background image

2-way Valve (Liguid Side)

3-way Valve (Gas Side)

Works

Shaft position

Shaft position

Service port

Shipping

Closed

Closed

Closed

(with valve cap)

(with valve cap)

(with cap)

Air purging

Open

Closed

Open

(Installation)

(counter-clockwise)

(clockwise)

(push-pin or with 

vacuum pump)

Operation

Open

Open

Closed

(with valve cap)

(with valve cap)

(with cap)

Pumping down

Closed

Open

Open

(Transfering)

(clockwise)

(counter-clockwise)

(connected 

manifold gauge)

Evacuation

Open

Open

Open

(Servicing)

(with charging  

cylinder)

Gas charging

Open

Open

Open

(Servicing)

(with charging 

cylinder)

Pressure check

Open 

Open

Open

(Servicing)

(with charging 

cylinder)

Gas releasing

Open

Open

Open

(Servicing)

(with charging 

cylinder)

- 39 -

2-way, 3-way Valve

3.

2.

1.

4.

5.

6.

Flare nut

To 

piping 

connection

Open position
Closed position

Flare nut

Valve cap

To 

piping 

connection

Open position
Closed position

Hexagonal wrench
(4mm)

To outdoor unit

Pin

Service 
port

Service 
port cap

To outdoor unit

Summary of Contents for L2-C243AL1

Page 1: ...Multi Type Room Air Conditioner SERVICE MANUAL MODEL LM 1830C2L M N LM 1830H2L M N LM 2430C2L M N LM 2430H2L M L2 C243AL1 ...

Page 2: ... 13 Display Function 20 Self diagnosis Function 20 Installation 21 Operation 35 Disassembly of the parts Indoor Unit 37 2 way 3 way Valve 39 Cycle Troubleshooting Guide 43 Electronic Parts Troubleshooting Guide 45 Electronic Control Device 52 Schematic Diagram 55 Exploded View and Replacement Parts List 57 2 Contents ...

Page 3: ...desired position or swing up and down automatically 3 Functions Indoor Unit Operation ON OFF by Remote controller Sensing the Room Temperature Room temperature control Starting Current Control Time Delay Safety Control Indoor Fan Speed Control Operation indication Lamps LED OUT DOOR Health Dehumidification Operation Both the indoor and outdoor fan stops during deicing Hot start after deice ends Th...

Page 4: ...tting the Time or Timer Airflow Direction Control Operation ON OFF Temperature Setting TEMPERATURE LOW HIGH Timer Selection ON OFF C F Timer Setting SET Timer Cancel CANCEL Fan Operation Mode Reset Fan Speed Selection Low Med High CHAOS Down to 18 C 64 F Up to 30 C 86 F Cooling Cancel Sleep Mode Timer ON or Timer OFF 1 2 3 4 5 6 7 Off Timer Fan Operates without cooling or heating High 39 C 102 F L...

Page 5: ...7 Outdoor 61 Liquid 6 35 1 4 Gas 9 52 3 8 780 780 at 7 5m O L C D Wireless O O Operation A Unit Only B Unit Only A Unit B Unit Remarks Unit Item Cooling Capacity Heating Capacity Moisture Removal h Power Source ø V Hz Air Circulation min Noise Level dB A Input W A E E R Btu h w C O P Dimensions W x H x D mm Net Weight kg Service Valve mm Inch Refrigerant R 22 g Airflow Direction Control Up Down Re...

Page 6: ... 2 78 Indoor 802 x 262 x 165 Outdoor 870 x 655 x 320 Indoor 7 Outdoor 63 Liquid 6 35 1 4 Gas 9 52 3 8 780 780 at 7 5m O L C D Wireless O O Operation A Unit Only B Unit Only A Unit B Unit Remarks Unit Item Cooling Capacity Heating Capacity Moisture Removal h Power Source ø V Hz Air Circulation min Noise Level dB A Input W A E E R Btu h w C O P Dimensions W x H x D mm Net Weight kg Service Valve mm ...

