ERROR CODE TABLES
Error
Code
Description
No. of Times Outdoor Unit LEDs
Blink
Outdoor
Operation
Status
LED01 (Red)
LED02 (Green)
21
DC Peak (IPM Fault); Compressor DC voltage was too high
2X
1X
OFF
22
Current Transformer2 (CT2) error; Alternating current (AC) input too high
2X
2X
OFF
23
DC Link Low Voltage (DC Link Voltage is <140VDC)
2X
3X
OFF
DC Link High Voltage (DC Link Voltage is >420VDC)
25
AC Low / High Voltage
2X
5X
OFF
26
DC Compressor Position Error (Compressor failed to start properly)
2X
6X
OFF
27
PSC / PFC Fault; Input current to inverter compressor PCB is too high
2X
7X
OFF
29
Current to inverter compressor is too high
2X
9X
OFF
32
Inverter compressor discharge pipe (D-Pipe) temperature is too high
3X
2X
OFF
35
Low Pressure Error; Pressure dropped below recommended limits
3X
5X
OFF
39
Communication Error between PFC MICOM and Inverter MICOM
3X
9X
OFF
40
CT Sensor Error; Thermistor is disconnected or has shorted out
4X
-
OFF
41
Inverter compressor discharge pipe (D-Pipe) sensor is disconnected or has shorted out
4X
1X
OFF
43
High pressure sensor is disconnected or has shorted out
4X
3X
OFF
44
Outdoor air sensor is disconnected or has shorted out
4X
4X
OFF
45
Mid-pipe thermistor of outdoor unit condenser is disconnected or has shorted out
4X
5X
OFF
46
Outdoor unit suction piping thermistor is disconnected or has shorted out
4X
6X
OFF
48
Outlet piping (liquid) of condenser is disconnected or has shorted out
4X
8X
OFF
51
Combination ratio (capacity) is out of range; Total nominal indoor unit capacity is<50%
or >130% of the outdoor unit capacity
5X
1X
OFF
53
Communication failure between outdoor unit and indoor unit(s)
5X
3X
OFF
54
Outdoor unit is not wired properly (ex: reversed phase)
5X
4X
OFF
60
Outdoor unit printed circuit board (PCB) EEPROM check sum error
6X
-
OFF
61
Condenser coil thermistor temperature is too high
6X
1X
OFF
62
Outdoor unit inverter compressor PCB heat sink temperature is too high
6X
2X
OFF
65
Heat sink thermistor is disconnected or has shorted out
6X
5X
OFF
67
Outdoor unit brushless direct current (BLDC) fan motor lock error
6X
7X
OFF
73
Outdoor unit PFC overcurrent (peak) error
7X
3X
OFF
Table 42: Outdoor Unit Error Codes.