Operation
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation(cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated super-high speed for 30 min. at cooling mode operation.
• In the Jet Cool mode, the room temperature is controlled to the setting temperature, 18°C.
• When the sleep timer mode input while the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vane is reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Jet cool mode operation
On-Timer Operation
Off-Timer Operation
Off-Timer <=> On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature.
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.
• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is
carried out according to the set time.
■
CT1 control
• If the operating current reaches I1, the operating frequency of the compressor decrease.
• After decreasing the operating frequency by 1step, if operating current is below I1 for 60 seconds continuous-
ly, the operating frequency of compressor increase by 1step.
■
CT2 control
• If the operating current of the appliance reaches I2, the compressor stop instantly and 2 minutes later the
compressor restart again.
• If CT2 occurs 5 times within 1hour, the appliance turn off and display ERROR CODE 22.
❇
I1:Current of operating frequency down
I2: Current of compressor cut off
cf. I1 is set the lowest level between intial value and in case dectection of dc paeak current.
Control table
Protection from total current control
AS-W2465DH0
13.5
13.5
14
14
15.5
AS-W2465DH1
13.5
13.5
14
14
15.5
I1
Cooling
Heating
Cooling
Heating
Outdoor temp
≥
38°C
Outdoor temp < 38°C
I2
Model