background image

GAS REQUIREMENTS

1 8

Safety Instructions

Installation Instructions

Operating Instruction

Troubleshooting Tips

Customer Service

When a rigid pipe is used it should be 1/2 inch IPS.
When acceptable to the gas supplier and local codes, 3/8-
inch approved tubing may be used for lengths under 6.1
m (20 feet). For lengths over 6.1m (20 feet), larger
tubing should be used. Pipe-joint compounds resistant to
the action of L.P. gas must be used.

Gas Dryers

NOTE : The gas service to a gas dryer must conform
with the local codes and ordinances or, in the absence
of local codes and ordinances, with the latest edition
of the National Fuel Gas Code  ANSI Z223.1/NFPA
54 or the CAN/CGA-B149, National Gas Installation
Code.

L.P (Liquefied Petroleum) Gas, 2,500 Btu/ft

3

(93.1

MJ/m

3

), service  must be supplied at  8~13 in. water

column pressure.

NOTE : DO NOT connect the dryer to L.P. Gas
Service without converting the gas valve.

L.P. gas conversion:

- Conversion must be made by a qualified technician. 

See gas valve burner base for gas conversion kit part
number. 

NOTE : When connecting to a gas line, an equipment
shutoff valve must be installed within 6 feet (1.8m) of
the dryer. An 1/8 in. N.P.T. pipe plug must be
installed as shown. Refer to Fig.1 

Supply line requirements:

Provide a rigid gas supply line to the dryer location.

An individual manual shutoff valve must be installed

within 1.8m (6 feet) of the dryer in accordance with the
National Fuel Gas Code ANSI Z223.1*.

WARNING

To reduce the risk of gas leaks, fire or
explosion:

• The dryer must be connected to the

type of gas as shown on the nameplate
located in the door recess.

• Use a new flexible stainless steel

connector.

• Use pipe joint compound insoluble in

L.P. (Liquefied Petroleum) Gas, or
Teflon tape, on all pipe threads.

• Purge air and sediment from gas supply

line before connecting it to the dryer.
Before tightening the connection, purge
remaining air from gas line to dryer
until odor of gas is detected. This step
is required to prevent a gas valve
contamination.

• Do not use an open flame to check for

gas leaks. Use a non-corrosive leak
detection fluid.

• Any dis-assembly requiring the use of

tools must be performed by an
authorized qualified service person.

Summary of Contents for DLE0332

Page 1: ...owed Additional spacing should be considered for installation and servicing Additional clearances might be required for wall door and floor moldings Additional spacing of 1 in 2 5 cm on all sides of the dryer is recommended to reduce noise transfer For closet installation with a door minimum ventilation openings in the top and bottom of the door are required Louvered doors with equivalent ventilat...

Page 2: ...ly will void warranty NOTE Venting materials are not supplied with the dryer obtain locally DO DON T Step 1 Position and Level the Dryer For further assistance refer to section on Location Requirements Place the dryer in position and adjust the legs until the dryer is level from side to side and front to back Level floor Maximum slope under entire dryer should not be more than 2 5cm 1 inch If slop...

Page 3: ... not damage the pipe thread when removing the cap 3 Connect to gas supply pipe using a new flexible stainless steel connector 4 Tighten all connections securely Turn on gas and check all pipe connections internal external for gas leaks with a non corrosive leak detection fluid 5 For L P Liquefied Petroleum gas connection refer to section on Gas Requirements 1 New Stainless Steel Flexible Connector...

Page 4: ...an all purpose cleaner or a detergent and water solution and a damp cloth to remove shipping dust from inside the dryer drum Step 6 Plug In the Dryer Refer to section on Electrical Requirements and connect the dryer to an electrical power source Step 7 Check Installation Heat Source Check Electric Dryers Close the loading door and start the dryer in a heat setting refer to the Operating Instructio...

Page 5: ...roceed as follows 1 1 2 2 3 3 1 1 Remove screw exhaust duct 2 2 Detach and remove the bottom left or right side knockout as desired 3 3 Reconnect the new duct 11 in 28cm to the blower housing and Fixing the duct to the base 4 4 Pre assemble 4 elbow with 4 duct Wrap duct tape around joint 5 5 Insert duct assembly elbow first through the side opening and connect the elbow to the dryer internal duct ...

