FINAL INSTALLATION PROCEDURES
Forced Cooling Operation Function
Use to add refrigerant to the system when outside ambient temperatures are cool (ex.: winter).
1. Shut power down to the system.
2. Set DIP Switch 1 to ON.
3. Turn power on to the system.
4. Verify that the Red LED on the outdoor unit PCB is ON (indicates indoor units are in forced cooling
operation).
5. Add refrigerant.
• If the green LED light on the outdoor unit PCB is ON, it indicates the compressor is OFF due to low pressure in the system.
• Turn DIP Switch 1 to OFF after finishing (Normal Operation setting).
• Only the first four DIP switches are functional on the LMU480, 540, 600HV.
Multi F LMU18CHV and LMU24CHV
DI P- SW
SW01 N
DIP SW
2
Multi F LMU30CHV and LMU36CHV
Multi F MAX LMU480HV and LMU540HV
DIP-SW01D
12
3
4
56
7
8
9
1
0
Multi F MAX LMU600HV
Location of DIP Switches on Multi F and Multi F MAX Outdoor Units
Figure 112: Multi F / Multi F MAX Outdoor Unit DIP Switch Locations.
1 2
4
3
1 2
4
3
ON
OFF
Figure 113: Forced Cooling DIP
Switch Setting.