Chapter 6. BUFFER MEMORY CONFIGURATION AND FUNCTIONS
6 - 1
Chapter 6. BUFFER MEMORY CONFIGURATION AND FUNCTIONS
The RTD input module a PLC CPU and buffer memories for data communications.
6.1 Buffer Memory Configuration
The followings describe buffer memory configuration.
6.1.1 G3F-RD3A Buffer Memory
Address
(Decimal)
Function
Descriptions
Default
Setting
Read /
Write
0
Channel enable/disable specification
Bit On(1):enable, Bit Off(0):disable
disable
R/W
1
Channel 0 Specifying RTD type
“
2
Channel 1 Specifying RTD type
“
3
Channel 2 Specifying RTD type
“
4
Channel 3 Specifying RTD type
“
5
Channel 4 Specifying RTD type
“
6
Channel 5 Specifying RTD type
“
7
Channel 6 Specifying RTD type
“
8
Channel 7 Specifying RTD type
0 : Pt 100
1: JPt 100
“0”
(Pt 100)
“
9
Detected temp. value of channel 0
Read only
10
Digital conversion value of channel 0
“
11
Error code of channel 0
“
12
Detected temp. value of channel 1
“
13
Digital conversion value of channel 1
“
14
Error code of channel 1
“
15
Detected temp. value of channel 2
“
16
Digital conversion value of channel 2
“
17
Error code of channel 2
“
18
Detected temp. value of channel 3
“
19
Digital conversion value of channel 3
“
20
Error code of channel 3
“
21
Detected temp. value of channel 4
“
22
Digital conversion value of channel 4
“
23
Error code of channel 4
“
24
Detected temp. value of channel 5
“
25
Digital conversion value of channel 5
“
26
Error code of channel 5
“
27
Detected temp. value of channel 6
“
28
Digital conv ersion value of channel 6
“
29
Error code of channel 6
“
30
Detected temp. value of channel 7
“
31
Digital conversion value of channel 7
“
32
Error code of channel 7
Detected temperature value
: A value of 10 times of the
real temperature is read.
Digital conversion value
: (Detected temperature value
+
2000) X 2
When the detected value of temp.
is used as the current value, the value
means the converted value, which is
equal to the input range of the current
value from 0 to 16,000.
Error code value
16: A disconnection detected
17: B disconnection detected
18: b disconnection detected,
A and B disconnection
Simultaneously detected.
19: Indicates that the detected
temperature is outside the input
range(-200~600.0
℃
) of the
RTD.
-
“
33
SET data enable/disable specification
Bit On(1) : The contents at address
0~8 are changed with
new values.
Bit Off(0): The contents at address
0~8 remains with the
previous value.
No
setting
values
R/W
34
Channel run information
Bit On(1):Run, Bit Off(0): Stop
-
Read only
35
Error information specifying RTD type
Bit On(1):Outside the setting range
Bit Off(0): Normal
-
“