52 | Four-Way caSSette
Four-W
ay Ceiling Cassette System Engineering Manual
PlaCement ConSiDerationS
Clearance Requirements when Different Obstacles are Present, continued. (Unit: Inch)
L
Minimum 39-3/8"
Minimum 39-3/8
"
Maximum 19-11/16"
Minimum 11-13/16"
Where there are obstacles on both suction
and discharge sides (discharge side obstacle
is lower than the outdoor unit).
Where there are obstacles above, and on both
suction and discharge sides (discharge side obstacle
is lower than the outdoor unit).
Minimum 19-11/16"
Minimum 11-13/16
"
H
Minimum 11-13/16"
Minimum 78-3/4"
Minimum 23-19/32"
Minimum 39-3/8"
Series installation
“L” should be lower than “H”. If
a stand is necessary, it should
be contained (not open frame)
to prevent the discharge air from
short cycling.