Page 7: ...door 61 Liquid 6 35 1 4 Gas 12 7 1 2 880 880 at 7 5m O L C D Wireless O O Operation A Unit Only B Unit Only A Unit B Unit Remarks Unit Item Cooling Capacity Heating Capacity Moisture Removal h Power Source ø V Hz Air Circulation min Noise Level dB A Input W A E E R Btu h w C O P Dimensions W x H x D mm Net Weight kg Service Valve mm Inch Refrigerant R 22 g Airflow Direction Control Up Down Remote ...

Page 8: ...2 66 2 70 2 66 2 70 Indoor 888 x 287 x 170 Outdoor 870 x 655 x 320 Indoor 7 Outdoor 63 Liquid 6 35 1 4 Gas 12 7 1 2 880 880 at 7 5m O L C D Wireless O O Operation A Unit Only B Unit Only A Unit B Unit Remarks Unit Item Cooling Capacity Heating Capacity Moisture Removal h Power Source ø V Hz Air Circulation min Noise Level dB A Input W A E E R Btu h w C O P Dimensions W x H x D mm Net Weight kg Ser...

Page 9: ...m Center Center ø70mm Left rear piping Right rear piping A A D H W Tubing hole cover W mm 802 888 H mm 262 287 D mm 165 170 LM 1830C2L M LM 1830H2L M LM 2430C2L M LM 2430H2L M MODEL DIM LM 1830C2L M LM 1830H2L M LM 2430C2L M LM 2430H2L M 1 Indoor Unit Pipe Hole Fix Hole Hanger Hole H W D Capacity W H D SP1 Ch 9K 12K 570 568 137 ...

Page 10: ...y valve Liquid side 2 Way valve L7 L5 L6 2 Outdoor Unit W mm 870 H mm 655 D mm 320 L1 mm 370 L2 mm 25 L3 mm 630 L4 mm 25 L5 mm 546 L6 mm 160 L7 mm 160 L8 mm 64 L9 mm 76 5 L10 mm 50 LM 1830C2L M LM 1830H2L M LM 2430C2L M LM 2430H2L M L2 C243AL1 MODEL DIM ...

Page 11: ...utdoor Unit Pipe Size Diameter inch Max piping length m Max piping elevation m Gas Btu h Liquid 1 2 1 4 15 8 3 8 24K 18K 1 4 15 8 ex Capillary Cooling Deice A UNIT B UNIT CAPILLARY TUBE LIQUID SIDE 2 WAY VALVE GAS SIDE 3 WAY VALVE HEAT EXCHANGER EVAPORATOR HEAT EXCHANGER CONDENSER COMPRESSOR B COMPRESSOR A 1 LM 1830C2L M LM 2430C2L M L2 C243AL1 Cooling only models 2 LM 1830H2L M LM 2430H2L M Cooli...

Page 12: ...S C G V S C G V S C G V S BK BR BL RD BK BR BL BK BK BR BL WH BL BL GN YL L2 L1 MAIN POWER FUS250V 2 5A FUS250V 2 5A FUS250V 2 5A FUS250V 2 5A OUTDOOR WIRING DIAGRAM 3854A20075K BK CAPACITOR TRANS FORMER CN SV CN POWER CN COMP1 CN COMP2 FUSE T3 15A CN TRANAS RY COMP A RY COMP B RY FAN1 MAIN DC PCB ASSY MAIN AC PCB ASSY PILLAR TERMINAL TO INDOOR UNIT B INDOOR A INDOOR CAPACITOR BK BK BK YL BK A COM...

Page 13: ...r On while in timer mode on off off when timer mode is completed or canceled Defrost Indicator Off except when hot start during heating mode operation or while in defrost control Cooling Mode Operation When the intake air temperature reaches 0 5 C below the setting temp the compressor and the outdoor fan stop When it reaches 0 5 C above the setting temp they start to operate again Compressor ON Te...

