Service Manual 43
Operation
■
CT1 control
• If the operating current reaches I1, the operating frequency of the compressor decrease.
• After decreasing the operating frequency by 1step, if operating current is below I1 for 60 seconds continuous-
ly, the operating frequency of compressor increase by 1step.
■
CT2 control
• If the operating current of the appliance reaches I2, the compressor stop instantly and 2 minutes later the
compressor restart again.
• If CT2 occurs 5 times within 1hour, the appliance turn off and display ERROR CODE 7.
❇
I1:Current of operating frequency down
I2: Current of compressor cut off
cf. I1 is set the lowest level between intial value and in case dectection of dc paeak current.
Control table
■
DC Peak Current Error by a fault signal of IPM
• If the operating current of IPM reaches 35A ±3A, the compressor stop instantly.
• If DC PEAK occurs 5 times within 1 hour, the appliance turns off and display ERROR CODE 6.
■
DC Peak Current Error by the compressor lock
• If the DC LINK voltage below DC 140V occurs 5 times within 1 hour while the compressor is operating, the
appliance turns off and display ERROR CODE 6.
■
DC Peak Current Error by the Outdoor Fan Lock
• If it’s 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65°C while the compressor
is operating, the appliance turns off and display ERROR CODE 6.
Protection from total current control
Protection from DC Peak Current
I1
Cooling
Heating
Cooling
Heating
Outdoor temp
≥
38°C
Outdoor temp < 38°C
I2
Model
1
AS-W096U_0 Series
6.5
8.5
7
9
12
2
AS-W126U_0 Series
6.5
7.5
7
8
10
3
AS-W096U_1 Series
5.5
7
6
7.5
9
4
AS-W126U_1 Series
6
7.5
6.5
8
10