50 Multi Air Conditioner
Installation
Connecting
cable
Drain hose
Indoor unit tubing
Flare nut
Pipings
Spanner
Torque wrench
Plastic bands
Insulation material
Press the lower left and right side of the unit
against the Installation Plate until the hooks
engage with their slots (sound click).
6. Indoor unit installation.
• Hook the indoor unit onto the upper position of
the installation plate. (Engage the two hooks of
the rear top of the indoor unit with the upper
edge of the installation plate.)
Ensure the hooks are properly seated on the
installation plate by moving it in left and right.
7. Connecting the pipings to the indoor unit.
• Align the center of the pipings and sufficiently
tighten the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench
until the wrench clicks.
Wrench tightening the flare nut with forque
wrench, ensure the direction for tightening fol-
lows the arrows on the wrench.
8. Wrap the insulation material around the con-
necting portion.
CAUTION
: Take care to arrange the
pipings, drain hose and cables as the
right upper picture for inserting it into the
indoor unit and refixing the tubing holder
easily.
Wrap the insulation material around the connecting
portion.
Pipe Size
Torque
Liquid Side (1/4")
1.8kg m
Liquid Side (3/8")
4.2kg m
Gas Side (1/2")
5.5kg m
Gas Side (5/8")
6.6kg m
Summary of Contents for L2-C242GL0
Page 13: ...Service Manual 13 Dimensions 900 1 225 370 L3 C482LL0 ...
Page 19: ...Service Manual 19 Electronic Control Device Display P C B ASM ...
Page 21: ...Service Manual 21 Schematic Diagram L2 C362LL0 ...
Page 22: ...22 Multi Air Conditioner Schematic Diagram Outdoor Unit L3 C362LL0 ...
Page 23: ...Service Manual 23 Schematic Diagram L3 C482LL0 ...
Page 75: ...P No 3828A20156P January 2005 Printed in Korea ...