Page 14: ... with the low airflow speed If overloaded while in heating mode operation in order to prevent the compressor from OLP operation the outdoor fan is turned on off according to the indoor pipe temp While in defrost control both of the indoor and outdoor fans are turned off Defrost Control H P model Defrost operation is controlled by timer and sensing temperature of outdoor pipe The first defrost star...

Page 15: ...oor fan is operated for 15 seconds Then an operation mode is selected according to the intake air temp at that moment as follows 24 C Inatake Air Temp Fuzzy Operation for Cooling 21 C Inatake Air Temp 24 C Fuzzy Operation for Dehumidification Inatake Air Temp 21 C Fuzzy Operation for Heating If any of the operation modes among cooling dehumidification heating mode operations is carried out for 10 ...

Page 16: ...d by Fuzzy rule when the intake air temp is 3 C or more above the setting temp the compressor is turned off When below the setting temp the compressor is turned on Compressor ON Temp Setting Temp Compressor OFF Temp Setting Temp 3 C At the beginning of Fuzzy mode operation the setting temperature is automatically selected according to the intake air temp at that time 20 C Intake Air Temp Intake Ai...

Page 17: ... heating cycle operations are different Chaos Natural Wind Mode When the Chaos Natural Wind mode is selected and then operated the high medium or low speed of the air flow mode is operated for 2 15 sec randomly by the Chaos Simulation Jet Cool Mode Operation C O Model If the Jet Cool key is input at any operation mode while in appliance operation the Jet Cool mode operates In the Jet Cool mode the...

Page 18: ...rried out in cooling mode with the setting temperature 22 C and the high speed of airflow While in forced operation the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation Forced Operation H P Model To operate the appliance by force in case that the remote control is lost the forced operation selection switch is on the main unit of the appl...

Page 19: ...pipe from frosting When the indoor pipe temp is 7 C or higher after 3 min pause of the compressor the compressor and the outdoor fan is turned on according to the condition of the room temperature Buzzer Sounding Operation When the appliance operation key is input by the remote control the short beep beep sounds When the appliance pause key is input by the remote control the long beep sounds When ...

Page 20: ...es 3sec twice 3sec 3sec once 3sec 3sec 3sec 2 3 5 8 Error Code Error LED Indoor body operation LED Error contents SVC check point Indoor suction temperature thermistor open short Indoor pipe temperature thermistor open short Indoor TH ass y check Outdoor TH ass y check Resetting of remocon operating mode Communication line circuit check Outdoor suction temperature thermistor open short Outdoor pip...

Page 21: ...ined A place where noise prevention is taken into consideration Do not install the unit near the door way Ensure the spaces indicated by arrows from the wall ceiling fence or other obstacles 2 Outdoor unit If an awning is built over the unit to prevent direct sunlight or rain exposure be careful that heat radiation from the condenser is not restricted There should not be any animals or plants whic...

Page 22: ...0mm dia holecore drill Line according to the arrows marked on lower the left and the rght side of the Installation Plate The meeting point of the extended line is the center of the hole Drill the piping hole at either the right or the left and the hole should be slightly slant to the out door side Installation Plate marking off line Thread Weight Type A screw ø70mm ø70mm 5 7mm A A A A ø70mm ø70mm ...

Page 23: ... pipes Some refrgerant gas may leak when the flare nuts are removed from the indoor unit as some gas is charged to prevent the inside of the pipe from rusting Fit the copper pipe end into the Bar of flare tool about 0 0 5mm higher See illustration Flare the pipe ends 4 Tape the flaring portion to protect it from the dust or damages 90 Slanted Pipe cutter Rough Reamer Pipe Point down A Bar Copper p...

Page 24: ...o not connect the cable to the indoor unit Make a small loop with the cable for easy con nection later 5 Tape the tubing drain hose and the connecting cable Be sure that drain hose locates at the lowest side of the bundle Locating at the upper side can be a reason that drain water overflows drain pan inside the unit Installation plate Pull Pull Connecting cable Gas side piping Liquid side piping D...