Page 6: ...cal Connections Electric Dryer Only must be a 4 wire connection 3 Venting Dryer MUST be exhausted to the outdoors The dryer can be exhausted to the outdoors through the back left right or bottom panel Gas dryers cannot be exhausted out the right side because of the burner housing The dryer exhaust duct must be secured to the mobile home structure Exhaust ducts MUST NOT be connected with sheet meta...

Page 7: ...can be moved from its normal location when necessary The power cord pigtail connection between wall receptacle and dryer terminal block IS NOT supplied with dryer Type of pigtail and gauge of wire must conform to local codes and with instructions mentioned on the following pages The method of wiring the dryer is optional and subject to local code requirements Refer to examples on next page Electri...

Page 8: ...are copper wire of power supply cord 3 3 4 in 1 9 cm UL listed strain relief 4 Center silver colored terminal block screw 5 Neutral grounding wire green 6 Neutral wire white 5 Connect the other wires to outer terminal block screws Tighten screws 6 Tighten strain relief screws 7 Insert tab of terminal block cover into slot of dryer rear panel Secure cover with hold down screw IMPORTANT A 4 wire con...

Page 9: ... slot of dryer rear panel Secure cover with hold down screw 1 External ground connector 2 Green or bare copper wire of power supply cord 3 3 4 in 1 9 cm UL listed strain relief 4 Center silver colored terminal block screw 5 Neutral grounding wire green 6 Neutral wire white 1 3 wire receptacle NEMA type 10 30R 2 3 wire plug 3 Neutral prong 4 Spade terminals with up turned ends 5 3 4 in 1 9 cm UL ap...

Page 10: ...res to outer terminal block screws Tighten screws 4 Tighten strain relief screws 5 Insert tab of terminal block cover into slot of dryer rear panel Secure cover with hold down screw 6 Connect a separate copper ground wire from the external ground connector screw to an adequate ground 1 Loosen or remove center terminal block screw 2 Place the hooked end of the neutral wire white or center wire of p...

Page 11: ...lug on the power cord should be plugged directly into a polarized three slot effectively grounded receptacle rated 120 Volts AC alternating current 15 Amps Refer to Figure 22 to determine correct polarity of the wall receptacle WARNING To reduce the risk of fire electric shock or personal injury all wiring and grounding MUST confirm with the latest edition of the National Electrical Code ANSI NFPA...

Page 12: ...ify the plug provided with the dryer unit if it will not fit the outlet have a proper outlet installed by a qualified electrician If the laundry room s electrical supply does not meet the above specifications and or if you are not sure the laundry room has an effective ground have a qualified electrician or your local electrical utility company check it and correct any problems STANDARD 120 VOLT 6...

Page 13: ... base for gas conversion kit part number NOTE When connecting to a gas line an equipment shutoff valve must be installed within 6 feet 1 8m of the dryer An 1 8 in N P T pipe plug must be installed as shown Refer to Fig 1 Supply line requirements Provide a rigid gas supply line to the dryer location An individual manual shutoff valve must be installed within 1 8m 6 feet of the dryer in accordance w...

Page 14: ...before installing your new dryer For best drying results recommended maximum length of exhaust system is shown in Table 1 To prevent backdraft when dryer is not in operation outer end of exhaust pipe must have a weather hood with hinged dampers obtain locally WARNING A clothes dryer produces combustible lint To reduce the risk of fire or gas accumulation the dryer MUST be exhausted to the outdoors...

Page 15: ...ameter flexible metal duct NOTE Deduct 6 feet 1 8 m for each additional elbow Use Only for Short Run Installations 0 1 2 3 4 65 feet 19 8 m 55 feet 16 8 m 47 feet 14 3 m 36 feet 11 0 m 28 feet 8 5 m 45 feet 13 7 m 35 feet 10 7 m 30 feet 9 1 m 25 feet 7 6 m 20 feet 6 1 m 55 feet 16 8 m 47 feet 14 3 m 41 feet 12 5 m 30 feet 9 1 m 22 feet 6 7 m 35 feet 10 7 m 27 feet 8 2 m 21 feet 6 4 m 17 feet 5 2 m...

Page 16: ...xhaust duct every one to two years as required thereafter The weather hood should be checked frequently to make sure the dampers move freely they are not pushed in and that nothing has been set against them This maintenance work should be done by a qualified service person Exhausting the dryer in hard to reach locations can be accomplished by installing the Flexible Metal Vent Kit available as opt...

Reviews: