Service Manual 57
Installation
(7) Maximum Length of Pipe and Freon Extra Charge
INDOOR UNIT
INDOOR UNIT
OUTDOOR UNIT
B(Length)
D(Length)
A(Height)
C(Height)
Capacity
STANDARD
CONNECTION TYPE
Charge am't(g)
(Btu/h)
LENGTH(m)
A
B
C
D
per 1m
~7000
7.5
7
15
7
15
20
~9000
7.5
7
15
7
15
20
~12000
7.5
7
15
7
15
20
~18000
7.5
10
20
10
20
20
~24000
7.5
15
30
15
30
30
** A, B mean indoor unit higher located than outdoor unit.
C, D mean outdoor unit higher located than indoor unit.
Charge amount per 1m
CAUTION: Capacity is based on standard length and maximum allowance length is on the
basis of reliability. Oil trap should be installed every 5~7 meters (16.4~23.0ft).