Chapter 7. DEDICATED INSTRUCTIONS FOR SPECIAL MODULES
7 - 4
7.2.2 Write to Buffer Memory
⋯
RPUT
<Format>
[ RPUT SI St S D n SS ]
Format
Description
Available data type
SI
Upper(AB) : Code value for RTD input module
G3F - RD3A : 04h
G4F - RD2A : 84h
Lower(CD) : Slot No. of the communications module of the local station
Setting range : 0 to 7
Integer
St
Upper(EF) : Slot No. of the RTD
Input module loaded onto the remote station
Setting range : 0 to 31
Lower(GH) : Station No. of the communications module loaded onto the
remote station(RBEA)
Setting range : 0 to 63
Integer
S
Head address of the device to be stored the data write.
M,P.K.L.T,C,D, #D
D
Head address of the specific module's buffer memory to write data
Integer
n
Word number of data to be write
Integer, D
SS
Area used for indicating the status information during link
M,P.K.L.T,C,D, #D
REMARK
If the content is write to the buffer memory of the RTD input module by use of RPUT, be sure to make the
program so that execution condition can transit from 0 to 1(Rising Edge : )
Otherwise, The content in the buffer memory of the RTD input module will not be changed with a new data.
<Format>
[Configuration]
[Write to buffer memory]
1) The content in the D100 to D108(9 words) of the devices in the CPU module
2) Will be written to addresses 0 to 8 of the buffer memory of the RTD input module, and
3) Information on the communication status is stored to D0
[program]
Execution condition
for RPUT
GM3-
PA1A
GM3-
CPUA
G3I-
A24A
G3I-
A22A
G3Q-
RY4A
G3Q-
RY2A
G3L-
FUEA
GM3-
PA1A
G3L-
RBEA
G3I-
D24A
G3F-
RD3A
Slot 4
Slot 1
Station No. 11
(0Bh)
condition for