- 29 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Operation
• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan
stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp
➲
Setting Temp+0.5°C
Compressor OFF Temp
➲
Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote control. While compressor is
off fan operates at low speed regardless of the setting.
• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C
≤
Intake Air Temp
➲
25°C
24°C
≤
Intake Intake Air Temp<26°C
➲
Intake Air Temp-1°C
18°C
≤
Intake Intake Air Temp<24°C
➲
Intake Air Temp-0.5°C
Intake Air Temp<18°C
➲
18°C
• While compressor off, the indoor fan repeats low airflow speed and stop.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp.
➲
Setting Temp+0.5°C
Compressor OFF Temp.
➲
Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Cooling Mode Operation
Healthy Dehumidification Mode Operation
• When the intake air temp r4°C above the setting temp, the compressor is turned off. When below
the setting temp, the compressor is turned on.
Compressor ON Temp.
➲
Setting Temp. +2°C
Compressor OFF Temp.
➲
Setting Temp. +4°C)
• While compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 27°C , it
operates with the low or setting speed. When the indoor pipe temp is between 20°C and 27°C, it operates with
Super-Low(while in sleep mode, with the medium airflow speed).
• While compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it
operates with the low airflow speed.
• While in defrost control, the indoor is outdoor fans are turned off.
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C after 35 minutes passed from
starting of heating operation and more than 4 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature
rises over 15°C even before 12 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C after 35 minutes passed
from ending of the first defrost and more than 4 minutes operation of compressor.
Heating Mode Operation
Defrost Control(Heating)
Summary of Contents for AS-W2465DH0
Page 70: ...P No 3828A20462R July 2008 ...