Page 25: ...y moving it in left and right 7 Connecting the pipings to the indoor unit Align the center of the pipings and sufficiently tighten the flare nut with fingers Finally tighten the flare nut with torque wrench until the wrench clicks Wrench tightening the flare nut with forque wrench ensure the direction for tightening fol lows the arrows on the wrench 8 Wrap the insulation material around the con ne...

Page 26: ...door unit onto the upper portion of installation plate Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate Ensure the hooks are properly seated on the installation plate by moving it in left and right Drain hose Tubing holder Taping Piping Push 2 Hook 1 Connecting cable Drain hose Press the lower left and right side of the unit against the Installa...

Page 27: ...oor unit 1 Align the center of the pipings and sufficiently tighten the flare nut with fingers 2 Finally tighten the flare nut with torque wrench until the wrench clicks When tightening the flare nut with torque wrench ensure the direction for tightening follows the arrow on the wrench Pipe Size Torque Liquid Side 1 4 1 8kg m Gas Side 3 8 4 2kg m Gas Side 1 2 5 5kg m ...

Page 28: ...ordance with local codes 7 Refix the cover control to the original position with the screw 8 Use lock nuts to secure the conduit tubes 1 Separately wire the high and low voltage line 2 Use heat proof electrical wiring capable of withstanding temperature up to 167 F 3 Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit For example Type...

Page 29: ...d wire about 25mm 15 16 2 Using a screwdriver remove the terminal screw s on the terminal plate 3 Using pliers bend the solid wire to from a loop suit able for the terminal screw 4 Shape the loop wire properly place it on the terminal plater and tighten securely with the terminal screw using a screwdriver For strand wiring 1 Cut the wire end with a wire cutter or wire cutting pli ers then strip th...

Page 30: ...Press the Grille toward the chassis until it will be back into place CAUTION CAUTION Air Conditioner Circuit Breaker Use a circuit breaker or time delay fuse Connecting cable Main power source If a power plug is not to be used provide a circuit breaker between power source and the unit as shown below Model 18K 1ø 230 208V 15A 24K 1ø 230 208V 20A Power source Fuse or breaker Capacity Be sure to ref...

Page 31: ... of the drain outlet should be routed above the ground Secure the drain hose appropriately 2 In cases where the outdoor unit is installed below the indoor unit perform the following Tape the piping drain hose and connecting cable from down to up Secure the tapped piping along the exterior wall using saddle or equivalent 3 In cases where the Outdoor unit is installed above the Indoor unit perform t...

Page 32: ...port nut and connect the gauge manifold and the vacuum pump to the service port by the charge hose 4 Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below 76cmHg 5 Disconnect the charge hose and fit the nut to the service port Tightening torque 1 8kg m 6 Remove the valve stem nuts and fully open the stems of the 2 way and 3 way valves with a hexagon wrench 7 Ti...

Page 33: ...gth A Height C Height Model STANDARD CONNECTION TYPE Charge am t g LENGTH m A B C D per 1m LM 1830C2L M 7 5 7 15 7 15 20 LM 1830H2L M LM 2430C2L M 7 5 7 15 7 15 20 LM 2430H2L M A B mean indoor unit higher located than outdoor unit C D mean outdoor unit higher located than indoor unit Charge amount per 1m ...

Page 34: ...mance 1 Measure the temperature of the intake and discharge air 2 Ensure the difference between the intake temperature and the discharge one is more than 8 C 1 Connection of power supply 1 Connect the power supply cord to the inde pendent power supply 2 Prepare the remote control Insert two batteries provided Remove the battery cover from the remote con troller Slide the cover according to the arr...

