cooling capacity tables
PerFormanCe Data
Model No. /
Nominal Capacity
(Btu/h)
Outdoor
Air Temp.
(°F DB)
Indoor Air Temp. °F DB / °F WB
68 / 57
73 / 61
77 / 64
80 / 67
86 / 72
90 / 75
TC SHC
PI
TC SHC
PI
TC SHC
PI
TC SHC
PI
TC SHC
PI
TC SHC
PI
LC427HV /
42,000
5
41.60
30.30
1.62
44.19
32.00
2.20
46.77
32.94
2.38
48.64
31.64
2.42
51.94
31.91
2.42
54.52
32.51
2.42
10
41.54
30.52
1.67
44.12
32.24
2.26
46.70
33.18
2.45
48.57
31.87
2.49
51.86
32.14
2.49
54.44
32.75
2.48
15
41.48
30.74
1.71
44.06
32.47
2.32
46.64
33.42
2.51
48.50
32.10
2.55
51.79
32.37
2.56
54.36
32.98
2.55
20
41.42
30.96
1.76
44.00
32.70
2.38
46.57
33.66
2.58
48.43
32.33
2.62
51.71
32.60
2.63
54.29
33.22
2.62
25
41.36
31.18
1.80
43.93
32.93
2.45
46.50
33.90
2.65
48.36
32.56
2.69
51.64
32.83
2.69
54.21
33.45
2.69
30
41.30
31.39
1.85
43.87
33.16
2.51
46.43
34.14
2.71
48.29
32.79
2.76
51.57
33.06
2.76
54.13
33.69
2.75
35
41.24
31.61
1.89
43.81
33.39
2.57
46.37
34.37
2.78
48.22
33.01
2.82
51.49
33.29
2.83
54.05
33.92
2.82
40
41.18
31.83
1.94
43.74
33.62
2.63
46.30
34.61
2.85
48.15
33.24
2.89
51.42
33.52
2.90
53.97
34.15
2.89
45
41.13
32.04
1.99
43.68
33.85
2.69
46.23
34.84
2.91
48.08
33.46
2.96
51.34
33.75
2.96
53.90
34.38
2.96
50
41.07
32.26
2.03
43.62
34.07
2.75
46.17
35.08
2.98
48.01
33.69
3.03
51.27
33.97
3.03
53.82
34.62
3.03
55
41.01
32.47
2.08
43.55
34.30
2.82
46.10
35.31
3.05
47.94
33.91
3.10
51.19
34.20
3.10
53.74
34.85
3.09
60
40.95
32.68
2.12
43.49
34.53
2.88
46.03
35.54
3.11
47.87
34.13
3.16
51.12
34.42
3.17
53.66
35.07
3.16
65
40.89
32.90
2.17
43.43
34.75
2.94
45.97
35.77
3.18
47.80
34.36
3.23
51.04
34.65
3.24
53.58
35.30
3.23
70
40.83
33.11
2.21
43.36
34.97
3.00
45.90
36.00
3.25
47.73
34.58
3.30
50.97
34.87
3.30
53.50
35.53
3.30
75
39.84
32.56
2.36
42.37
34.44
3.10
44.90
35.50
3.34
46.73
34.12
3.39
49.96
34.45
3.42
52.49
35.13
3.44
80
38.86
32.01
2.50
41.39
33.90
3.19
43.91
34.98
3.42
45.73
33.65
3.49
48.95
34.01
3.54
51.48
34.72
3.59
85
37.89
31.42
2.84
40.41
33.33
3.47
42.92
34.43
3.67
44.74
33.15
3.74
47.96
33.55
3.80
50.47
34.28
3.86
90
36.91
30.83
3.18
39.43
32.75
3.74
41.94
33.88
3.92
43.75
32.64
3.98
46.96
33.08
4.06
49.47
33.83
4.14
95
35.86
30.51
3.52
38.36
32.45
3.99
40.85
33.62
4.14
42.00
31.92
4.07
45.85
32.91
4.27
48.35
33.68
4.35
100
34.98
29.69
3.69
37.48
31.63
4.07
39.98
32.81
4.17
41.46
31.43
4.14
44.98
32.20
4.27
47.47
32.99
4.35
105
34.11
28.87
3.87
36.61
30.82
4.15
39.11
32.02
4.19
40.91
30.93
4.21
44.10
31.49
4.26
46.60
32.30
4.36
110
33.24
27.88
3.76
35.74
29.82
3.92
38.23
31.03
3.91
40.04
30.01
3.89
43.23
30.60
3.93
45.73
31.41
4.02
115
32.37
27.05
3.38
34.86
28.98
3.41
37.36
30.20
3.33
39.17
29.24
3.29
42.36
29.87
3.30
44.86
30.70
3.37
118
30.57
25.78
2.99
32.97
27.65
2.94
35.36
28.85
2.81
37.10
27.95
2.75
40.16
28.57
2.74
42.56
29.39
2.81
122
29.97
25.35
2.86
32.33
27.20
2.79
34.70
28.39
2.64
36.41
27.51
2.57
39.43
28.14
2.56
41.79
28.95
2.63
Table 19: LC427HV System Cooling Capacity Table.
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
PI = Power input (KW). Power input (KW) includes compressor and fan(s).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor
unit. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table rows indicate reference data. When operating at this temperature, these values can
be different if the system is not running consistently.