/477/406
Dehumidification Rate (Pts/hr)
2.1
2.5
4.2
Sound Level H/M/L (dB(A)+3)
32/26/25
33/31/26
34/31/29
Electrical
Nominal Running Current (A)
0.25
0.25
0.25
Power Supply (Ø/V/Hz)
1/208~230/60
1/208~230/60
1/208~230/60
Piping Connections
Liquid (inches)
1/4
1/4
1/4
Gas (inches)
3/8
3/8
1/2
Drain OD,ID (inches)
1 1/4, 1
1 1/4, 1
1 1/4, 1
Temperature Sensor
Thermistor
Thermistor
Thermistor
Refrigerant
R410a
R410a
R410a
Connectable Outdoor Unit
Multi F series
Multi F series
Multi F series
Power/Transmission Interunit Cable (No. x AWG)
14/3
14/3 14/3
Coil (Row/Column/FPI)
2R x 12C x 21
2R x 12C x 21
2R x 11C x 21
Dimensions (WxHxD)
Body (inches)
32.3 x 7.5 x 22.6
32.3 x 7.5 x 22.6
43.3 x 7.5 x 22.6
Decorative Panel (inches)
-
-
-
Net Weight Body (lbs)
45.2
45.2
58.4
Net Weight Decorative Panel (lbs)
-
-
-
CEILING CONCEALED DUCT • FLEX MULTI-SPLIT
LMDN095HV
(H/P Model)
LMDN125HV
(H/P Model)
LMDN185HV
(H/P Model)
•
Inverter Compressor
•
Drain pump
•
Control lock function
•
Auto operation (Artificial
Intelligence)
•
Auto restart operation
•
2 thermistor control
Interior Unit Includes:
•
Ceiling unit
•
Owner’s manual
•
Installation manual
FEATURES:
*Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 80ºF (26.7ºC ) DB/67ºF (19.4ºC) WB
- Outdoor Temperature 95ºF (35ºC) DB/75ºF (23.9ºC) WB
Heating: - Indoor Temperature 70ºF (21.1ºC) DB/60ºF (15.6ºC) WB
- Outdoor Temperature 47ºF (8.3ºC) DB/43ºF (6.1ºC) WB
Piping Length: - Interconnecting Piping Length 24.6 ft.(7.5m)
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national codes.
3. The specification may be subject to change without prior notice for purpose of
improvement.
4. For more capacity(*) information, refer to the combination tables.
Warranty: 2 years parts; 5 years compressor.
See page 31 for electrical specifications, refrigerant line requirements & formulas.
•
Optional wired remote control
Summary of Contents for LMU365HV
Page 2: ......
Page 7: ...4 THE LG HVAC ADVANTAGE ...
Page 27: ...24 FLEX MULTI SPLIT ...
Page 56: ...53 Stabs bacteria Breaks it Deodorizes ...
Page 57: ...54 NOTES ...
Page 58: ...55 NOTES ...
Page 59: ...NOTES 56 ...
Page 60: ...LG Electronics Canada Inc 1 888 LG Canada 542 2623 LG ca ...