background image

Service Manual 

21

Troubleshooting Guide 

COMPLAINT

CAUSE

REMEDY

Check the position of knob If not at the coldest set-
ting, advance the knob to this setting and restart unit.
Check continuity of the thermostat. Replace thermo-
stat if circuit is open.

Check the TEMP control. If not at the lowest number,
set TEMP control to this setting and restart the unit.
Check the continuity of the thermistor. Replace the
thermistor if the circuit is open.

Check the capacitor.
Replace if not within ±10% of manufacturers rating.
Replace if shorted, open, or damaged.

Check the compressor for open circuit or ground. If
open or grounded, replace the compressor.

Check the compressor overload, if externally mount-
ed. Replace if open. (If the compressor temperature
is high, remove the overload, cool it, and retest.)

Check the voltage.
If not within limits, call an electrician.

Check overload, if externally mounted.
Replace if open. (If the compressor temperature is
high, remove the overload, cool, and retest.)

If not running, determine the cause. Replace if
required.

Remove the cabinet. inspect the interior surface of
the condenser; if restricted, clean carefully with a
vacuum cleaner (do not damage fins) or brush.
Clean the interior base before reassembling.

If condenser fins are closed over a large area on the
coil surface, head pressures will increase, causing
the compressor to overload. Straighten the fins or
replace the coil.

Test capacitor.

Check the terminals. If loose, repair or replace.

Check the system for a restriction.

If restricted, clean of replace.

Close if open.

Determine if the unit is properly sized for the area to
be cooled.

Check the set screw or clamp. If loose or missing,
correct. If the turbo or fan is hitting air guide,
rearrange the air handling parts.

Remove the cabinet carefully and rearrange tubing
not to contact cabinet, compressor, shroud, and bar-
rier.

Thermostat

Thermistor

Capacitor (Discharge
capacitor before servicing.) 

Compressor

Overload

Voltage

Overload

Fan motor

Condenser air flow restric-
tion

Condenser fins (damaged)

Capacitor

Wiring

Refrigerating system

Air filter

Exhaust damper door

Unit undersized

Turbo or fan

Copper tubing

Compressor will not run,
but fan motor runs.

Compressor cycles on
overload.

Compressor cycles on
overload.

Compressor cycles on
overload.

Insufficient cooling or heat-

ing

Excessive noise

Summary of Contents for L6004R

Page 1: ...Window Air Conditioner SVC MANUAL General MODEL Window CAUTION Before Servicing the unit read the safety precautions in General SVC manual Only for authorized service personnel http biz lgservice com ...

Page 2: ...e Manual CONTENTS Safety Precautions 3 Operation 6 Features 6 Control Locations Function of Controls 6 Troubleshooting Guide 9 Piping System 9 Troubleshooting Guide 10 Electrical Parts Troubleshooting Guide 12 Room Air Conditioner Voltage Limits 20 ...

Page 3: ...nts and circuit boards are at main potential when the equipment is connected to the power cables This volt age is extremely dangerous and may cause death or severe injury if come in con tact with it SAFETY PRECAUTIONS 1 When servicing the unit set the main SWITCH to OFF and remove the POWER SUPPLY cables 2 Observe the original lead dress If a short circuit is found replace all parts which have bee...

Page 4: ...leaks during work execute ventilation If the refrigerant gas touches to a fire poisonous gas generates A case of leakage of the refriger ant and the closed room full with gas is dangerous because a shortage of oxy gen occurs Be sure to execute ventilation When removing the front panel or cabinet execute short circuit and discharge between high voltage capacitor terminals If discharge is not execut...

Page 5: ...r If drainage is faulty the water to enter the room and wet floor Check to see if the power cable plug is not dirty or loose If the plug is dust or loose it can cause an electrical shock or fire Do not use a joined power cable or extension cable or share the same power outlet with other electrical appliances otherwise it can cause an electrical shock excessive heat generation or fire Do not insert...

Page 6: ...ted by positioning the knob to the desired position The 5 or 6 position is a normal setting for average conditions Operation Operation Features CLOSE VENT OPEN 1 Thermostat Operation 2 3 4 9 8 7 6 5 Off Med Fan Low Fan High Cool Med Cool Low Cool 1 Thermostat Operation 2 3 4 9 8 7 6 5 Off Med Fan Low Fan High Cool Med Cool Low Cool 0 0 On Off Auto Swing CAUTION A slight heat odor may come from the...

Page 7: ...es sary in accordance with your temperature prefer ence The thermostat automatically controls cooling or heating but the fan runs continuously whenever the air conditioner is in operation If the room is too warm turn the thermostat control clockwise If the room is too cool turn the themostat control counterclockwise OPERATION OFF Turns the air conditioner off LOW FAN Permits the low fan speed oper...

Page 8: ...mer is set by 1 hour FAN SPEED SELECTOR Select the fan speed Cooling Model 3 steps High F3 Low F1 Med F2 High F3 Heating Model 2 steps High F2 Low F1 High F2 ROOM TEMPERATURE SETTING BUTTON Control the room temperature within a range of 16 C to 30 C The room temperature will be adjusted by 1 C 30min and by 2 C 1 hour later SIGNAL RECEIVER AUTO SWING The vertical louver swings horizontally by the a...

Page 9: ... CAPILLARY TUBE OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH SUCTION LINE COOL LOW PRESSURE VAPOR COOLED AIR COMPLETE LIQUID BOIL OFF POINT LIQUID PRESSURE DROP ROOM AIR HEAT LOAD VAPOR INLET HOT DISCHARGED AIR LIQUID OUTLET HIGH PRESSURE VAPOR LIQUID REFRIGERANT LOW PRESSURE VAPOR ROOM AIR CONITIONER EVAPORATOR COILS CONDENSER COILS CYCLE OF REFRIGERATION CAPILLARY TUBE COMPRESSOR BLOWER EVAP...

