2008 Product Data
77
9. Capacity coefficient factor
Notes
❈
Equivalent pipe length = actual pipe number of band x 0.3
❈
Additional Refrigerant Charge
Example: For Model No. AS-W126ADR0 having 15m pipe length, additional refrigerant to be charged is
(15-7) x 20 = 160g
* Refer to the specification for the maximum pipe length of each model.
* 18k S5/S8 Chassis total piping length is 15m.
AS-W096ADR0
15
7
20(0.22)
AS-W0964GG1
15
7
20(0.22)
AS-W096E*H2
15
7
20(0.22)
AS-W096E1G0
15
7
20(0.22)
AS-W096F*G2
15
7
20(0.22)
AS-W096F1G2
15
7
20(0.22)
AS-W096U*H1
15
7
20(0.22)
AS-W126ADR0
15
7
20(0.22)
AS-W1264GG1
15
7
20(0.22)
AS-W126E*H2
15
7
20(0.22)
AS-W126E1G0
15
7
20(0.22)
AS-W126F*G2
15
7
20(0.22)
AS-W126F1G2
15
7
20(0.22)
AS-W126U*H1
15
7
20(0.22)
AS-W1863*H3
15
7
20(0.22)
AS-W1865DH2
15
7
20(0.22)
AS-W1865GG1
15
7
20(0.22)
AS-W1868*H1
15
7
20(0.22)
AS-W2463*H3
30
15
30(0.32)
AS-W2465DH2
30
15
30(0.32)
AS-W2468*H1
30
15
30(0.32)
AS-W306DGM0
50
30
30(0.32)
AS-W366DGM0
50
30
35(0.37)
Model No.
Max. Pipe
Length(m)
Max. Elevation
(m)
Additional
Refrigerant[g/m(oz/ft)]
CAUTION:
• Capacity is based on
standard length and
maximum allowance
length is on the basis
of reliability.
• Oil trap should be
installed every 5~7
meters.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
If piping length is more than 5m
Summary of Contents for AS-W0964GG1
Page 1: ...5RMA2 01A Inverter Single 50Hz R410A ...
Page 32: ...2008 Product Data 31 5 Dimensional drawings Indoor units 5 1 Indoor Units ...
Page 33: ...32 2008 Product Data 5 Dimensional drawings Indoor units ...
Page 34: ...2008 Product Data 33 5 Dimensional drawings Indoor units ...
Page 36: ...2008 Product Data 35 5 Dimensional drawings Indoor units ...
Page 40: ...2008 Product Data 39 5 Dimensional drawings Outdoor units 1 5 2 Outdoor Units ...
Page 41: ...40 2008 Product Data 5 Dimensional drawings Outdoor units 1 ...
Page 46: ...2008 Product Data 45 6 Wiring diagrams Indoor Unit Models AS W096ADR0 AS W126ADR0 ...
Page 48: ...2008 Product Data 47 6 Wiring diagrams Indoor Unit Models AS W1868 H1 Models AS W2463 H3 ...
Page 49: ...48 2008 Product Data 6 Wiring diagrams Indoor Unit Models AS W2468 H1 ...
Page 52: ...2008 Product Data 51 Models AS W096ADR0 AS W126ADR0 6 Wiring diagrams Outdoor units ...