56
BACnet Gateway
Detailed Explanation of Object
18) User Mode (Setting)
Point number: 17
Object name: UserModeCommand_XXX (XXX: A/C unit address)
Object type: Multi-state Output
Meaning: This object is used to set the basic operation mode in vent and also additional operation
mode (quick fresh, energy efficiency, and heating).
Present_Value property:
0: Quick fresh
1: Energy saving
2: Heat
Remarks
: This object is for vent only, and will not apply if the property has not been set in the past.
19) User Mode (Status)
Point number: 18
Object name: UserModeStatus_XXX (XXX: A/C unit address)
Object type: Multi-state Input
Meaning : This object is used to monitor the basic operation mode in vent
Property_Value property:
0: Quick fresh
1: Energy saving
2: Heat
Reamark
: This object is for vent only, and will not apply if the property has not been in the past.