104
2008 Product Data
14. Installation
Air Purging
Air purging
The air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling(or heating) efficiency drops.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system.
Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor
unit.
Air purging with vacuum pump
1. Preparation
• Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected
and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on
the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
2. Leak test
• Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi"
knob of the manifold valve must always be kept close.
• Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the
gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its
bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
1. Do a leak test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves.
Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
2. After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening the
charge hose connector at the nitrogen
cylinder. When the system pressure is
reduced to normal, disconnect the hose from
the cylinder.
Lo
Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas
cylinder(in vertical
standing position)
Pressure
gauge
Summary of Contents for AS-W0964GG1
Page 1: ...5RMA2 01A Inverter Single 50Hz R410A ...
Page 32: ...2008 Product Data 31 5 Dimensional drawings Indoor units 5 1 Indoor Units ...
Page 33: ...32 2008 Product Data 5 Dimensional drawings Indoor units ...
Page 34: ...2008 Product Data 33 5 Dimensional drawings Indoor units ...
Page 36: ...2008 Product Data 35 5 Dimensional drawings Indoor units ...
Page 40: ...2008 Product Data 39 5 Dimensional drawings Outdoor units 1 5 2 Outdoor Units ...
Page 41: ...40 2008 Product Data 5 Dimensional drawings Outdoor units 1 ...
Page 46: ...2008 Product Data 45 6 Wiring diagrams Indoor Unit Models AS W096ADR0 AS W126ADR0 ...
Page 48: ...2008 Product Data 47 6 Wiring diagrams Indoor Unit Models AS W1868 H1 Models AS W2463 H3 ...
Page 49: ...48 2008 Product Data 6 Wiring diagrams Indoor Unit Models AS W2468 H1 ...
Page 52: ...2008 Product Data 51 Models AS W096ADR0 AS W126ADR0 6 Wiring diagrams Outdoor units ...