Installation
Installation Manual
11
3) Piping length and the elevation
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
If piping length is more than 10m
Outdoor unit
Indoor unit
B
CAUTION:
• Rated performance for refrigerant line length of:7.5m
• Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.
Model
*Additional
refrigerant
(g/m)
Pipe Size
mm(inch)
Length A(m)
Elevation B(m)
Gas
Liquid
Standard
Max.
Standard
Max.
JT-C186PLE0
12.7 (1/2")
6.35(1/4")
7.5
30
5
20
25
JT-C246PLE0
15.88 (5/8")
15.88 (5/8")
6.35(1/4")
7.5
50
5
30
25
JT-C368NLE0
9.52(3/8")
7.5
50
5
30
30
JT-C488MLE0
19.05(3/4") 9.52(3/8")
7.5
50
5
30
40