20 Room Air Conditioner
Installation
• Bundle the piping and drain hose together by
wrapping them with cloth tape over the range with-
in which they fit into the rear piping housing sec-
tion.
8. Reroute the pipings and the drain hose across
the back of the chassis.
9. Set the pipings and the drain hose to the back of
the chassis with the tubing holder.
• Hook the edge of tubing holder to tap on chassis
and push the bottom of tubing holder to be
engaged at the bottom of chassis.
10. Indoor unit installation
• Remove the spacer.
• Ensure that the hooks are properly seated on the
installation plate by moving it left and right.
Press the lower left and right sides of the unit against the
installation plate until the hooks engage into their
slots(clicking sound).
1. Align the center of the pipings and sufficiently
tighten the flare nut by hand.
2. Finally, tighten the flare nut with torque wrench
until the wrench clicks.
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the
arrow on the wrench.
mm
inch
kg.m
Ø6.35
1/4
1.8
Ø9.52
3/8
4.2
Ø12.7
1/2
5.5
Ø15.88
5/8
6.6
Ø19.05
3/4
6.6
Outside diameter
Torque
Drain hose
Vinyl tape(narrow)
Pipe
Wrap with
vinyl tape(wide)
Piping for
passage through
piping hole
Outdoor unit
Gas side piping
(Bigger diameter)
Liquid side
piping
(Smaller
diameter)
Torque wrench
Tubing holder
Drain hose
Connecting
cable
Connection of the Pipes-Outdoor
Summary of Contents for AS-W096QGG1
Page 48: ...48 Room Air Conditioner Schematic Diagram Schematic Diagram Electric Control Device Indoor ...
Page 49: ...Service Manual 49 Schematic Diagram Outdoor AS W096_Series AS W126_Series ...
Page 50: ...50 Room Air Conditioner Schematic Diagram Outdoor AS W186_Series AS W246_Series ...
Page 84: ...P No 3828A20195S February 2007 Printed in Korea ...