Service Manual 21
Installation
• Connect the cable to the indoor unit by connecting the wires to the terminals on the control board in
dividually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and
the terminal No. are the same as those of the indoor unit.)
The earth wire should be longer than the common wires.
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit
breaker or time
delay fuse.
CAUTION
The power connecting cable connected to
the indoor and outdoor unit should be
complied with the following specifications
(Type "B" approved by HAR or SAA).
The power cord connected to the "A" unit
should be complied with the following
specifications(Type "B" approved by HAR or
SAA).
7k, 9k
12k
18k
1.0
1.5
2.5
NORMAL CROSS
-SECTIONAL AREA
Grade
7k, 9k
12k
18k
1.0
1.5
2.5
NORMAL CROSS
-SECTIONAL AREA
Grade
(mm
2
)
(mm
2
)
CAUTION:
• The above circuit diagram is subject to change
without notice.
• Be sure to connect wires according to the wiring
diagram.
• Connect the wires firmly, so that not to be pulled
out easily.
• Connect the wires according to color codes by
referring the wiring diagram.
• When installing, refer to the circuit diagram on the
Control Box of Indoor Unit.
• When installing, refer to the wiring diagram on the
Control Cover Inside Outdoor Unit.
Connect the Cable to the Indoor Unit.
CAUTION:
If a power plug is not to be used, provide a circuit
breaker between power source and the unit as shown
below.
Summary of Contents for AS-W096QGG1
Page 48: ...48 Room Air Conditioner Schematic Diagram Schematic Diagram Electric Control Device Indoor ...
Page 49: ...Service Manual 49 Schematic Diagram Outdoor AS W096_Series AS W126_Series ...
Page 50: ...50 Room Air Conditioner Schematic Diagram Outdoor AS W186_Series AS W246_Series ...
Page 84: ...P No 3828A20195S February 2007 Printed in Korea ...