Electrical Wiring
Installation Manual
57
ENGLISH
Connection method of the connecting cable (Example)
1. Make a hole appropriate for the passage of connection cable through on cap by tool.
2. After knocking out the holes, we recommend you paint the edges and areas around the edges using
the repair paint to prevent rusting
3. Pass the connecting cable through the hole.
4. Properly connect the cable on the terminal block.
5. Fix the connection cable with the cord clamp providing on the unit not to have strain at the terminal.
6. Finally, Fix the cap to the conduit panel.
WARNING
• Loose wiring may cause the terminal to overheat or result in unit malfunction.
• A fire hazard may also exist.
• Therefore, be sure all wiring is tightly connected.
Conduit
Model name
ARWN072BA2 ARWN144BA2 ARWN216BA2 ARWN288BA2 ARWN360BA2 ARWN432BA2
AWG
10
6
4
2
2
2
Conduit (inch)
2-Jan
1
1/4/01
1/4/01
1/4/01
1/4/01
Knockout Diameter (inch)
8-Jul
1-23/64
1-23/32
1-23/32
1-23/32
1-23/32
Model name
ARWN096DA2 ARWN192DA2 ARWN290DA2 ARWN390DA2 ARWN480DA2 ARWN432BA2
AWG
14
12
6
6
4
4
Conduit (inch)
2-Jan
2-Jan
1
1
1/4/01
1/4/01
Knockout Diameter (inch)
8-Jul
8-Jul
1-23/64
1-23/64
1-23/32
1-23/32