8
ENGLISH
Level gauge
Ceiling
Ceiling board
Unit:mm(inch)
875(34-7/16) (Ceiling opening)
787(30-15/16)
(Hanging bolt)
bolt)
TM/TN/TP Chassis
Unité:mm
67
1(
2
6
-7
/1
6
)
TQ/TR Series
585~660
517
461
517
585~660
523
570
570
319
840(33-1/16)
Unit size
840(33-
1/
16)
Unit siz
e
CAUTION
• This air-conditioner uses a drain pump.
• Install the unit horizontally using a level
gauge.
• During the installation, care should be
taken not to damage electric wires.
!
THE INDOOR UNIT INSTALLATION
THE INDOOR UNIT INSTALLATION
- Select and mark the position for fixing bolts
and piping hole.
- Decide the position for fixing bolts slightly
tilted to the drain direction after considering
the direction of drain hose.
- Drill the hole for anchor bolt on the wall.
- When using cardboard on the bottom of
packaging, use after separating installation
paper from bottom of the product packaging
using back of a knife as shown in the picture
(TM/TN/TP/TQ/TR)
Included Paper
Cardboard on the bottom
of packaging
NOTE
!
Avoid the following installation location.
1
Such places as restaurants and kitchen
where considerable amount of oil steam
and flour is generated. These may cause
heat exchange efficiency reduction, or
water drops, drain pump mal-function. In
these cases, take the following actions;
- Make sure that ventilation fan is enough
to cover all noxious gases from this
place.
- Ensure enough distance from the cooking
room to install the air conditioner in such
a place where it may not suck oily steam.
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table
Air conditioner
Take enough
distance
Summary of Contents for LDN097HV4
Page 20: ...20 ENGLISH ...