Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Four-Way caSSette | 45
Application Guidelines
PlaCement ConSiDerationS
Indoor unit
Selecting the Best location
Do’s
•
Place the unit where air circulation will not be blocked.
•
Place the unit where drainage can be obtained easily.
•
Place the unit where noise prevention is taken into consideration.
•
Ensure there is sufficient strength to bear the load of the indoor unit.
•
Ensure there is sufficient maintenance space.
•
Locate the indoor unit in a location that is level, and where it can be easily connected to the outdoor unit.
Don’ts
•
The unit should not be installed near a heat or steam source, or where considerable amounts of oil, iron powder, or flour are used.
•
The unit should not be installed where sulfuric acid and flammable or corrosive gases are generated, vented into, or stored.
•
Avoid installing the unit near high-frequency generators or near any equipment that generates an electromagnetic field (minimum 3-1/3
feet away).
•
Do not install the unit near a doorway.
the unit may be damaged, may malfunction, and / or will not operate as designed if installed in any of the conditions listed.
Installing in a High or Dropped Ceiling
High or dropped ceilings, often found in commercial buildings and offices, may cause a wide temperature differentiation. To countermeasure:
•
Change the indoor unit mode selection to allow for higher ceilings (see table).
•
Install an air circulator.
•
Set the air discharge outlet so that heated air flows in a downward direction.
•
Use a dual door system to protect the building gate or exit.
If the unit is installed near a body of water, certain components are at risk of being corroded. Appropriate anti-corrosion methods should be taken
for the unit and all components.
Ceiling Height
Mode Selection
≤7-1/2 feet
Low Ceiling
7-1/2 feet to 8-7/8 feet
Standard
8-7/8 feet to 10-3/16 feet
High Ceiling
10-3/16 feet to 11-13/16 feet
Very High Ceiling
Table 28: Indoor Unit High Ceiling Mode Selection Options (LCN187HV,
LCN247HV).
Ceiling Height
Mode Selection
≤8-7/8 feet
Low Ceiling
8-7/8 feet to 10-1/2 feet
Standard
10-1/2 feet to 11-13/16 feet
High Ceiling
11-13/16 feet to 13-13/16 feet
Very High Ceiling
Table 29: Indoor Unit High Ceiling Mode Selection Options (LCN367,
LCN427HV ).