Appendix
Installation Manual
25
E
N
G
LIS
H
value
not used (set in 0% usually)
0 = Fan direction fixed for air conditioner product
state
1 = Fan direction auto for air conditioner product
Default Value
5) Fan direction auto input/output (Only applies to air conditioner)
Valid Range
SNVT_switch
( Index : 95 )
NV
Filed
Operation
Function
Fan direction auto command input
Input
Using NV
Network input variable : SNVT_switch nviSwing_n
Operation
It controls the fan direction of each product (air conditioner/ventilation)
Function
Fan direction auto status display
Output
Using NV
Network output variable : SNVT_switch nvoSwing_n
Operation
It monitors the fan direction of each product (air conditioner/ventilation)
6) Temperature setting input/output (Only applies to air conditioner)
Function
Set temperature range input
Input
Using NV
Network input variable : SNVT_switch nviSetPoint_n
Operation
It controls the temperature setting of each product (air conditioner/ventilation)
Function
Set temperature range status display
Output
Using NV
Network output variable : SNVT_switch nvoSetPoint_n
Operation
It monitors the set temperature of each product (air conditioner/ventilation)
At Cool mode : 18 ~ 30
°
C
At Heat mode : 18 ~ 30
°
C
At Dry mode and Fan mode : Not available
Default Value
Valid Range
SNVT_switch
( Index : 95 )
NV
Operation
Summary of Contents for BNU-LW