Page 10: ... fan operation Check gas leakage Repair gas leak Replacement of unit if the unit is beyond repair Satisfactory operation with temperature difference of inlet outlet air 44 50 F 7 10 C Check heat load increase Clean condenser Not on separate circuit Check inside gas pressure Adjusting of refrigerant charged Malfunction of compressor Replacement of compressor Check cold air circulation for smooth fl...

Page 11: ...gular motor insulation Replacement of fan motor Regular but fails to start Replacement of compressor locking of rotor metal Improper thermostat setting Loose terminal connection Improper wiring Irregular motor resistance Irregular motor insulation Replacement of compressor Motor damaged Drop of power voltage Capacitor check Replacement Compressor only fails to start Defect of compressor capacitor ...

Page 12: ... Voltage of IC02D DC 5V Is the voltage No 20 of Micom DC 5V Exchange Main PCB Ass y Is the connection between Main and Display all right Is the reset circuit all right The No 16 of Micom is 5V Check the Fuse Check the wiring diagram Check the Main PCB pattern Exchange the Trans Exchange D02D D05D Exchange IC01D Exchange IC02D Exchange IC01A C02A Connect connector exactly Check the PCB pattern NO N...

Page 13: ...emp 0 5 C Is the voltage No 11 of IC01M 0V Exchange IC01M Select the setting Temp to lower Number Wait 3 Minutes Is the Unit for 3 minutes delay Exchange MAIN PCB Ass y Is the voltage N0 6 of IC01M DC 5V Check the RY COMP Check the wiring Diagram NO NO NO YES YES YES YES Is the wire connection of RY COMP all right Check the RY COMP Connect LEAD Wire to RY COMP again NO YES NO ...

Page 14: ...the voltage NO 2 or 3 or 4 of IC01M DC 5V Is the voltage NO 13 or 14 or 15 of IC01M 0V Check the RY Hi or RY Med or RY Lo Check the wiring diagram NO NO YES YES NO NO YES YES Is the Knob of SW1 set to left position Is the voltage No 1 of CN DISP1 of Main PCB Ass y DC 5V Reference to OWNER S MANUAL Set the Knob of SW1 to left position Check the SW1 Check the pattern of Main Display PCB ...

Page 15: ...nge the display PCB Ass y Exchange IC01G Exchange Q12G Q13G Q14G Connect connector to CN DISP2 exactly Does the Q12G Q13G Q14G operate normally on main PCB Ass y Check the PCB pattern Is the voltage of Battery about over 2 3V Exchange Receiver Ass y Is the connection of CN DISP2 all right Is the voltage No 10 of CN DISP2 on Main PCB Ass y DC 5V Exchange the battery Check the PCB pattern Connect co...

Page 16: ... of IC3 DC 5V Is the voltage No 20 of IC1 DC 5V Exchange Main PCB Ass y Is the connection between Main and Display all right Is the reset circuit all right The No 16 of IC1 is 5V Check the Fuse Check the wiring diagram Check the Main PCB pattern Exchange the Trans Exchange BD1 Exchange IC2 Exchange IC3 Exchange IC4 C07 Connect connector exactly Check the PCB pattern NO NO NO NO NO NO NO YES YES YE...

Page 17: ...m Temp 0 5 C Is the voltage No 10 of IC7 0V Exchange IC7 Select the setting Temp to lower Number Wait 3 Minutes Is the Unit for 3 minutes delay Exchange MAIN PCB Ass y Is the voltage N0 7 of IC 7 DC 5V Check the RY COMP Check the wiring Diagram NO NO NO YES YES YES YES Is the wire connection of RY COMP all right Check the RY COMP Connect LEAD Wire to RY COMP again NO YES NO ...

Page 18: ... 15 of IC7 0V Check the RY High or RY Low Check the wiring diagram NO NO YES YES Is the voltage of Battery about over 2 3V Exchange Receiver Ass y Is the connection of CN DISP2 all right Is the voltage No 7 of CN DISP2 on Main PCB Ass y DC 5V Exchange the battery Check the PCB pattern Connect connector to CN DISP2 exactly NO NO NO YES YES YES Possible Trouble 5 Remote controller does not operate ...

Page 19: ...exactly Does the TR1 TR2 TR3 operate normally on main PCB Ass y NO NO YES YES Is the Knob of SW1 set to left position Is the voltage No 3 of CN DISP2 of Main PCB Ass y DC 5V Reference to OWNER S MANUAL Set the Knob of SW1 to left position Check the SW1 Check the pattern of Main Display PCB Possible Trouble 6 It displays abnormally on display PCB Ass y Possible Trouble 7 The function of Auto Restar...

Page 20: ...otor Pay attention to any change from high speed to low speed If the speed does not change replace the motor If cracked out of balance or partially missing replace it If cracked out of balance or partially missing replace it Tighten it If knocking sounds continue when running or loose replace the motor If the motor hums or noise appears to be internal while running replace motor Check voltage If n...

Page 21: ...ct the interior surface of the condenser if restricted clean carefully with a vacuum cleaner do not damage fins or brush Clean the interior base before reassembling If condenser fins are closed over a large area on the coil surface head pressures will increase causing the compressor to overload Straighten the fins or replace the coil Test capacitor Check the terminals If loose repair or replace Ch...

Page 22: ...P NO MFL37825901 JANUARY 2007 ...

Reviews: