Service Manual 77
When compressor does not oprate normally.
■
Communication error between Indoor and Outdoor (Error Code
➄
)
Trouble 8-2
Does the operating LED in display PCB
Ass'y blink 5 times?
• Check the state of connecting cable
(3 line) bewteen indoor and outdoor unit .
• Check Fuse, Noise Filter, PTC, etc.
NO
YES
Is the voltage of BR/BK, RD AC220/240V in
Main PCB Ass'y.
• Electrical wiring diagram(Colors)
• Check the connecting state
of connectors in outdoor PCB Ass'y
• Check the Fuse of outdoor PCB Ass'y.
NO
YES
Is the connection of CN-T/Block and in
CN-AC/DC indoor P.C.B Ass'y is right?
Replace the PCB Ass'y.
• Main PCB Ass'y (Indoor/Outdoor)
• Control Box Ass'y.
• Reconnect the connectors.
• Check the PCB pattern(Resoldering).
NO
YES
Troubleshooting Guide