Troubleshooting
64
Troubleshoo
ting
4
P410
Battery Under Voltage
Fault
Voltage level of the battery is
lower than the limitation and the
state is maintained for more than
10 minutes
Contact service center
P411
Battery MisWiring
Fault
Battery MisWiring
Contact service center
P412
Extention Kit Relay
Fault
Extention Kit Relay is melted
Contact service center
P460
Grid L1 Under Voltage Voltage level of the grid (L1) is
lower than the limitation
Automatically restart
within a Minute
P461
Grid L2 Under Voltage Voltage level of the grid (L2) is
lower than the limitation
Automatically restart
within a Minute
P462
Grid L3 Under Voltage Voltage level of the grid (L3) is
lower than the limitation
Automatically restart
within a Minute
P463
Grid L1 Over Voltage
Voltage level of the grid (L1) is
higher than the limitation
Automatically restart
within a Minute
P464
Grid L2 Over Voltage
Voltage level of the grid (L2) is
higher than the limitation
Automatically restart
within a Minute
P465
Grid L3 Over Voltage
Voltage level of the grid (L3) is
higher than the limitation
Automatically restart
within a Minute
P466
Grid L1 Over Voltage
10min
The 10minutes average voltage
level of the grid (L1) is higher than
the limitation
Automatically restart
within a Minute
P467
Grid L2 Over Voltage
10min
The 10minutes average voltage
level of the grid (L2) is higher than
the limitation
Automatically restart
within a Minute
P468
Grid L3 Over Voltage
10min
The 10minutes average voltage
level of the grid (L3) is higher than
the limitation
Automatically restart
within a Minute
P469
Grid Over Frequency
Frequency level of the grid is
higher than the limitation
Automatically restart
within a Minute
P470
Grid Under Frequency Frequency level of the grid is lower
than the limitation
Automatically restart
within a Minute
P471
Grid Anti Islanding
There was a power failure
Automatically restart
within a Minute
P472
Grid L1 DC Offset
Current
DC offset current is added on
grid(L1)
Automatically restart
within a Minute
P473
Grid L2 DC Offset
Current
DC offset current is added on
grid(L2)
Automatically restart
within a Minute