Page 35: ...s when the button is pressed again OPERATION MODE SELECTION BUTTON Used to select the operation mode ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature INDOOR FAN SPEED SELECTOR Used to select fan speed in four steps low medium high or CHAOS JET COOL Used to start or stop the speed cooling Speed cooling operates super high fan speed in cooling mode CHAOS SWING BUTTON Used to stop...

Page 36: ...ation TIME SETTING BUTTONS Used to adjust the time TIMER SET CANCEL BUTTONS Used to set the timer when the desired time is obtained and to cancel the Timer operation SLEEP MODE AUTO BUTTON Used to set Sleep Mode Auto operation AIR CIRCULATION BUTTON Used to circulate the room air without cooling or heating turns indoor fan on off ROOM TEMPERATURE CHECKING BUTTON Used to check the room temperature ...

Page 37: ... Set the up and down air discharge louver to open position horizontally by finger pressure Remove the securing screws To remove the Grille pull the lower left and right side of the grille toward you slightly tilted and lift it straight upward 1 To remove the sensor housing connect step motor conductor with sensor holder Motor Evaporator P C B Screw Step Motor Conductor Motor Conductor Sensor Condu...

Page 38: ...or and the holder eva Unhook the tab on the right inside of the chas sis at the same time slightly pull the evapora tor toward you until the tab is clear of the slot 5 To remove the Cross Flow Fan Loosen the screw securing the cross flow fan to the fan motor do not remove Lift up the right side of the cross flow fan and the fan motor separate the fan motor from the cross flow fan Remove the left e...

Page 39: ...ransfering clockwise counter clockwise connected manifold gauge Evacuation Open Open Open Servicing with charging cylinder Gas charging Open Open Open Servicing with charging cylinder Pressure check Open Open Open Servicing with charging cylinder Gas releasing Open Open Open Servicing with charging cylinder 39 2 way 3 way Valve 3 2 1 4 5 6 Flare nut To piping connection Open position Closed positi...

Page 40: ...rom the hose 5 Set the liquid side valve to the closed position 6 Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg cm2 g 7 Immediately set the gas side valve to the closed position Do this quickly so that the gauge ends up indi cating 1kg g 8 Disconnect the charge set and mount the liquid side and gas side valve caps and the service port nut Use torque wren...

Page 41: ...the Low handle of the gauge turn off the vacuum pump and confirm that the gauge nee dle does not move approximately 5 minutes after turning off the vacuum pump 6 Disconnect the charge hose from the vacuum pump Vacuum pump oil If the vacuum pump oil becomes dirty or deplet ed replenish as needed 7 Mount the valve caps and the service port caps 8 Apply steps from 1 to 7 to each unit A unit B unit by...

Page 42: ...i cient wait approximately 1 minute and then repeat the procedure pumping down pin 4 Immediately disconnect the charge hose from the gas side valve s service port Stopping partway will allow the gas to be dis charged If the system has been charged with liquid refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose 5 Mount the valve stem nuts and t...

Page 43: ... 5 6 0 kg cm2 G at normal condition 2 The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty 43 Cycle Troubleshooting Guide Temp difference approx 0 C Current less than 80 of rated current Temp difference approx 8 C Current less than 80 of rated current Temp difference less than 8 C Current over the rated current Temp difference over 8 C Temp...

Page 44: ...2 Step 3 Outdoor Operation Mode COMP 40 B only COMP 60 A only COMP 100 A B together 18k Max 19k Cooling Qs 7k Qs 12k 12k Qs Heating Qs 9k 12k Qs 21k Max 23k Cooling Qs 9k Qs 12k 12k Qs Heating Qs 9k 12k Qs 30k Max 33k Cooling Qs 12k Qs 19k 19k Qs Heating Qs 12k Qs 19k 19k Qs Outdoor Max capacity 14k 14k combination 18k 19kcombination 21k 23k combination 30k 33k combination ...

Page 45: ...or ZNRØ1J Outdoor PCB Ass y Check the connection housing for contacting Connector related to CN DC AC Display PWB Ass y Check Check each load Indoor Outdoor Fan Motor Compressor Stepping Motor etc and contacting condition of related connector PCB Board Operation Check Items Power Transformer Outdoor unit Input Voltage Output Voltage IC01D 7812 Output Indoor Outdoor unit IC02D 7805 Output Indoor Ou...

Page 46: ...int the wind speed is not controlled by the remote controller When operated in the Sleeping Mode the wind speed is set to the low speed by force Check DISP PWB Ass y Voltage between CN DISP1 DC 5V When the detect switch double key inside the remote controller door is fault it is impossible to operate temperature regulating and wind speed selecting Check the connecting circuit between the remote co...

Page 47: ...lose as to be effected by the temperature of Heat Exchanger EVA When the sensor circuit for indoor temperature and connector are in bad connection or are not engaged Compressor Outdoor Fan is stopped Check the related circuit of R02H 12 1K R01H 1 0K R04H 6 2K R03H 1 0K Indoor unit Check the indoor temperature sensor is disconnected or not About 10kΩ at 25 C Check if connection line Indoor Outdoor ...

Page 48: ...oor unit Check the connection of CN MOTOR check the operation of blower by manual Correct connection line 4 When indoor Fan does not operate or ON OFF led of display blinks 8 times Check POLY S W in indoor PCB Ass y If it is opened If it is shorted Exchange Indoor PCB Ass y Check the outdoor PCB Ass y Bad connection Good connection ...

Page 49: ...ndition of CN U D Connector Check the soldering condition on PWB of CN U D Connector If there are no problems after above checks Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver 5 When Vertical Louver does not operate Check the operating circuit of the Vertical Louver Confirm that there is DC 12V between pin RED of CN U D and GND...

Page 50: ... 28 C Check the connector of intake and pipe sensor thermistors Check the related circuit of R02H 12 1K R01H 1 0K R04H 6 2K R03H 1 0K Check the indoor room temperature is disconnected or not about 10KΩ at 25 C Check the indoor pipe temperature is disconnected or not about 5KΩ at 25 C Turn ON Main Power Check if connection line Indoor Outdoor is complied with Wiring Diagram Check Outdoor Unit PCB A...

Page 51: ...e control data can be transmitted or received between indoor and outdoor unit with one signal cable If the data be disturbed by any noise level and misconnection the unit will be operated incorrectly In this case the indoor unit blinks the operation and operation LED on display and indoor fan outdoor fan COMP are not operated The unit can be reoperated by On Off control of Remocon Check Outdoor Un...

Page 52: ... 52 Electronic Control Device 1 Indoor MAIN P C B ASM ...

Page 53: ... 53 2 Outdoor MAIN P C B ASM ...

Page 54: ... 54 3 Display Ass y ...

Page 55: ... 55 Schematic Diagram 1 Indoor ...

Page 56: ... 56 2 Outdoor ...

Page 57: ...d View and Replacement Parts List 1 Indoor Unit LM 1830C2L M LM 1830H2L M 135312 268712 267110 135311 354210 152313 249951 152302 135511 159901 342800 131410 733010 346812 263230 268714 352150 146811 35211B 359011 ...

Page 58: ...6323A20003A 6323A20003A 6323A20003A 6323A20003A 6323A20003A 6323A20003A R 267110 REMOTE CONTROLLER ASSY 6711A20039M 6711A20025N 6711A20025M 6711A20039N 6711A20026U 6711A20026T R 268712 PWB PCB ASSY DISPLAY 6871A30009C 6871A30009P 6871A30009P 6871A30009C 6871A30009P 6871A30009P R 268714 PWB PCB ASSY MAIN 6871A10035K 6871A10035K 6871A10035K 6871A10035J 6871A10035J 6871A10035J R 342800 BEARING 3H0282...

Page 59: ... 59 2 Indoor Unit LM 2430C2L M LM 2430H2L M 135312 268712 267110 135311 354210 249951 152302 135511 159901 1 159901 1 342800 131410 733010 346812 263230 268714 352150 146811 35211B 359011 152313 ...

Page 60: ...0143L 4995A20143L 4995A20143L 4995A20143K 4995A20143K R 263230 THERMISTOR ASSY 6323A20003A 6323A20003A 6323A20003A 6323A20003A 6323A20003A R 267110 REMOTE CONTROLLER ASSY 6711A20039M 6711A20025N 6711A20025M 6711A20039N 6711A20039N R 268712 PWB PCB ASSY DISPLAY 6871A30009E 6871A30009Q 6871A30009Q 6871A30009E 6871A30009E R 268714 PWB PCB ASSY MAIN 6871A10035L 6871A10035M 6871A10035M 6871A10035M 6871...

Page 61: ...581 330870 135311 3 146811 346810 135500 1 146811 135311 2 131410 352380 352150 35211B 263230 2 263230 1 147581 152302 135314 268712 268717 135316 354210 144710 2 146811 146811 144710 1 147581 352116 352115 249951 249941 266090 268715 159830 268716 Indoor Unit L2 C243AL1 ...

Page 62: ...X ASSY INDOOR 4995A20372P R 249941 CONTROL BOX INDOOR 4994A10046A R 268715 PWB PCB ASSY MAIN AC 6871A20380D R 268716 PWB PCB ASSY MAIN DC 6871A20381H R 266090 H V ASSEMBLY 6609A10003S R 263230 1 THERMOSTOR ASSY 6323AQ6226T R 263230 2 THERMOSTOR ASSY 6323A20004N R 268712 PWB PCB ASSY DISPLAY 6871A20388B R 267110 REMOTE CONTROLLER ASSY 6711A20073E R 330870 DRAIN PAN ASSY 3087A30004A R 346810 MOTOR A...

Page 63: ...M 1830C2L M LM 2430C2L M L2 C243AL1 435512 554030 137213 435311 437210 W0CZZ 1 261704 W0CZZ 2 263230 268716 559010 346810 447910 435511 649950 268717 W52110 2 W52110 1 430410 349600 554160 552203 1 552203 2 552203 3 266310 ...

Page 64: ...A30004A R 346810 MOTOR ASSY OUTDOOR 4681A20008D 4681A20008D 4681A20008D R 349600 MOUNT MOTOR 4960AP1361A 4960AP1361A 4960AP1361A R 552203 1 VALVE SERVICE 2A00393S 2H01890P 2H01890P R 552203 2 VALVE SERVICE 2A00393K 2H01890Q 2H01890Q R 552203 3 VALVE SERVICE 2H02479J 2H02479J 2H02479J R 554030 CONDENSER ASSY BENT 5403A20049D 5403A10009F 5403A10009F R 554160 COMPRESSOR ASSY SET 2520UKAK2DA 2520UKRK2...

Page 65: ...2L M 435512 554030 435300 137213 1 137213 2 135301 349480 437210 559010 346811 447910 435511 561410 2 561410 1 430410 349600 554160 552202 552203 1 552203 2 552203 3 W0CZZ 1 261704 W0CZZ 2 263230 268716 649950 W52110 2 W52110 1 268717 266310 ...

Page 66: ...2202 VALVE REVERSING 5220AR3084A 5220AR3084A R 552203 1 VALVE SERVICE 2A00393S 2H01890P R 552203 2 VALVE SERVICE 2A00393K 2H01890Q R 552203 3 VALVE SERVICE 2H02479J 2H02479J R 554030 CONDENSER ASSY BENT 5403A20049B 5403A10009D R 554160 COMPRESSOR ASSY SET 2520UKAK2DA 2520UKRK2EA R 559010 FAN ASSY PROPELLER 1A00195B 1A00195B R 561410 1 COIL ASSY REVERSING 6141AR3509C 6141AR3509C R 561410 2 COIL ASS...

Page 67: ...P No 3828A20097A July 2005 Printed in Korea ...

Reviews: